Ophyd is the hardware abstraction layer developed by NSLS-II and used by BEC to communicate with the hardware. It is a Python library that provides a uniform interface to different hardware components. Ophyd is used to control the hardware and to read out the data. It is also used to create a virtual representation of the hardware in the form of devices and signals.

It can be used to test the hardware without spinning up BEC, simply by importing the ophyd library.

Within BEC, ophyd objects are created dynamically on the devices server, following the specifications given in the device configuration. As explained in the device configuration section, the device configuration can be loaded from and stored to a yaml file and contains all necessary information about the devices.

An example of an ophyd device based on EPICS is a single PV, e.g. the synchrotron's ring current:

curr:
  acquisitionConfig:
    acquisitionGroup: monitor
    readoutPriority: baseline
    schedule: sync
  description: SLS ring current
  deviceClass: EpicsSignalRO
  deviceConfig:
    auto_monitor: true
    name: curr
    read_pv: ARIDI-PCT:CURRENT
  deviceTags:
    - cSAXS
  onFailure: buffer
  status:
    enabled: true
    enabled_set: false

The following sections explain the different parts of the device configuration in more detail.

  • deviceClass
    The device class specifies the type of the device. In the example above, the device class is EpicsSignalRO, which is a read-only signal based on EPICS. Another example is EpicsMotor for motors based on EPICS. For a full list of available device classes, please refer to the Ophyd documentation and the Ophyd devices repository.

  • deviceConfig
    The device config contains the configuration of the device. In the example above, the device config contains the name of the device (name) and the read PV (read_pv). The read PV is the PV that is read out by the device. In this case, the read PV is ARIDI-PCT:CURRENT. The device config can contain any configuration parameter that is supported by the device class. The device is constructed by passing the device config to the device class. In the example above, the device is constructed by calling EpicsSignalRO(name='curr', read_pv='ARIDI-PCT:CURRENT', auto_monitor=True).

  • acquisitionConfig
    The acquisition config contains the configuration of the acquisition. It must contain the acquisition group (acquisitionGroup) and the readout priority (readoutPriority). The acquisition group specifies the group to which the device belongs. The readout priority specifies the priority with which the device is read out. The readout priority can be either ignored, baseline or monitored. The ignored priority is used for devices that should not be read out during the scan. The baseline priority is used for devices that are read out at the beginning of the scan and whose value does not change during the scan. The monitored priority is used for devices that are read out during the scan and whose value may change during the scan.

  • status
    The status contains the status of the device. It must contain the enabled status (enabled) and the enabled set status (enabled_set). The enabled status specifies whether the device is enabled. The enabled set status specifies whether the device is readonly.

  • deviceTags
    The device tags contain the tags of the device. The tags are used to group devices and to filter devices.

  • onFailure
    The on failure parameter specifies the behavior of the device in case of a failure. It can be either buffer, retry or raise. If an error occurs and the on failure parameter is set to buffer, the device readout will fall back to the last value in Redis. If the on failure parameter is set to retry, the device readout will retry to read the device and raises an error if it fails again. If the on failure parameter is set to raise, the device readout will raise an error immediately.

  • description
    The description contains the description of the device. It is used to provide additional information about the device.

Ophyd devices

As Ophyd provides a uniform interface to different hardware components, only a few commands are needed to control the hardware. The following section explains the available commands that are used by BEC:

  • stage
    Called by before the scan starts and is used to prepare the hardware for the scan. While for most devices, nothing needs to be done, for some devices such as detectors, the stage command can be used to automatically set the exposure time to the correct value. Please refer to the device bootstrapping section for more information.
  • unstage
    Called after the scan has finished and is used to clean up the hardware. It can be used to reset values that were changed during the scan or to perform additional checks to ensure that the hardware has completed the scan successfully. However, it is important to ensure that unstage is idempotent, i.e. can be called multiple times. Please refer to the device bootstrapping section for more information.
  • hints
    As every device may contain many signals, it is important to declare their priority. The hints command is used to retrieve a list of important signals.
  • describe
    Provides the schema and metadata for the read() method of the device.
  • describe_configuration
    Provides the schema and metadata for the read_configuration() method of the device.
  • name
    Returns the name of the device.
  • stop
    Stops the device.
  • set
    Sets the value of the device.
  • read
    Reads all normal and hinted signals of the device and returns a dictionary with the values and timestamps. The dictionary is structured as follows:
{ '<device_name>': 
  { '<device_name>_<signal_name1>': 
    { 'value': value, 
    'timestamp': timestamp 
    } 
  },
  { '<device_name>_<signal_name2>': 
    { 'value': value, 
    'timestamp': timestamp 
    } 
  } 
}