record(bo, "AGEBD-INJECTIONGUARD:CONTROL-BRIDGE-CHECK-$(NR)") {
record(bo, "$(DEVICE):CONTROL-BRIDGE-CHECK-$(NR)") {
field(DESC, "Only in MD mode: bridge check $(NR)")
field(ASG, "PROTECTED")
field(FLNK, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-MD")
field(FLNK, "$(DEVICE):CHECK-$(NR)-MD")
field(VAL, "0")
field(ZSV, "NO_ALARM")
field(OSV, "MINOR")
field(PINI, "YES")
}
record(bo, "AGEBD-INJECTIONGUARD:CHECK-$(NR)") {
record(bo, "$(DEVICE):CHECK-$(NR)") {
field(DESC, "$(Description)")
field(ASG, "PROTECTED")
field(FLNK, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-MD")
field(FLNK, "$(DEVICE):CHECK-$(NR)-MD")
field(ZSV, "MAJOR")
field(OSV, "NO_ALARM")
field(VAL, "1")
@@ -19,53 +19,53 @@ record(bo, "AGEBD-INJECTIONGUARD:CHECK-$(NR)") {
field(HIGH, "1") # Seconds until automatic switch to Alarm
}
record(calc, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-MD") {
record(calc, "$(DEVICE):CHECK-$(NR)-MD") {
field(DESC, "Check $(NR) MD, written by IOC")
field(ASG, "READONLY")
field(FLNK, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCHFWD")
field(FLNK, "$(DEVICE):CHECK-$(NR)-LATCHFWD")
field(LOLO, "0.1")
field(LLSV, "MAJOR")
field(CALC, "A ? 1 : B")
field(INPA, "AGEBD-INJECTIONGUARD:CONTROL-BRIDGE-CHECK-$(NR)")
field(INPB, "AGEBD-INJECTIONGUARD:CHECK-$(NR)")
field(INPA, "$(DEVICE):CONTROL-BRIDGE-CHECK-$(NR)")
field(INPB, "$(DEVICE):CHECK-$(NR)")
}
# forward only alarm states to latch bo
record(calcout, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCHFWD") {
record(calcout, "$(DEVICE):CHECK-$(NR)-LATCHFWD") {
field(DESC, "Latchfwd for check $(NR)")
field(ASG, "READONLY")
field(FLNK, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCH")
field(FLNK, "$(DEVICE):CHECK-$(NR)-LATCH")
field(CALC, "$(Latch)? ( A? C : B ) : 1")
field(PINI, "YES")
field(INPA, "AGEBD-INJECTIONGUARD:CONTROL-MODE CP")
field(INPB, "AGEBD-INJECTIONGUARD:CHECK-$(NR) CP")
field(INPC, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-MD CP")
field(INPA, "$(DEVICE):CONTROL-MODE CP")
field(INPB, "$(DEVICE):CHECK-$(NR) CP")
field(INPC, "$(DEVICE):CHECK-$(NR)-MD CP")
field(OOPT, "When Zero")
field(DOPT, "Use CALC")
field(OUT, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCH.VAL")
field(OUT, "$(DEVICE):CHECK-$(NR)-LATCH.VAL")
}
# forward current state to latch bo on reset event
record(calcout, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCHRST") {
record(calcout, "$(DEVICE):CHECK-$(NR)-LATCHRST") {
field(DESC, "Latchfwd for check $(NR)")
field(ASG, "READONLY")
field(FLNK, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCH")
field(FLNK, "$(DEVICE):CHECK-$(NR)-LATCH")
field(SCAN, "Event")
field(EVNT, "5")
field(CALC, "$(Latch)? ( A? C : B ) : 1")
field(PINI, "YES")
field(INPA, "AGEBD-INJECTIONGUARD:CONTROL-MODE")
field(INPB, "AGEBD-INJECTIONGUARD:CHECK-$(NR)")
field(INPC, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-MD")
field(INPA, "$(DEVICE):CONTROL-MODE")
field(INPB, "$(DEVICE):CHECK-$(NR)")
field(INPC, "$(DEVICE):CHECK-$(NR)-MD")
field(OOPT, "Every Time")
field(DOPT, "Use CALC")
field(OUT, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCH.VAL")
field(OUT, "$(DEVICE):CHECK-$(NR)-LATCH.VAL")
}
record(bo, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCH") {
record(bo, "$(DEVICE):CHECK-$(NR)-LATCH") {
field(DESC, "$(Description)")
field(ASG, "READONLY")
field(FLNK, "AGEBD-INJECTIONGUARD:CHECK-SUM-OP-A")
field(FLNK, "$(DEVICE):CHECK-SUM-OP-A")
field(ZSV, "MINOR")
field(OSV, "NO_ALARM")
field(VAL, "1")
@@ -73,17 +73,15 @@ record(bo, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-LATCH") {
}
# emit event for master rearm when alarm state is left and non latched
record(calcout, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-REARM-MASTER") {
record(calcout, "$(DEVICE):CHECK-$(NR)-REARM-MASTER") {
field(DESC, "Rearm Master for non latched checks")
field(ASG, "NOACCESS")
field(CALC, "!$(Latch)? ( A? C : B ) : 1")
field(PINI, "YES")
field(INPA, "AGEBD-INJECTIONGUARD:CONTROL-MODE CP")
field(INPB, "AGEBD-INJECTIONGUARD:CHECK-$(NR) CP")
field(INPC, "AGEBD-INJECTIONGUARD:CHECK-$(NR)-MD CP")
field(INPA, "$(DEVICE):CONTROL-MODE CP")
field(INPB, "$(DEVICE):CHECK-$(NR) CP")
field(INPC, "$(DEVICE):CHECK-$(NR)-MD CP")
field(OOPT, "Transition To Non-zero")
field(OEVT, "4")
field(ODLY, "0.1")
}