#AUTO
|
|
NO TE: $Revision: 1.2 $
|
|
NO TE: $Date: 2006-11-01 06:04:09 $
|
|
NO TE: Author: Dan Bartlett
|
|
NO TE: Limit switch HOME routine added by Ferdi Franceschini
|
|
NO TE: Last revision by: $Author: ffr $
|
|
NO TE:
|
|
NO TE: A-SAMPLE UPPER TILT (sphi) - TILT 1
|
|
NO TE: B-SAMPLE LOWER TILT (schi) - TILT 2
|
|
NO TE: C-SAMPLE UPPER TRANSLATION (sz:nexus, sx:KDL) - LINEAR 1
|
|
NO TE: D-SAMPLE LOWER TRANSLATION (sx:nexus, sy:KDL) - LINEAR 2
|
|
NO TE: E-SAMPLE ROTATION (som) - ROTATE
|
|
NO TE: F-DETECTOR ROTATE
|
|
NO TE: G-SPARE
|
|
NO TE: H-SPARE
|
|
MT-2,-2,-2,-2,-2,-2,-2,-2;'CONFIGURES ALL AXES AS STEPPER
|
|
MO;' FIRST TIME MOTOR OFF
|
|
CN 1;' CONFIGURES LIMIT SWITCHES TO ACCEPT NC CONTACTS
|
|
II 8,,,0;' CONFIGURES THE 8TH INPUT TO ACTIVATE THE #ININT ROUTINE
|
|
OP 65280;' SETS OUTPUTS 9-16 ON = RELAYS OFF
|
|
IA 137,157,201,4;' CONFIGURES IP ADDRESS
|
|
AC 25000,25000,25000,25000,25000,15000,25000,25000;' SET ACELERATION
|
|
DC 25000,25000,25000,25000,25000,15000,25000,25000;' SET DECELERATION
|
|
SP 25000,25000,25000,25000,50000,150000,25000,25000;' SET SPEED
|
|
SIA=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
SIB=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
SIC=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
SID=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
SIE=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
SIF=1,25,25,0<-1>2;'HEIDENHAIN RCN226
|
|
SIG=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
SIH=1,25,13,0<-1>2;'HEIDENHAIN ROQ425
|
|
DONE=0;' FIRST TIME THROUGH AIRPAD CONTROL NOT DONE
|
|
JS #SOLCTRL
|
|
EN
|
|
#SOLCTRL
|
|
NO TE: CONTROLS THE AIRPAD SOLENOID VALVES
|
|
IF (_MOF=0);'DETECTOR MOTOR IS ON
|
|
SB 10;'DETECTOR AIR PAD OFF-SOLENOID OFF
|
|
CB 9;'DETECTOR AIR PAD ON-SOLENOID ON
|
|
DONE=0
|
|
ENDIF
|
|
IF (_MOF=1)&(DONE=0);'DETECTOR MOTOR IS OFF
|
|
SB 9;'DETECTOR AIR PAD ON-SOLENOID OFF
|
|
CB 10;'DETECTOR AIR PAD OFF-SOLENOID ON
|
|
WT500;'WAIT 1/2 SEC
|
|
SB 10;'DETECTOR AIR PAD OFF-SOLENOID OFF
|
|
DONE=1
|
|
ENDIF
|
|
JP #SOLCTRL
|
|
EN
|
|
#TCPERR
|
|
NO TE: EMPTY ROUTINE FOR A TCP ERROR
|
|
RE
|
|
#ININT
|
|
NO TE: INTERUPT ROUTINE TO STOP ALL AXES
|
|
NO TE: WHEN SAFETY & INTERLOCK SYSTEM REQUESTS IT
|
|
STA,B,C,D,E,F,G,H
|
|
AM
|
|
MO
|
|
RI
|
|
#LIMSWI
|
|
NO TE: LIMIT SWITCH ROUTINE WHICH SHORTENS DECEL TIME WHEN A LIMIT IS HIT
|
|
OLDDCA=_DCA;' REMEMBERS CURRENT DECEL
|
|
OLDDCB=_DCB
|
|
OLDDCC=_DCC
|
|
OLDDCD=_DCD
|
|
OLDDCE=_DCE
|
|
OLDDCF=_DCF
|
|
OLDDCG=_DCG
|
|
OLDDCH=_DCH
|
|
IF (_LFA = 0) | (_LRA = 0)
|
|
DCA=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STA
|
|
AMA
|
|
MOA
|
|
DCA=OLDDCA;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFB = 0) | (_LRB = 0)
|
|
DCB=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STB
|
|
AMB
|
|
MOB
|
|
DCB=OLDDCB;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFC = 0) | (_LRC = 0)
|
|
DCC=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STC
|
|
AMC
|
|
MOC
|
|
DCC=OLDDCC;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFD = 0) | (_LRD = 0)
|
|
DCD=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STD
|
|
AMD
|
|
MOD
|
|
DCD=OLDDCD;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFE = 0) | (_LRE = 0)
|
|
DCE=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STE
|
|
AME
|
|
MOE
|
|
DCE=OLDDCE;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFF = 0) | (_LRF = 0)
|
|
DCF=75000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STF
|
|
AMF
|
|
MOF
|
|
DCF=OLDDCF;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFG = 0) | (_LRG = 0)
|
|
DCG=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STG
|
|
AMG
|
|
MOG
|
|
DCG=OLDDCG;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
IF (_LFH = 0) | (_LRH = 0)
|
|
DCH=100000;' DECEL FOR LIMIT HIT OCCURENCE
|
|
STH
|
|
AMH
|
|
MOH
|
|
DCH=OLDDCH;' RESET DECEL TO OLD VALUE
|
|
ENDIF
|
|
RE
|
|
|
|
|