# EPICS database for counterbox-like interface using proton current,
|
|
# as retrieved via network from HIPA.
|
|
#
|
|
# This is created to be able reuse the SinqDAQ interface
|
|
# in Nicos, to avoid having more code to maintain there.
|
|
#
|
|
# This requires following macros to specified:
|
|
# INSTR: Instrument prefix, e.g. "SQAMOR:"
|
|
# NAME: Name of the DAQ, e.g. "PROTONDAQ"
|
|
# SHUTTER1_PV: PV of a shutter state will be taken as a gate signal for the protoon current
|
|
# SHUTTER1_CLOSED_VAL: Value of the shutter PV when the shutter is closed
|
|
# SHUTTER2_PV: PV of a second shutter state will be taken as a gate signal for the protoon current
|
|
# SHUTTER2_CLOSED_VAL: Value of the shutter PV when the shutter is closed
|
|
|
|
record(mbbi, "$(INSTR)$(NAME):STATUS")
|
|
{
|
|
field(DESC, "DAQ Status")
|
|
field(ZRVL, "0")
|
|
field(ZRST, "Idle")
|
|
field(ONVL, "1")
|
|
field(ONST, "Counting")
|
|
field(TWVL, "2")
|
|
field(TWST, "Low rate")
|
|
field(THVL, "3")
|
|
field(THST, "Paused")
|
|
# 4 should never happen, if it does it means the DAQ reports undocumented statusbits
|
|
field(FRVL, "4")
|
|
field(FRST, "INVALID")
|
|
# We start in idle
|
|
field(VAL, 0)
|
|
}
|
|
|
|
record(longin, "$(INSTR)$(NAME):CHANNELS")
|
|
{
|
|
field(DESC, "Total Supported Channels")
|
|
field(VAL, 1)
|
|
field(DISP, 1)
|
|
}
|
|
|
|
record(stringin, "$(INSTR)$(NAME):MsgTxt")
|
|
{
|
|
field(DESC, "Miscellanous messages")
|
|
}
|
|
|
|
record(bi, "$(INSTR)$(NAME):IS_LOWRATE")
|
|
{
|
|
field(ZNAM, "LOW RATE")
|
|
field(ONAM, "GOOD RATE")
|
|
}
|
|
|
|
################################################################################
|
|
# Commands
|
|
################################################################################
|
|
|
|
record(int64in, "$(INSTR)$(NAME):PRESET-COUNT")
|
|
{
|
|
field(DESC, "Count until preset reached")
|
|
field(VAL, 0)
|
|
field(FLNK, "$(INSTR)$(NAME):PRESET-COUNT-TRIG")
|
|
}
|
|
|
|
record(longout, "$(INSTR)$(NAME):PRESET-COUNT-TRIG")
|
|
{
|
|
field(DESC, "Count until preset reached")
|
|
# Signal count preset as command
|
|
field(VAL, 1)
|
|
field(OUT, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
field(FLNK, "$(INSTR)$(NAME):COUNT-TYPE")
|
|
}
|
|
|
|
record(calcout, "$(INSTR)$(NAME):PRESET-TIME")
|
|
{
|
|
field(DESC, "Count for specified time")
|
|
field(VAL, 0)
|
|
field(PREC, 2)
|
|
field(EGU, "seconds")
|
|
# Signal count preset as command
|
|
field(OCAL, 2)
|
|
field(OOPT, "Every Time")
|
|
field(DOPT, "Use OCAL")
|
|
field(OUT, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
field(FLNK, "$(INSTR)$(NAME):COUNT-TYPE")
|
|
}
|
|
|
|
record(calcout, "$(INSTR)$(NAME):PAUSE")
|
|
{
|
|
field(DESC, "Pause the current count")
|
|
field(VAL, 0)
|
|
field(OCAL, 3)
|
|
field(OOPT, "Every Time")
|
|
field(DOPT, "Use OCAL")
|
|
field(OUT, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
}
|
|
|
|
record(calcout, "$(INSTR)$(NAME):CONTINUE")
|
|
{
|
|
field(DESC, "Continue with a count that was paused")
|
|
field(VAL, "0")
|
|
field(OCAL, 4)
|
|
field(OOPT, "Every Time")
|
|
field(DOPT, "Use OCAL")
|
|
field(OUT, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
}
|
|
|
|
record(calcout, "$(INSTR)$(NAME):STOP")
|
|
{
|
|
field(DESC, "Stop the current counting operation")
|
|
field(OCAL, 5)
|
|
field(OOPT, "Every Time")
|
|
field(DOPT, "Use OCAL")
|
|
field(OUT, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
}
|
|
|
|
record(calcout, "$(INSTR)$(NAME):FULL-RESET")
|
|
{
|
|
field(DESC, "Reset the DAQ")
|
|
field(OCAL, 6)
|
|
field(OOPT, "Every Time")
|
|
field(DOPT, "Use OCAL")
|
|
field(OUT, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
}
|
|
|
|
# Record is to signal command given by the client to the emulated counter.
|
|
# It's set back to no command from the emulated counter subroutine record
|
|
record(mbbi, "$(INSTR)$(NAME):COMMAND-TRIG")
|
|
{
|
|
field(DESC, "Command type")
|
|
field(VAL, 0)
|
|
field(ZRST, "No command")
|
|
field(ZRVL, 0)
|
|
field(ONST, "Count preset command")
|
|
field(ONVL, 1)
|
|
field(TWST, "Time preset command")
|
|
field(TWVL, 2)
|
|
field(THST, "Pause command")
|
|
field(THVL, 3)
|
|
field(FRST, "Continue command")
|
|
field(FRVL, 4)
|
|
field(FVST, "Stop command")
|
|
field(FVVL, 5)
|
|
field(FVST, "Full reset command")
|
|
field(FVVL, 6)
|
|
}
|
|
|
|
# Copy COMMAND-TRIG to memorize what type of count is on-going
|
|
record(longin, "$(INSTR)$(NAME):COUNT-TYPE") {
|
|
field(INP, "$(INSTR)$(NAME):COMMAND-TRIG.VAL NPP")
|
|
field(VAL, 0)
|
|
}
|
|
|
|
record(longout,"$(INSTR)$(NAME):THRESHOLD-MONITOR")
|
|
{
|
|
# Alias to RBV to be compatible with higher level interface
|
|
alias("$(INSTR)$(NAME):THRESHOLD-MONITOR_RBV")
|
|
field(DESC, "Channel monitored for minimum rate")
|
|
field(VAL, "1") # Monitor
|
|
field(DRVL, "0") # Smallest Threshold Channel (0 is off)
|
|
field(DRVH, "1") # Largest Threshold Channel
|
|
}
|
|
|
|
record(ao,"$(INSTR)$(NAME):THRESHOLD")
|
|
{
|
|
# Alias to RBV to be compatible with higher level interface
|
|
alias("$(INSTR)$(NAME):THRESHOLD_RBV")
|
|
field(DESC, "Minimum rate for counting to proceed")
|
|
field(VAL, "1") # Default Rate
|
|
field(DRVL, "1") # Minimum Rate
|
|
field(DRVH, "100000") # Maximum Rate
|
|
field(OMSL, "supervisory")
|
|
}
|
|
|
|
record(ai,"$(INSTR)$(NAME):ELAPSED-TIME")
|
|
{
|
|
field(DESC, "DAQ Measured Time")
|
|
field(EGU, "sec")
|
|
}
|
|
|
|
# Array Subroutine record which emulates the counterbox functionality
|
|
# Use an aSub because it allows specifying the type.
|
|
record(aSub, "$(INSTR)$(NAME):EMULATION")
|
|
{
|
|
# Scan rate determines how often we sample the rate
|
|
# and how often the counter value updates.
|
|
field(SCAN, ".1 second")
|
|
field(SNAM, "processEmulatedCounter")
|
|
|
|
# The first 4 inputs are also mapped as the first 4 outputs
|
|
field(INPA, "$(INSTR)$(NAME):STATUS")
|
|
field(FTA, "ULONG")
|
|
field(INPB, "$(INSTR)$(NAME):M0")
|
|
field(FTB, "INT64")
|
|
field(INPC, "$(INSTR)$(NAME):ELAPSED-TIME")
|
|
field(FTC, "DOUBLE")
|
|
field(OUTD, "$(INSTR)$(NAME):COMMAND-TRIG")
|
|
field(FTD, "ULONG")
|
|
field(OUTE, "$(INSTR)$(NAME):THRESHOLD")
|
|
field(FTE, "DOUBLE")
|
|
|
|
# Address the PV which are mapped as input backwards
|
|
field(INPF, "$(INSTR)$(NAME):COUNT-TYPE")
|
|
field(FTF, "ULONG")
|
|
field(INPG, "$(INSTR)$(NAME):PRESET-COUNT")
|
|
field(FTG, "INT64")
|
|
field(INPH, "$(INSTR)$(NAME):PRESET-TIME")
|
|
field(FTH, "DOUBLE")
|
|
# L is last input before EPICS 7.0.10
|
|
field(INPJ, "$(INSTR)$(NAME):R0-PREV")
|
|
field(FTJ, "DOUBLE")
|
|
field(INPL, "$(INSTR)$(NAME):R0 PP")
|
|
field(FTL, "DOUBLE")
|
|
|
|
# The first 4 outputs are also mapped as the first 4 inputs
|
|
field(OUTA, "$(INSTR)$(NAME):STATUS PP")
|
|
field(FTVA, "ULONG")
|
|
field(OUTB, "$(INSTR)$(NAME):M0 PP")
|
|
field(FTVB, "INT64")
|
|
field(OUTC, "$(INSTR)$(NAME):ELAPSED-TIME PP")
|
|
field(FTVC, "DOUBLE")
|
|
field(OUTD, "$(INSTR)$(NAME):COMMAND-TRIG PP")
|
|
field(FTVD, "ULONG")
|
|
field(OUTE, "$(INSTR)$(NAME):R0-PREV PP")
|
|
field(FTVE, "DOUBLE")
|
|
field(OUTF, "$(INSTR)$(NAME):IS_LOWRATE PP")
|
|
field(FTVF, "ULONG")
|
|
field(OUTF, "$(INSTR)$(NAME):MSG_TXT PP")
|
|
field(FTVF, "CHAR")
|
|
}
|
|
|
|
#######################
|
|
# Channel interface
|
|
#######################
|
|
record(int64in, "$(INSTR)$(NAME):M0")
|
|
{
|
|
field(DESC, "DAQ CH0, proton current")
|
|
field(EGU, "cts")
|
|
}
|
|
|
|
# The proton rate take by a PV over the network, PV named indicated by $(REMOTE_RATE_PV) macro
|
|
# It emulates Zero rate if either shutter is closed.
|
|
record(calc, "$(INSTR)$(NAME):R0")
|
|
{
|
|
field(DESC, "Rate of DAQ CH0 proton current")
|
|
#field(INPA, "$(REMOTE_RATE_PV) CA")
|
|
field(INPA, "$(INSTR)$(NAME):PROTON_CURR")
|
|
field(INPB, "$(SHUTTER1_PV=0)")
|
|
field(INPC, "$(SHUTTER1_CLOSED_VAL=1)")
|
|
field(INPD, "$(SHUTTER2_PV=0)")
|
|
field(INPE, "$(SHUTTER2_CLOSED_VAL=1)")
|
|
# If either shutter is closed we have no rate
|
|
field(CALC, "B != C && D != E ? A : 0")
|
|
field(EGU, "cts/sec")
|
|
}
|
|
|
|
# Store previous rate value, so we can average over the period
|
|
record(ai, "$(INSTR)$(NAME):R0-PREV") {
|
|
field(DESC, "Previous rate of DAQ CH0 proton current")
|
|
}
|
|
|
|
# Clear channel, has to be calcout due to client
|
|
# writing 1 to it.
|
|
record(calcout, "$(INSTR)$(NAME):C0")
|
|
{
|
|
field(DESC, "Clear the current channel count")
|
|
field(OOPT, "Every Time")
|
|
field(DOPT, "Use OCAL")
|
|
field(OCAL, "0")
|
|
field(OUT, "$(INSTR)$(NAME):M0 PP")
|
|
}
|
|
|
|
# Current Status of Channel, i.e. is it ready to count?
|
|
# This is probbably only need to satify the interface.
|
|
record(bi, "$(INSTR)$(NAME):S0")
|
|
{
|
|
field(DESC, "Channel Status")
|
|
field(VAL, 0)
|
|
field(ZNAM, "OK")
|
|
field(ONAM, "CLEARING")
|
|
}
|
|
|
|
record(calc, "$(INSTR)$(NAME):PROTON_CURR") {
|
|
field(SCAN, ".1 second")
|
|
field(CALC, "1500 * 101 * SIN(A)")
|
|
field(INPA, "$(INSTR)$(NAME):PROTON_CURR_VAR PP")
|
|
}
|
|
|
|
record(calc, "$(INSTR)$(NAME):PROTON_CURR_VAR") {
|
|
field(CALC, "VAL + 0.001")
|
|
}
|