record(bo, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER")
{
field(DESC, "Open or close the shutter")
field(DTYP, "Soft Channel")
field(OMSL, "supervisory")
field(VAL, 0)
field(ZNAM, "Closed")
field(ONAM, "Open")
field(FLNK, "$(INSTR)$(SPS_REGISTER_NAME):CLEAR-CONTROL PP")
}
# The Exposed SPS Interface has an open register and a close register. You need
# to write 1 to the corresponding register to perform said action and make sure
# that the other bit is set back to 0. These two records, in combination with
# "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER", first clear both control bits and
# then maps the binay 0/1 to writing a 1 to the required register.
record(dfanout, "$(INSTR)$(SPS_REGISTER_NAME):CLEAR-CONTROL")
{
field(DOL, 0)
field(OUTA, "$(INSTR)$(SPS_REGISTER_NAME):CLOSE-SHUTTER PP")
field(OUTB, "$(INSTR)$(SPS_REGISTER_NAME):OPEN-SHUTTER PP")
field(FLNK, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER-CONTROL PP")
field(SELM, "All")
}
record(seq, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER-CONTROL")
{
field(SELM, "Specified")
field(SELL, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER.VAL NPP")
field(DO0, 1)
field(DO1, 1)
field(LNK0, "$(INSTR)$(SPS_REGISTER_NAME):CLOSE-SHUTTER PP")
field(LNK1, "$(INSTR)$(SPS_REGISTER_NAME):OPEN-SHUTTER PP")
}
record(calc, "$(INSTR)$(SPS_REGISTER_NAME):MAP-STATUS")
{
field(DESC, "Maps Status Variables to singular status")
field(INPA, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER-READY NPP")
field(INPB, "$(INSTR)$(SPS_REGISTER_NAME):NOT-LOCKED NPP")
field(INPC, "$(INSTR)$(SPS_REGISTER_NAME):REMOTE-OKAY NPP")
field(INPD, "$(INSTR)$(SPS_REGISTER_NAME):PSYS-OK NPP")
field(INPE, "$(INSTR)$(SPS_REGISTER_NAME):EMERGENCY-STOP-OFF NPP")
field(INPF, "$(INSTR)$(SPS_REGISTER_NAME):MOVES NPP")
field(INPG, "$(INSTR)$(SPS_REGISTER_NAME):ConnStatusFetch NPP")
field(INPH, "$(INSTR)$(SPS_REGISTER_NAME):ConnStatusWrite NPP")
field(CALC, "(G=0||H=0||E=0||B=0)?3:(A=0||D=0)?2:F=1?1:C=0?3:0")
field(SCAN, ".1 second")
field(FLNK, "$(INSTR)$(SPS_REGISTER_NAME):STATUS PP")
}
record(mbbi, "$(INSTR)$(SPS_REGISTER_NAME):STATUS")
{
field(DESC, "Status of Shutter")
field(INP, "$(INSTR)$(SPS_REGISTER_NAME):MAP-STATUS NPP")
field(ZRVL, "0")
field(ZRST, "Okay")
field(ONVL, "1")
field(ONST, "Busy")
field(TWVL, "2")
field(TWST, "Warning")
field(THVL, "3")
field(THST, "Error")
field(FRST, "4")
field(FRST, "Unknown")
field(FLNK, "$(INSTR)$(SPS_REGISTER_NAME):STATUS-Msg PP")
}
record(stringout, "$(INSTR)$(SPS_REGISTER_NAME):MOTION-Msg")
{
field(DESC, "Shutter opening/closing message")
field(VAL, "Shutter in motion")
}
record(stringout, "$(INSTR)$(SPS_REGISTER_NAME):Connection-Msg")
{
field(DESC, "Shutter connection disrupted message")
field(VAL, "Connection to SPS Disrupted")
}
record(scalcout, "$(INSTR)$(SPS_REGISTER_NAME):STATUS-Msg")
{
field(DESC, "Status Message")
field(INPA, "$(INSTR)$(SPS_REGISTER_NAME):OPEN NPP")
field(INPC, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER-READY NPP")
field(INPD, "$(INSTR)$(SPS_REGISTER_NAME):NOT-LOCKED NPP")
field(INPE, "$(INSTR)$(SPS_REGISTER_NAME):REMOTE-OKAY NPP")
field(INPF, "$(INSTR)$(SPS_REGISTER_NAME):PSYS-OK NPP")
field(INPG, "$(INSTR)$(SPS_REGISTER_NAME):EMERGENCY-STOP-OFF NPP")
field(INPH, "$(INSTR)$(SPS_REGISTER_NAME):MOVES NPP")
field(INPI, "$(INSTR)$(SPS_REGISTER_NAME):ConnStatusFetch NPP")
field(INPJ, "$(INSTR)$(SPS_REGISTER_NAME):ConnStatusWrite NPP")
field(INAA, "$(INSTR)$(SPS_REGISTER_NAME):OPEN-Msg NPP")
field(INBB, "$(INSTR)$(SPS_REGISTER_NAME):REMOTE-Msg NPP")
field(INCC, "$(INSTR)$(SPS_REGISTER_NAME):SHUTTER-READY-Msg NPP")
field(INDD, "$(INSTR)$(SPS_REGISTER_NAME):EMERGENCY-STOP-Msg NPP")
field(INEE, "$(INSTR)$(SPS_REGISTER_NAME):BLOCKED-Msg NPP")
field(INFF, "$(INSTR)$(SPS_REGISTER_NAME):BLOCKED-REASON-Msg NPP")
field(INGG, "$(INSTR)$(SPS_REGISTER_NAME):PSYS-OK-Msg NPP")
field(INHH, "$(INSTR)$(SPS_REGISTER_NAME):MOTION-Msg NPP")
field(INII, "$(INSTR)$(SPS_REGISTER_NAME):Connection-Msg NPP")
field(CALC, '(I=0||J=0)?II:H=1?HH:G=0?DD:D=0?(EE+": "+FF):F=0?GG:C=0?CC:E=0?BB:AA')
}