R6-7 update.

This commit is contained in:
Ron Sluiter
2011-10-20 21:50:45 +00:00
parent 05b412312a
commit bdbf61cf99
+23
View File
@@ -138,6 +138,29 @@ Known Problems
some unknown reason) ignored and several subsequent status request
result in communication timeouts.
8) The OMS VME58 controller ignores its' Velocity Base command (VB) on the up
ramp of a home search operation; but not on the down ramp.
Modification Log for R6-7
=========================
1) Since the purpose of a Home search is to establish an absolute reference
position, the soft travel limits are not valid during a home search
operation. Accordingly, the motor record's soft travel limit error
check is now disabled during a home search operation.
In addition, the motor record was not setting an acceleration rate for
a home search. It now uses the home velocity (HVEL), base velocity
(BVEL) and accel. time (ACCL) fields to set a home acceleration rate.
File modified: motorApp/MotorSrc/motorRecord.cc
2) If an OMS VME58 board rebooted (as described under item #12 R6-6), it could
end up in an endless loop in the driver's send_mess() function. Add
a counter to prevent the endless loop.
File modified: motorApp/OmsSrc/drvOms58.cc
Modification Log from R6-5 to R6-6
==================================