Files
sinqSPS/db/shutter.db
2025-03-28 11:42:12 +01:00

76 lines
3.0 KiB
Plaintext

record(bo, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER")
{
field(DESC, "Open or close the shutter")
field(DTYP, "Soft Channel")
field(OMSL, "supervisory")
field(VAL, 0)
field(ZNAM, "Closed")
field(ONAM, "Open")
field(FLNK, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-CONTROL PP")
}
# The Exposed SPS Interface has an open register and a close register. You need
# to write 1 to the corresponding register to perform said action. This, in
# combination with "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER", maps the binay 0/1
# to writing a 1 to the required register.
record(seq, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-CONTROL")
{
field(SELM, "Specified")
field(SELL, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER.VAL NPP")
field(DO0, 1)
field(DO1, 1)
field(LNK0, "$(PREFIX):$(SPS_REGISTER_NAME):CLOSE-SHUTTER PP")
field(LNK1, "$(PREFIX):$(SPS_REGISTER_NAME):OPEN-SHUTTER PP")
}
record(calc, "$(PREFIX):$(SPS_REGISTER_NAME):MAP-STATUS")
{
field(DESC, "Maps Status Variables to singular status")
field(INPA, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-READY NPP")
field(INPB, "$(PREFIX):$(SPS_REGISTER_NAME):NOT-LOCKED NPP")
field(INPC, "$(PREFIX):$(SPS_REGISTER_NAME):REMOTE-OKAY NPP")
field(INPD, "$(PREFIX):$(SPS_REGISTER_NAME):PSYS-OK NPP")
field(INPE, "$(PREFIX):$(SPS_REGISTER_NAME):EMERGENCY-STOP-OFF NPP")
field(CALC, "(E=0||B=0)?2:(A=0||D=0)?1:C=0?2:0")
field(SCAN, ".1 second")
field(FLNK, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS PP")
}
record(mbbi, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS")
{
field(DESC, "Status of Shutter")
field(INP, "$(PREFIX):$(SPS_REGISTER_NAME):MAP-STATUS NPP")
field(ZRVL, "0")
field(ZRST, "Okay")
field(ONVL, "1")
field(ONST, "Warning")
field(TWVL, "2")
field(TWST, "Error")
field(THVL, "3")
field(THST, "Unknown")
field(FLNK, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS-Msg PP")
}
record(scalcout, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS-Msg")
{
field(DESC, "Status Message")
field(INPA, "$(PREFIX):$(SPS_REGISTER_NAME):OPEN NPP")
field(INPC, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-READY NPP")
field(INPD, "$(PREFIX):$(SPS_REGISTER_NAME):NOT-LOCKED NPP")
field(INPE, "$(PREFIX):$(SPS_REGISTER_NAME):REMOTE-OKAY NPP")
field(INPF, "$(PREFIX):$(SPS_REGISTER_NAME):PSYS-OK NPP")
field(INPG, "$(PREFIX):$(SPS_REGISTER_NAME):EMERGENCY-STOP-OFF NPP")
field(INAA, "$(PREFIX):$(SPS_REGISTER_NAME):OPEN-Msg NPP")
field(INBB, "$(PREFIX):$(SPS_REGISTER_NAME):REMOTE-Msg NPP")
field(INCC, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-READY-Msg NPP")
field(INDD, "$(PREFIX):$(SPS_REGISTER_NAME):EMERGENCY-STOP-Msg NPP")
field(INEE, "$(PREFIX):$(SPS_REGISTER_NAME):BLOCKED-Msg NPP")
field(INFF, "$(PREFIX):$(SPS_REGISTER_NAME):BLOCKED-REASON-Msg NPP")
field(INGG, "$(PREFIX):$(SPS_REGISTER_NAME):PSYS-OK-Msg NPP")
# field(CALC, '(C=0||D=0||F=0)?"inv":G=0?DD:E=0?BB:AA')
# field(CALC, 'E=0?BB:G=0?DD:AA')
# field(CALC, 'G=0?DD:F=0?GG:C=0?CC:(EE[8,10]!="not")?(EE+": "+FF):E=0?BB:AA')
# field(CALC, 'G=0?DD:F=0?GG:C=0?CC:D=0?(EE+": "+FF):E=0?BB:AA')
field(CALC, 'G=0?DD:D=0?(EE+": "+FF):F=0?GG:C=0?CC:E=0?BB:AA')
}