Files
sinqSPS/db/shutter.db

49 lines
2.0 KiB
Plaintext

record(calc, "$(PREFIX):$(SPS_REGISTER_NAME):MAP-STATUS")
{
field(DESC, "Maps Status Variables to singular status")
field(INPA, "$(PREFIX):$(SPS_REGISTER_NAME):OPEN NPP")
field(INPC, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-READY NPP")
field(INPD, "$(PREFIX):$(SPS_REGISTER_NAME):NOT-LOCKED NPP")
field(INPE, "$(PREFIX):$(SPS_REGISTER_NAME):REMOTE-OKAY NPP")
field(INPF, "$(PREFIX):$(SPS_REGISTER_NAME):PSYS-OK NPP")
field(INPG, "$(PREFIX):$(SPS_REGISTER_NAME):EMERGENCY-STOP-OFF NPP")
field(CALC, "(C=0||D=0||E=0||F=0||G=0)?2:A=1")
field(SCAN, ".1 second")
field(FLNK, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS PP")
}
record(mbbi, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS")
{
field(DESC, "Simplified Status of Shutter")
field(INP, "$(PREFIX):$(SPS_REGISTER_NAME):MAP-STATUS NPP")
field(ZRVL, "0")
field(ZRST, "Closed")
field(ONVL, "1")
field(ONST, "Open")
field(TWVL, "2")
field(TWST, "Error")
# Should never happen
field(THVL, "3")
field(THST, "Invalid")
field(FLNK, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS-Msg PP")
}
record(scalcout, "$(PREFIX):$(SPS_REGISTER_NAME):STATUS-Msg")
{
field(DESC, "Status Message")
field(INPA, "$(PREFIX):$(SPS_REGISTER_NAME):OPEN NPP")
field(INPC, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-READY NPP")
field(INPD, "$(PREFIX):$(SPS_REGISTER_NAME):NOT-LOCKED NPP")
field(INPE, "$(PREFIX):$(SPS_REGISTER_NAME):REMOTE-OKAY NPP")
field(INPF, "$(PREFIX):$(SPS_REGISTER_NAME):PSYS-OK NPP")
field(INPG, "$(PREFIX):$(SPS_REGISTER_NAME):EMERGENCY-STOP-OFF NPP")
field(INAA, "$(PREFIX):$(SPS_REGISTER_NAME):OPEN-Msg NPP")
field(INBB, "$(PREFIX):$(SPS_REGISTER_NAME):REMOTE-Msg NPP")
field(INCC, "$(PREFIX):$(SPS_REGISTER_NAME):SHUTTER-READY-Msg NPP")
field(INDD, "$(PREFIX):$(SPS_REGISTER_NAME):EMERGENCY-STOP-Msg NPP")
field(INEE, "$(PREFIX):$(SPS_REGISTER_NAME):BLOCKED-Msg NPP")
field(INFF, "$(PREFIX):$(SPS_REGISTER_NAME):BLOCKED-REASON-Msg NPP")
field(INGG, "$(PREFIX):$(SPS_REGISTER_NAME):PSYS-OK-Msg NPP")
field(CALC, '(C=0||D=0||F=0)?"inv":G=0?DD:E=0?BB:AA')
}