Files
StreamGenerator/db/daq_common.db

208 lines
5.3 KiB
Plaintext

# EPICS Database for streamdevice specific to measurement channels
#
# Macros
# INSTR - Prefix
# NAME - the device name, e.g. EL737
# PORT - StreamGenerator Port
record(longout, "$(INSTR)$(NAME):FULL-RESET")
{
field(DESC, "Reset the DAQ")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) RESET")
}
################################################################################
# Status Variables
# record(stringin, "$(INSTR)$(NAME):MsgTxt")
# {
# field(DESC, "Unexpected received response")
# field(DTYP, "devDAQStringError")
# field(FLNK, "$(INSTR)$(NAME):INVALID-CONFIG")
# }
record(mbbi, "$(INSTR)$(NAME):STATUS")
{
field(DESC, "DAQ Status")
field(DTYP, "asynInt32")
field(INP, "@asyn($(PORT),0,$(TIMEOUT=1)) STATUS")
field(ZRVL, "0")
field(ZRST, "Idle")
field(ONVL, "1")
field(ONST, "Counting")
field(TWVL, "2")
field(TWST, "Low rate")
field(THVL, "3")
field(THST, "Paused")
# 4 should never happen, if it does it means the DAQ reports undocumented statusbits
field(FRVL, "4")
field(FRST, "INVALID")
# This is probably too fast. We could trigger things the same as sinqDAQ to ensure the db is update in the same order
field(SCAN, "I/O Intr")
field(PINI, "YES")
}
record(longin, "$(INSTR)$(NAME):CHANNELS")
{
field(DESC, "Total Supported Channels")
field(VAL, $(CHANNELS))
field(DISP, 1)
}
# Trigger a change in status as clearing
record(bo, "$(INSTR)$(NAME):ETT")
{
field(DESC, "Trigger Clearing Status")
field(VAL, 1)
field(OUT, "$(INSTR)$(NAME):ETS PP")
}
# Trigger a change in status as value returned to 0
record(seq, "$(INSTR)$(NAME):ETO")
{
field(DESC, "Trigger Returned to 0 Status")
field(LNK0, "$(INSTR)$(NAME):ETS PP")
field(DO0, 0)
field(SELM, "Specified")
field(SELL, "$(INSTR)$(NAME):ELAPSED-TIME.VAL")
field(SCAN, ".1 second")
}
# Current Status of Channel, i.e. is it ready to count?
record(bi, "$(INSTR)$(NAME):ETS")
{
field(DESC, "Channel Status")
field(VAL, 0)
field(ZNAM, "OK")
field(ONAM, "CLEARING")
field(PINI, 1)
}
################################################################################
# Count Commands
record(ao,"$(INSTR)$(NAME):PRESET-COUNT")
{
field(DESC, "Count until preset reached")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) P_CNT")
field(VAL, 0)
field(PREC, 2)
}
record(ao,"$(INSTR)$(NAME):PRESET-TIME")
{
field(DESC, "Count for specified time")
field(EGU, "seconds")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) P_TIME")
field(VAL, 0)
field(PREC, 2)
}
# record(bo,"$(INSTR)$(NAME):PAUSE")
# {
# field(DESC, "Pause the current count")
# field(DTYP, "stream")
# field(OUT, "@... pauseCount($(INSTR)$(NAME):) $(PORT)")
# field(VAL, "0")
# field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
# }
#
# record(bo,"$(INSTR)$(NAME):CONTINUE")
# {
# field(DESC, "Continue with a count that was paused")
# field(DTYP, "stream")
# field(OUT, "@... continueCount($(INSTR)$(NAME):) $(PORT)")
# field(VAL, "0")
# field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
# }
record(longout, "$(INSTR)$(NAME):STOP")
{
field(DESC, "Stop the current counting operation")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) STOP")
}
record(longout, "$(INSTR)$(NAME):MONITOR-CHANNEL")
{
field(DESC, "PRESET-COUNT Monitors this channel")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) MONITOR")
field(DRVL, "0") # Smallest Monitor Channel
field(DRVH, "$(CHANNELS)") # Largest Monitor Channel
}
record(longin, "$(INSTR)$(NAME):MONITOR-CHANNEL_RBV")
{
field(DESC, "PRESET-COUNT Monitors this channel")
field(DTYP, "asynInt32")
field(INP, "@asyn($(PORT),0,$(TIMEOUT=1)) MONITOR")
field(SCAN, "I/O Intr")
field(PINI, "YES")
}
record(ao,"$(INSTR)$(NAME):THRESHOLD")
{
field(DESC, "Minimum rate for counting to proceed")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) THRESH")
field(VAL, "1") # Default Rate
field(DRVL, "1") # Minimum Rate
field(DRVH, "100000") # Maximum Rate
}
record(ai,"$(INSTR)$(NAME):THRESHOLD_RBV")
{
field(DESC, "Minimum rate for counting to proceed")
field(EGU, "cts/sec")
field(DTYP, "asynInt32")
field(INP, "@asyn($(PORT),0,$(TIMEOUT=1)) THRESH")
field(SCAN, "I/O Intr")
field(PINI, "YES")
}
record(longout,"$(INSTR)$(NAME):THRESHOLD-MONITOR")
{
field(DESC, "Channel monitored for minimum rate")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) THRESH_CH")
field(VAL, "1") # Monitor
field(DRVL, "0") # Smallest Threshold Channel (0 is off)
field(DRVH, "$(CHANNELS)") # Largest Threshold Channel
}
record(longin,"$(INSTR)$(NAME):THRESHOLD-MONITOR_RBV")
{
field(DESC, "Channel monitored for minimum rate")
field(EGU, "CH")
field(DTYP, "asynInt32")
field(INP, "@asyn($(PORT),0,$(TIMEOUT=1)) THRESH_CH")
field(SCAN, "I/O Intr")
field(PINI, "YES")
}
record(longout, "$(INSTR)$(NAME):CT")
{
field(DESC, "Clear the timer")
field(DTYP, "asynInt32")
field(OUT, "@asyn($(PORT),0,$(TIMEOUT=1)) C_TIME")
field(FLNK, "$(INSTR)$(NAME):ETT")
}
################################################################################
# Read all monitors values
record(ai,"$(INSTR)$(NAME):ELAPSED-TIME")
{
field(DESC, "DAQ Measured Time")
field(EGU, "sec")
field(DTYP, "asynInt32")
field(INP, "@asyn($(PORT),0,$(TIMEOUT=1)) TIME")
field(SCAN, "I/O Intr")
field(PINI, "YES")
# field(FLNK, "$(INSTR)$(NAME):ETO")
}