towards recabeling and reconfiguring all Powerbricks and Smaracts devices
Here all IOCs were started without any hardware. So in the next steps the hardware must be tested.
This commit is contained in:
70
cfg/MX2_home.cfg
Normal file
70
cfg/MX2_home.cfg
Normal file
@@ -0,0 +1,70 @@
|
||||
define(PLC_Homing='1')
|
||||
|
||||
//Homing:
|
||||
//Move all motors left bottom
|
||||
//move 1mm up
|
||||
//move both mottors at same time
|
||||
|
||||
//move to limit switch, gather data, move to other limit switch, gather stop. move back to first limit switch
|
||||
//motID :P0 : Motor Number
|
||||
//direction :P1 : Motion direction to first limit switch: -1 -> #1j- ,+1 -> #1j+
|
||||
//status :P100: local status
|
||||
//timer :P101: local timer
|
||||
|
||||
open plc PLC_Homing
|
||||
define(motID='L0',direction='P1',status='P100',timer='P101')
|
||||
jog-1; jog-2; jog-3; jog-4;
|
||||
Motor[1].HomeVel=0.5
|
||||
Motor[2].HomeVel=0.5
|
||||
Motor[3].HomeVel=0.5
|
||||
Motor[4].HomeVel=0.5
|
||||
status=10
|
||||
while(1)
|
||||
{
|
||||
if((Motor[1].MinusLimit==1 || Motor[1].FeFatal==1)){
|
||||
if((Motor[2].MinusLimit==1 || Motor[2].FeFatal==1)){
|
||||
if((Motor[3].MinusLimit==1 || Motor[3].FeFatal==1)){
|
||||
if((Motor[4].MinusLimit==1 || Motor[4].FeFatal==1)){
|
||||
status=11
|
||||
break
|
||||
}}}}
|
||||
}
|
||||
timer = Sys.RunTime + 2
|
||||
status=100
|
||||
while (Sys.RunTime < timer){} //wait 2 sec
|
||||
status=101
|
||||
jog1:1000; jog2:1000; jog3:1000; jog4:1000;
|
||||
timer = Sys.RunTime + 2
|
||||
status=200
|
||||
while (Sys.RunTime < timer){} //wait 2 sec
|
||||
status=201
|
||||
while(1)
|
||||
{
|
||||
if(Motor[1].DesVelZero==1 && Motor[2].DesVelZero==1 && Motor[3].DesVelZero==1 && Motor[4].DesVelZero==1)
|
||||
{
|
||||
status=12
|
||||
break
|
||||
}
|
||||
}
|
||||
timer = Sys.RunTime + 2
|
||||
while (Sys.RunTime < timer){}
|
||||
home 1; home 2; home 3; home 4
|
||||
status=13
|
||||
while(1) //wait homing index found done
|
||||
{
|
||||
if(Motor[1].HomeComplete==1 && Motor[2].HomeComplete==1 && Motor[3].HomeComplete==1 && Motor[4].HomeComplete==1)
|
||||
{
|
||||
status=14
|
||||
break
|
||||
}
|
||||
}
|
||||
while(1) //wait moving to zero position done
|
||||
{
|
||||
if(Motor[1].DesVelZero==1 && Motor[2].DesVelZero==1 && Motor[3].DesVelZero==1 && Motor[4].DesVelZero==1)
|
||||
{
|
||||
status=15
|
||||
break
|
||||
}
|
||||
}
|
||||
disable plc PLC_Homing
|
||||
close
|
||||