Merge branch 'master' of gitlab.psi.ch-samenv:samenv/sea

This commit is contained in:
2022-11-14 14:47:50 +01:00
3 changed files with 41 additions and 14 deletions

View File

@ -798,13 +798,13 @@ proc dil12::autostep {phase init} {
}
dil12::check_cool_button
if {[result dil p1] < [hvali [sct]/p1low] && [result dil g1] < 5 &&
[result dil p2] < [hvali [sct]/p2low] && [result dil v6pos] > 99} {
[result dil p2] < [hvali [sct]/p2low] && [result dil v6pos] > 50} {
if {[sct pumptime] == 0} {
dil12::openvalves v5a v2a v7 v2 v1 v6 v5 v3 vb_open
dil v4a 1
sct pumptime [expr [DoubleTime] + 105]
dil12::msg "pump for 2 more minutes"
} elseif {[DoubleTime] > [sct pumptime]} {
} elseif {[DoubleTime] > [sct pumptime] && [result dil v6pos] > 99} {
# do not check for vb/vm here, as the user already might manipulate the valves
dil12::openvalves v1 v6 v3 v5
dil v4a 0

View File

@ -27,8 +27,20 @@ proc stdConfig::heliox {} {
node pot_state -text upd
node target_hours par 60
node target_hours par 48
prop help "how many hours the pot should last (< 75)"
node holdflow out
default 1.5
prop check heliox::check_holdflow
prop help "flow for holding pressure"
prop write stdSct::complete
node condenseflow out
default 3
prop check heliox::check_condenseflow
prop help "flow for condensing"
prop write stdSct::complete
}
catch {
hsetprop /tt getsample hvali /th/pot
@ -67,7 +79,7 @@ proc heliox::check_set {} {
set mainsensor /th/pot
switch [sctval [sct]/mode] {
1 {
nv set 2.5
nv set [hvali [sct]/holdflow]
th setsorb/channel C
th setsorb 20
th mainloop set
@ -75,7 +87,7 @@ proc heliox::check_set {} {
run tt [sct target]
}
2 {
nv set 2.5
nv set [hvali [sct]/holdflow]
th setsorb/channel C
th setsorb 20
th mainloop set
@ -84,7 +96,7 @@ proc heliox::check_set {} {
th set [sct target]
}
3 {
nv set 2.5
nv set [hvali [sct]/holdflow]
th setsorb/channel B
th mainloop setsorb
th set 0
@ -129,7 +141,7 @@ proc heliox::check_mode {} {
0 {
}
1 {
nv set 2.5
nv set [hvali [sct parent]/holdflow]
if {[sct target] != [hvali [sct]]} {
th set [hvali /th/target]
}
@ -139,7 +151,7 @@ proc heliox::check_mode {} {
set state "hi-T mode"
}
2 {
nv set 2.5
nv set [hvali [sct parent]/holdflow]
if {[sct target] != [hvali [sct]]} {
th set [hvali /th/target]
}
@ -149,7 +161,7 @@ proc heliox::check_mode {} {
set state "mid-T mode"
}
3 {
nv set 2.5
nv set [hvali [sct parent]/holdflow]
if {[hvali [sct parent]/lasts_until] > [DoubleTime]} {
th set 0
th setsorb/channel B
@ -181,6 +193,20 @@ proc heliox::check_mode {} {
sct update [sct target]
}
proc heliox::check_condenseflow {} {
if {[sctval [sct parent]/mode] == 4} {
nv set [sct target]
}
sct update [sct target]
}
proc heliox::check_holdflow {} {
if {[sctval [sct parent]/mode] != 4} {
nv set [sct target]
}
sct update [sct target]
}
proc heliox::complete {} {
sct print [lindex {undefined "hi-T mode" "mid-T mode" "low-T mode" "-> condense"} [sct target]]
return idle
@ -218,11 +244,11 @@ proc heliox::read {} {
}
if {[hvali [sct]] == 4} {
if {$ts > 3} {
nv set 4
nv set [hvali [sct parent]/condenseflow]
set lasts_until 0
sct condense_deadline [expr $now + 36000] # timeout: should be 3600
} elseif {[result th sorb] > 39} {
nv set 4
nv set [hvali [sct parent]/condenseflow]
# 3He vapor pressure: 200 mbar at 2 K, power law
set p [expr 200 * ($ts / 2.0) ** 3.5]
# dump pressure at condensation start
@ -244,8 +270,9 @@ proc heliox::read {} {
th setsorb/channel B
th mainloop setsorb
th setsorb [silent 0.25 hgetpropval [sct parent] goto]
sct update 3
nv set 2.5
# switch to lowT and trigger check_mode
hset [sct] 3
nv set [hvali [sct parent]/holdflow]
clientput "the 3He pot [hvali [sct parent]/pot_state]"
}
}

View File

@ -303,7 +303,7 @@ proc ipsmag::update_leads {{n_of_slaves 3}} {
set msg "slave currents ($currents) are not within $mincur .. $maxcur"
hupdate [sct objectPath]/status $msg
if {$status eq ""} {
# clientlog "ERROR: $msg"
clientlog "WARNING: $msg"
}
} elseif {[string match {slave currents *} $status]} {
hupdate [sct objectPath]/status ""