Some nanotec testing at BOA and Oxford temperature controllers

I tested the nanotec a little at BOA. Not finished yet, especially the homing bit.

I also added support for an Oxfolrd Mercury temperature controller. But this is not
working because my simulation for the Mercury is a different version then the one
the EPICS driver is for.
This commit is contained in:
2015-09-04 09:55:49 +02:00
parent e224004969
commit 047b0d8c74
5 changed files with 100 additions and 0 deletions

View File

@ -5,3 +5,4 @@ epicsEnvSet("EPICS_BASE","/usr/local/epics")
epicsEnvSet("ASYN","/usr/local/epics/support/asyn-4-18")
epicsEnvSet("MOTOR","/usr/local/epics/support/motor-6-7")
epicsEnvSet("LAKESHORE336","/usr/local/epics/support/lakeshore336")
epicsEnvSet("OXINSTCRYOJET","/usr/local/epics/support/OxInstCryojet-2-18-3")

View File

@ -0,0 +1,6 @@
file "$(MOTOR)/db/basic_asyn_motor.db"
{
pattern
{P, N, M, DTYP, PORT, ADDR, DESC, EGU, DIR, VELO, VBAS, ACCL, BDST, BVEL, BACC, MRES, PREC, DHLM, DLLM, INIT}
{KM36:nano:, 1, "m$(N)", "asynMotor", nano, 1, "m1", mm, Pos, 2.0, 0.1, .2, 0, 1, .2, .001, 3, 180, -180, "1"}
}

View File

@ -27,6 +27,16 @@ NanotecCreateController("nano","serial1",3,"1,10,9");
dbLoadRecords("$(ASYN)/db/asynRecord.db","P=KM36:,R=serial1,PORT=serial1,ADDR=0,OMAX=80,IMAX=80")
#------------------------------------------------------------------------------
# DANGER DANGER DANGER
#
#If the gearing factor in the substitutions file is wrong, then the nanotec
# drives badly. Not really a surprise. Thus the following procedure is required:
#
# - After editing the gearing ratios in the substitutions file, drive each motor
# carefully for a small amount and check if it is driving the correct amount by
# eye.
#------------------------------------------------------------------------------
cd ${TOP}/iocBoot/${IOC}
dbLoadTemplate "motor.substitutions.nanotec"

View File

@ -0,0 +1,46 @@
#!../../bin/linux-x86-debug/sinqEPICS
## You may have to change sinqEPICS to something else
## everywhere it appears in this file
< envPaths
cd ${TOP}
## Register all support components
dbLoadDatabase "dbd/sinqEPICS.dbd"
#dbLoadDatabase "dbd/sinq.dbd"
sinqEPICS_registerRecordDeviceDriver pdbbase
## Load record instances
#dbLoadRecords("db/xxx.db","user=koenneckeHost")
#---------- load Nanotec motor controller
#drvAsynIPPortConfigure("serial1", "narziss-ts:3002",0,0,0)
drvAsynIPPortConfigure("serial1", "boa-ts:3013",0,0,0)
NanotecCreateController("nano","serial1","1","4");
### Motors
dbLoadRecords("$(ASYN)/db/asynRecord.db","P=KM36:,R=serial1,PORT=serial1,ADDR=0,OMAX=80,IMAX=80")
#------------------------------------------------------------------------------
# DANGER DANGER DANGER
#
#If the gearing factor in the substitutions file is wrong, then the nanotec
# drives badly. Not really a surprise. Thus the following procedure is required:
#
# - After editing the gearing ratios in the substitutions file, drive each motor
# carefully for a small amount and check if it is driving the correct amount by
# eye.
#------------------------------------------------------------------------------
cd ${TOP}/iocBoot/${IOC}
dbLoadTemplate "motor.substitutions.nanoboa"
iocInit
## Start any sequence programs
#seq sncxxx,"user=koenneckeHost"

37
iocBoot/iocsinqEPICS/oxford.cmd Executable file
View File

@ -0,0 +1,37 @@
#!../../bin/linux-x86-debug/sinqEPICS
## You may have to change sinqEPICS to something else
## everywhere it appears in this file
< envPaths
cd ${TOP}
epicsEnvSet("STREAM_PROTOCOL_PATH", "$(OXINSTCRYOJET)/protocol/")
## Register all support components
dbLoadDatabase "dbd/sinqEPICS.dbd"
#dbLoadDatabase "dbd/sinq.dbd"
sinqEPICS_registerRecordDeviceDriver pdbbase
#----------
drvAsynIPPortConfigure("serial1", "localhost:7020",0,0,0)
dbLoadRecords("$(ASYN)/db/asynRecord.db","P=KM36:,R=serial1,PORT=serial1,ADDR=0,OMAX=80,IMAX=80")
cd ${TOP}/iocBoot/${IOC}
dbLoadRecords("$(OXINSTCRYOJET)/db/MercuryiTC-SCPI.template","P=KM36:,Q=HG,PORT=serial1")
#-------------------------------------------------------------------------------------
# This might have worked but our Mercury Simulation simulates something different
# then this is for.
#------------------------------------------------------------------------------------
iocInit
## Start any sequence programs
#seq sncxxx,"user=koenneckeHost"