Merge pull request 'SINQSW-107-configuring-with-nicos' (#1) from SINQSW-107-configuring-with-nicos into master
Reviewed-on: #1
This commit is contained in:
30
Makefile
30
Makefile
@ -1,7 +1,7 @@
|
||||
# This build the sinq extensions for the PSI EPICS setup
|
||||
include /ioc/tools/driver.makefile
|
||||
|
||||
MODULE=counterbox
|
||||
MODULE=sinqDAQ
|
||||
BUILDCLASSES=Linux
|
||||
EPICS_VERSIONS=7.0.7
|
||||
ARCH_FILTER=RHEL%
|
||||
@ -13,23 +13,27 @@ REQUIRED+=stream
|
||||
|
||||
# DB files to include in the release
|
||||
TEMPLATES += db/channels.db
|
||||
TEMPLATES += db/counterbox_4ch.db
|
||||
TEMPLATES += db/counterbox_8ch.db
|
||||
TEMPLATES += db/counterbox_common.db
|
||||
TEMPLATES += db/counterbox_v2.db
|
||||
TEMPLATES += db/counterbox_v2_test.db
|
||||
TEMPLATES += db/counterbox.proto
|
||||
TEMPLATES += db/gating_channels.db
|
||||
TEMPLATES += db/daq_4ch.db
|
||||
TEMPLATES += db/daq_8ch.db
|
||||
TEMPLATES += db/daq_common.db
|
||||
TEMPLATES += db/daq_2nd_gen.db
|
||||
TEMPLATES += db/daq_2nd_gen_test.db
|
||||
TEMPLATES += db/daq.proto
|
||||
|
||||
# Just for simulation
|
||||
TEMPLATES += db/daq_simcontrol.db
|
||||
|
||||
# DBD files to include in the release
|
||||
DBDS += src/counterbox.dbd
|
||||
DBDS += src/daq.dbd
|
||||
|
||||
# Source files to build
|
||||
SOURCES += src/counterbox.cpp
|
||||
SOURCES += src/daq.cpp
|
||||
|
||||
SCRIPTS += scripts/counterbox_4ch.cmd
|
||||
SCRIPTS += scripts/counterbox_8ch.cmd
|
||||
SCRIPTS += scripts/counterbox_v2.cmd
|
||||
SCRIPTS += sim/counterbox_sim.py
|
||||
SCRIPTS += scripts/daq_4ch.cmd
|
||||
SCRIPTS += scripts/daq_8ch.cmd
|
||||
SCRIPTS += scripts/daq_2nd_gen.cmd
|
||||
SCRIPTS += sim/daq_sim.py
|
||||
|
||||
CXXFLAGS += -std=c++17
|
||||
USR_CFLAGS += -Wall -Wextra #-Werror
|
||||
|
166
README.md
166
README.md
@ -1,7 +1,8 @@
|
||||
Counterbox Epics Module
|
||||
SINQDAQ Epics Module
|
||||
-----------------------
|
||||
|
||||
A Stream and Asyn based driver for configuring the Counterboxes at SINQ.
|
||||
A Stream and Asyn based driver for configuring the Data Acquisition Systems at
|
||||
SINQ.
|
||||
|
||||
This supports the older 4 and 8 channel EL737 models and the new 10CH 2nd
|
||||
generation systems.
|
||||
@ -9,51 +10,53 @@ generation systems.
|
||||
## How to Use
|
||||
|
||||
Unless a custom database is needed, a device can be configure simply by setting
|
||||
the required environment variables when calling the correct counterbox script.
|
||||
the required environment variables when calling the correct DAQ interface
|
||||
script.
|
||||
|
||||
Required Variables
|
||||
|
||||
| Environment Variable | Purpose |
|
||||
|----------------------|-----------------------------------------|
|
||||
| PREFIX | Prefix of all device specific PVs |
|
||||
| INSTR | Prefix of all device specific PVs |
|
||||
| NAME | First field in all PVs after Prefix |
|
||||
| CNTBOX\_IP | Network IP of device |
|
||||
| CNTBOX\_PORT | Network Port of device |
|
||||
| DAQ\_IP | Network IP of device |
|
||||
| DAQ\_PORT | Network Port of device |
|
||||
|
||||
All PVs take the form
|
||||
|
||||
```
|
||||
$(PREFIX):$(NAME):*
|
||||
$(INSTR)$(NAME):*
|
||||
```
|
||||
|
||||
Available device startup scripts
|
||||
|
||||
* scripts/counterbox\_4ch.cmd
|
||||
* scripts/counterbox\_8ch.cmd
|
||||
* scripts/counterbox\_v2.cmd
|
||||
* scripts/daq\_4ch.cmd
|
||||
* scripts/daq\_8ch.cmd
|
||||
* scripts/daq\_2nd\_gen.cmd
|
||||
|
||||
A device can be configured using one of the startup scripts as follows
|
||||
|
||||
```
|
||||
epicsEnvSet("PREFIX", "SQ:INSTRUMENT") # can also be set in runScript call
|
||||
epicsEnvSet("INSTR", "SQ:INSTRUMENT:") # can also be set in runScript call
|
||||
|
||||
runScript "$(counterbox_DIR)counterbox_v2.cmd" "NAME=COUNTERBOX, CNTBOX_IP=TestInst-DAQ1, CNTBOX_PORT=2000"
|
||||
runScript "$(sinqDAQ_DIR)daq_2nd_gen.cmd" "NAME=DAQ, DAQ_IP=TestInst-DAQ1, DAQ_PORT=2000"
|
||||
```
|
||||
|
||||
## PVs of Interest
|
||||
|
||||
| PV | Description |
|
||||
|---------------------------------------|----------------------------------------------------------------------|
|
||||
| \$(PREFIX):\$(NAME):MsgTxt | Contains unexpected response to executed command |
|
||||
| \$(PREFIX):\$(NAME):STATUS | 0: Idle, 1: Counting, 2: Low rate, 3: Paused, 4: Error |
|
||||
| \$(PREFIX):\$(NAME):MONITOR-CHANNEL | Channel that PRESET-COUNT monitors (has RBV, only v2 can be changed) |
|
||||
| \$(PREFIX):\$(NAME):PRESET-COUNT | Run count until specified pv value reached |
|
||||
| \$(PREFIX):\$(NAME):PRESET-TIME | Run count until specified pv value in seconds reached |
|
||||
| \$(PREFIX):\$(NAME):THRESHOLD | Minimum rate for counting to preceed. (has RBV) |
|
||||
| \$(PREFIX):\$(NAME):THRESHOLD-MONITOR | Channel monitored for minimum rate (has RBV) |
|
||||
| \$(PREFIX):\$(NAME):ELAPSED-TIME | Time Counterbox has been measuring for |
|
||||
| \$(PREFIX):\$(NAME):M_ | Current count on channel. (1-10 depending on box) |
|
||||
| \$(PREFIX):\$(NAME):CHANNELS | Number of available channels (4, 8 or 10) |
|
||||
|-------------------------------------|----------------------------------------------------------------------|
|
||||
| \$(INSTR)\$(NAME):MsgTxt | Contains unexpected response to executed command |
|
||||
| \$(INSTR)\$(NAME):STATUS | 0: Idle, 1: Counting, 2: Low rate, 3: Paused, 4: Error |
|
||||
| \$(INSTR)\$(NAME):MONITOR-CHANNEL | Channel that PRESET-COUNT monitors (has RBV, only v2 can be changed) |
|
||||
| \$(INSTR)\$(NAME):PRESET-COUNT | Run count until specified pv value reached |
|
||||
| \$(INSTR)\$(NAME):PRESET-TIME | Run count until specified pv value in seconds reached |
|
||||
| \$(INSTR)\$(NAME):THRESHOLD | Minimum rate for counting to preceed. (has RBV) |
|
||||
| \$(INSTR)\$(NAME):THRESHOLD-MONITOR | Channel monitored for minimum rate (has RBV) |
|
||||
| \$(INSTR)\$(NAME):ELAPSED-TIME | Time DAQ has been measuring for |
|
||||
| \$(INSTR)\$(NAME):M_ | Current count on channel. (1-10 depending on DAQ system) |
|
||||
| \$(INSTR)\$(NAME):CHANNELS | Number of available channels (4, 8 or 10) |
|
||||
| \$(INSTR)\$(NAME):GATE-_ | Configuration for Gating in newer hardware |
|
||||
|
||||
## Generating Test Signals
|
||||
|
||||
@ -64,34 +67,133 @@ runtime via the following
|
||||
|
||||
```
|
||||
epicsEnvSet("LOAD_TEST_PVS","")
|
||||
runScript "$(counterbox_DIR)counterbox_v2.cmd" "NAME=COUNTERBOX, CNTBOX_IP=TestInst-DAQ1, CNTBOX_PORT=2000"
|
||||
runScript "$(sinqDAQ_DIR)daq_2nd_gen.cmd" "NAME=DAQ, DAQ_IP=TestInst-DAQ1, DAQ_PORT=2000"
|
||||
```
|
||||
|
||||
See the file [counterbox\_v2\_test.db](./db/counterbox_v2_test.db)
|
||||
See the file [daq\_2nd\_gen\_test.db](./db/daq_2nd_gen_test.db)
|
||||
|
||||
## Nicos Interface
|
||||
|
||||
A set of Nicos devices have been developed which allow control of the Detector
|
||||
Hardware via this Epics Driver. The corresponding code can be found in
|
||||
[sinqdaq.py](https://gitea.psi.ch/lin-instrument-computers/Nicos/src/branch/release-3.12/nicos_sinq/devices/epics/sinqdaq.py).
|
||||
|
||||
## Full Example
|
||||
|
||||
Include the following snippet in your IOC
|
||||
|
||||
```
|
||||
# st.cmd at SINQTEST
|
||||
|
||||
epicsEnvSet("STREAM_PROTOCOL_PATH","./db")
|
||||
epicsEnvSet("INSTR","SQ:SINQTEST:")
|
||||
|
||||
require sinqDAQ
|
||||
runScript "$(sinqDAQ_DIR)daq_2nd_gen.cmd" "NAME=DAQ, DAQ_IP=TestInst-DAQ1, DAQ_PORT=2000"
|
||||
```
|
||||
|
||||
What follows is an example Nicos setup file. The "channels" are created in the loop
|
||||
at the bottom.
|
||||
|
||||
```
|
||||
# DAQDetector.py
|
||||
description = 'Devices for the detectors'
|
||||
|
||||
countprefix = 'SQ:SINQTEST:DAQ'
|
||||
|
||||
devices = dict(
|
||||
ElapsedTime = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQTime',
|
||||
daqpvprefix = countprefix,
|
||||
),
|
||||
DAQPreset = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQPreset',
|
||||
description = '2nd Generation Data Acquisition',
|
||||
daqpvprefix = countprefix,
|
||||
channels = [],
|
||||
time_channel = ['ElapsedTime'],
|
||||
),
|
||||
DAQV2 = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.SinqDetector',
|
||||
description = 'Detector Interface',
|
||||
timers = ['ElapsedTime'],
|
||||
counters = [],
|
||||
monitors = ['DAQPreset'],
|
||||
images = [],
|
||||
others = [],
|
||||
liveinterval = 2,
|
||||
saveintervals = [2]
|
||||
),
|
||||
ThresholdChannel = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQMinThresholdChannel',
|
||||
daqpvprefix = countprefix,
|
||||
channels = [],
|
||||
visibility = {'metadata', 'namespace'},
|
||||
),
|
||||
Threshold = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQMinThreshold',
|
||||
daqpvprefix = countprefix,
|
||||
min_rate_channel = 'ThresholdChannel',
|
||||
visibility = {'metadata', 'namespace'},
|
||||
),
|
||||
Gate1 = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQGate',
|
||||
daqpvprefix = countprefix,
|
||||
channel = 1,
|
||||
visibility = {'metadata', 'namespace'},
|
||||
),
|
||||
Gate2 = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQGate',
|
||||
daqpvprefix = countprefix,
|
||||
channel = 2,
|
||||
visibility = {'metadata', 'namespace'},
|
||||
),
|
||||
TestGen = device('nicos_sinq.devices.epics.sinqdaq.DAQTestGen',
|
||||
daqpvprefix = countprefix,
|
||||
visibility = {'metadata', 'namespace'},
|
||||
),
|
||||
)
|
||||
|
||||
for i in range(10):
|
||||
devices[f'monitor{i+1}'] = device(
|
||||
'nicos_sinq.devices.epics.sinqdaq.DAQChannel',
|
||||
description = f'Monitor {i + 1}',
|
||||
daqpvprefix = countprefix,
|
||||
channel = i + 1,
|
||||
type = 'monitor',
|
||||
)
|
||||
devices['DAQPreset'][1]['channels'].append(f'monitor{i+1}')
|
||||
devices['ThresholdChannel'][1]['channels'].append(f'monitor{i+1}')
|
||||
devices['DAQV2'][1]['monitors'].append(f'monitor{i+1}')
|
||||
|
||||
startupcode = '''
|
||||
SetDetectors(DAQV2)
|
||||
'''
|
||||
```
|
||||
|
||||
## Simulation
|
||||
|
||||
Simulation of the Hardware can be toggled on as follows:
|
||||
|
||||
```
|
||||
epicsEnvSet("SET_SIM_MODE","") # run counterbox simulation instead of connecting to actual box
|
||||
runScript "$(counterbox_DIR)counterbox_v2.cmd" "NAME=CB_TEST, CNTBOX_IP=localhost, CNTBOX_PORT=2000"
|
||||
epicsEnvSet("SET_SIM_MODE","") # run DAQ simulation instead of connecting to actual system
|
||||
runScript "$(sinqDAQ_DIR)daq_2nd_gen.cmd" "NAME=CB_TEST, DAQ_IP=localhost, DAQ_PORT=2000"
|
||||
```
|
||||
|
||||
In such a case, the provided `CNTBOX_IP` is ignored, and a python program
|
||||
In such a case, the provided `DAQ_IP` is ignored, and a python program
|
||||
simulating the hardware is started in the background, listening at the
|
||||
specified `CNTBOX_PORT`. So, if you have multiple devices listening on the same
|
||||
specified `DAQ_PORT`. So, if you have multiple devices listening on the same
|
||||
port, you might have to change this port value of one of the devices when
|
||||
simulating hardware. You can then interact with the PVs as with the normal
|
||||
hardware. Keep in mind, however, that not all functionality has been
|
||||
implemented.
|
||||
|
||||
See [sim/counterbox\_sim.py](sim/counterbox_sim.py).
|
||||
See [sim/daq\_sim.py](sim/daq_sim.py).
|
||||
|
||||
## Testing
|
||||
|
||||
An IOC with the counterbox\_v2 started in simulation mode can be started via
|
||||
the [test/ioc.sh](test/ioc.sh) script.
|
||||
An IOC with the 2nd generation DAQ started in simulation mode can be started
|
||||
via the [test/ioc.sh](test/ioc.sh) script.
|
||||
|
||||
There is also a simple automated test that can be run for a simple check of
|
||||
functionality and that the PVs load [test/test.py](test/test.py).
|
||||
|
@ -1,20 +1,77 @@
|
||||
# EL737 EPICS Database for streamdevice support
|
||||
# EPICS Database for streamdevice specific to measurement channels
|
||||
#
|
||||
# Macros
|
||||
# P - Prefix
|
||||
# NAME - just a name, e.g. EL737
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to EL737
|
||||
# ASYN_PORT - Low level Asyn IP Port to DAQ
|
||||
# CHANNEL - the number associated with the measurment channel
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
# Trigger a change in status as clearing
|
||||
record(bo, "$(INSTR)$(NAME):T$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Trigger Clearing Status")
|
||||
field(VAL, 1)
|
||||
field(OUT, "$(INSTR)$(NAME):S$(CHANNEL) PP")
|
||||
}
|
||||
|
||||
# Trigger a change in status as value returned to 0
|
||||
record(seq, "$(INSTR)$(NAME):O$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Trigger Returned to 0 Status")
|
||||
field(LNK0, "$(INSTR)$(NAME):S$(CHANNEL) PP")
|
||||
field(DO0, 0)
|
||||
field(SELM, "Specified")
|
||||
field(SELL, "$(INSTR)$(NAME):M$(CHANNEL).VAL")
|
||||
}
|
||||
|
||||
# Current Status of Channel, i.e. is it ready to count?
|
||||
record(bi, "$(INSTR)$(NAME):S$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Channel Status")
|
||||
field(VAL, 0)
|
||||
field(ZNAM, "OK")
|
||||
field(ONAM, "CLEARING")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):C$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Clear the current channel count")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) clearChannel($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)")
|
||||
field(FLNK, "$(INSTR)$(NAME):T$(CHANNEL)")
|
||||
}
|
||||
|
||||
record(ao,"$(INSTR)$(NAME):THRESH$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Sets minimum rate for counting to proceed")
|
||||
field(OMSL, "supervisory")
|
||||
field(OROC, "0")
|
||||
field(OUT, "@$(PROTO) setMinRate($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
||||
|
||||
record(longin, "$(P):$(NAME):M$(CHANNEL)")
|
||||
record(longin, "$(INSTR)$(NAME):M$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Counterbox CH$(CHANNEL)")
|
||||
field(DESC, "DAQ CH$(CHANNEL)")
|
||||
field(EGU, "cts")
|
||||
field(FLNK, "$(INSTR)$(NAME):O$(CHANNEL)")
|
||||
}
|
||||
|
||||
record(ai, "$(INSTR)$(NAME):R$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Rate of DAQ CH$(CHANNEL)")
|
||||
field(INP, "@$(PROTO) readRate($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
field(EGU, "cts/sec")
|
||||
field(SCAN, "1 second")
|
||||
}
|
||||
|
@ -1,134 +0,0 @@
|
||||
#
|
||||
# Counterbox Protocol File
|
||||
#
|
||||
OutTerminator = CR;
|
||||
InTerminator = CR;
|
||||
ReadTimeout = 100;
|
||||
WriteTimeout = 100;
|
||||
ReplyTimeout = 200;
|
||||
LockTimeout = 450;
|
||||
|
||||
initialise {
|
||||
out "RMT 1"; # Turn on Remote Control
|
||||
in;
|
||||
out "ECHO 2"; # Ask for reponses
|
||||
in "%(\$1MsgTxt)s"; # Clear MsgTxt on Init
|
||||
@mismatch{
|
||||
exec 'echo "Failed to configure counterbox" && exit(1)';
|
||||
}
|
||||
}
|
||||
|
||||
fullReset {
|
||||
out "\%";
|
||||
wait 5000;
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
readStatus {
|
||||
out "RS";
|
||||
in "%d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readPresetMonitor {
|
||||
out "PC";
|
||||
in "%d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
writePresetMonitor {
|
||||
out "PC %d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
startWithCountPreset {
|
||||
out "MP %d";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
startWithTimePreset {
|
||||
out "TP %#.2f";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
pauseCount {
|
||||
out "PS";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
continueCount {
|
||||
out "CO";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
stopCount {
|
||||
out "S";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
setMinRate{
|
||||
out "DL %(\$1THRESHOLD-MONITOR)d %(\$1THRESHOLD)d";
|
||||
in;
|
||||
out "DR %(\$1THRESHOLD-MONITOR)d";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readMinRate{
|
||||
out "DR";
|
||||
in "%(\$1THRESHOLD-MONITOR_RBV)d";
|
||||
out "DL %(\$1THRESHOLD-MONITOR_RBV)d";
|
||||
in "%(\$1THRESHOLD_RBV)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read Values From Monitors
|
||||
|
||||
readAll4 {
|
||||
out "RA";
|
||||
in "%(\$1ELAPSED-TIME)f %(\$1M1)d %(\$1M2)d %(\$1M3)d %(\$1M4)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readAll8 {
|
||||
out "RA";
|
||||
in "%(\$1ELAPSED-TIME)f %(\$1M1)d %(\$1M2)d %(\$1M3)d %(\$1M4)d %(\$1M5)d %(\$1M6)d %(\$1M7)d %(\$1M8)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readAll10 {
|
||||
out "RA";
|
||||
in "%(\$1ELAPSED-TIME)f %(\$1M1)d %(\$1M2)d %(\$1M3)d %(\$1M4)d %(\$1M5)d %(\$1M6)d %(\$1M7)d %(\$1M8)d %(\$1M9)d %(\$1M10)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readRate {
|
||||
out "RR \$2";
|
||||
in "%(\$1R\$2)f";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Testing Commands
|
||||
|
||||
switchTestgenOnOff {
|
||||
out "TG %{off|on}";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
# Only suppporting test channel 1 at the moment. (The first argument to TG)
|
||||
setTestSignal {
|
||||
out "TG 1 %(\$1TESTGEN-HIGHRATE)d %(\$1TESTGEN-LOWRATE)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
@ -1,29 +0,0 @@
|
||||
# Counterbox EPICS Database
|
||||
# Macros
|
||||
# P - Prefix
|
||||
# NAME - just a name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to EL737
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(longin, "$(P):$(NAME):MONITOR-CHANNEL")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
record(longin, "$(P):$(NAME):MONITOR-CHANNEL_RBV")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
@ -1,29 +0,0 @@
|
||||
# EL737 EPICS Database for streamdevice support
|
||||
# Macros
|
||||
# P - Prefix
|
||||
# NAME - just a name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to EL737
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(longin, "$(P):$(NAME):MONITOR-CHANNEL")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
record(longin, "$(P):$(NAME):MONITOR-CHANNEL_RBV")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
@ -1,215 +0,0 @@
|
||||
# EL737 EPICS Database for streamdevice support
|
||||
# Macros
|
||||
# P - Prefix
|
||||
# NAME - just a name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to EL737
|
||||
|
||||
# Send initial initialisation commands
|
||||
record(bo, "$(P):$(NAME):INIT-CONF")
|
||||
{
|
||||
field(DESC, "Initialises the Counterbox")
|
||||
field(OUT, "@$(PROTO) initialise($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(PINI, "YES") # Run at init
|
||||
field(DTYP, "stream")
|
||||
field(FLNK, "$(P):$(NAME):INIT-BOX")
|
||||
}
|
||||
|
||||
# As we aren't certain of the order that PINI exectutes PVs, we only set it to
|
||||
# true on INIT-CONF to make sure the box is ready to receive commands, and then
|
||||
# let INIT-CONF trigger the initialisation of other necessary records
|
||||
record(fanout, "$(P):$(NAME):INIT-BOX")
|
||||
{
|
||||
field(DESC, "Rewrite PVs to Box")
|
||||
field(SELM, "All")
|
||||
field(LNK0, "$(P):$(NAME):MONITOR-CHANNEL_RBV PP")
|
||||
field(LNK1, "$(P):$(NAME):RAW-STATUS PP")
|
||||
field(LNK2, "$(P):$(NAME):THRESHOLD_RBV PP")
|
||||
}
|
||||
|
||||
record(longout, "$(P):$(NAME):FULL-RESET")
|
||||
{
|
||||
field(DESC, "Reset the Counterbox")
|
||||
field(OUT, "@$(PROTO) fullReset($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(stringin, "$(P):$(NAME):MsgTxt")
|
||||
{
|
||||
field(DESC, "Unexpected received response")
|
||||
field(DTYP, "devCounterBoxStringError")
|
||||
field(FLNK, "$(P):$(NAME):INVALID-CONFIG")
|
||||
}
|
||||
|
||||
# We want to recognise the invalid config error message, so that we can rerun
|
||||
# the init if it occurs. This should only happen after turning the box off and
|
||||
# on again or running a full reset
|
||||
record(scalcout, "$(P):$(NAME):INVALID-CONFIG")
|
||||
{
|
||||
field(DESC, "Has the counterbox been configured?")
|
||||
field(CALC, "AA[0,2] == '?OF'")
|
||||
field(INAA, "$(P):$(NAME):MsgTxt")
|
||||
field(FLNK, "$(P):$(NAME):REINIT-CONF")
|
||||
}
|
||||
|
||||
record(seq, "$(P):$(NAME):REINIT-CONF")
|
||||
{
|
||||
field(LNK1, "$(P):$(NAME):INIT-CONF PP")
|
||||
field(DO1, 1)
|
||||
field(SELM, "Specified")
|
||||
field(SELL, "$(P):$(NAME):INVALID-CONFIG.VAL")
|
||||
}
|
||||
|
||||
# Important! The "$(P):$(NAME):READALL" isn't configure with a SCAN. Instead,
|
||||
# it must always be triggered after the value of $(P):$(NAME):RAW-STATUS is
|
||||
# updated, so that it can't be the case that the status changes back from
|
||||
# counting to idle, without having updated the time and count values.
|
||||
record(longin, "$(P):$(NAME):RAW-STATUS")
|
||||
{
|
||||
field(DESC, "Raw returned status value")
|
||||
field(DTYP, "stream")
|
||||
field(SCAN, ".1 second")
|
||||
field(INP, "@$(PROTO) readStatus($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(FLNK, "$(P):$(NAME):READALL")
|
||||
}
|
||||
|
||||
record(calc, "$(P):$(NAME):MAP-STATUS")
|
||||
{
|
||||
field(DESC, "Maps Raw Status to State")
|
||||
field(INPA, "$(P):$(NAME):RAW-STATUS NPP")
|
||||
field(INPB, "$(P):$(NAME):INVALID-CONFIG NPP")
|
||||
field(INPC, "$(P):$(NAME):RAW-STATUS.UDF NPP") # should also be invalid if can't read the status
|
||||
field(CALC, "(B=1||C==1)?4:A=0?0:(A=1||A=2)?1:(A=5||A=6)?2:(A=9||A=13||A=10||A=14)?3:4")
|
||||
field(FLNK, "$(P):$(NAME):STATUS")
|
||||
}
|
||||
|
||||
record(mbbi, "$(P):$(NAME):STATUS")
|
||||
{
|
||||
field(DESC, "Counterbox Status")
|
||||
field(INP, "$(P):$(NAME):MAP-STATUS NPP")
|
||||
field(ZRVL, "0")
|
||||
field(ZRST, "Idle")
|
||||
field(ONVL, "1")
|
||||
field(ONST, "Counting")
|
||||
field(TWVL, "2")
|
||||
field(TWST, "Low rate")
|
||||
field(THVL, "3")
|
||||
field(THST, "Paused")
|
||||
# 4 should never happen, if it does it means the counter box reports undocumented statusbits
|
||||
field(FRVL, "4")
|
||||
field(FRST, "INVALID")
|
||||
}
|
||||
|
||||
record(longin, "$(P):$(NAME):CHANNELS")
|
||||
{
|
||||
field(DESC, "Total Supported Channels")
|
||||
field(VAL, $(CHANNELS))
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
record(ao,"$(P):$(NAME):PRESET-COUNT")
|
||||
{
|
||||
field(DESC, "Count until preset reached")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) startWithCountPreset($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 0)
|
||||
field(PREC, 2)
|
||||
}
|
||||
|
||||
record(ao,"$(P):$(NAME):PRESET-TIME")
|
||||
{
|
||||
field(DESC, "Count for specified time")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) startWithTimePreset($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 0)
|
||||
field(PREC, 2)
|
||||
field(EGU, "seconds")
|
||||
}
|
||||
|
||||
record(bo,"$(P):$(NAME):PAUSE")
|
||||
{
|
||||
field(DESC, "Pause the current count")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) pauseCount($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, "0")
|
||||
}
|
||||
|
||||
record(bo,"$(P):$(NAME):CONTINUE")
|
||||
{
|
||||
field(DESC, "Continue with a count that was paused")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) continueCount($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, "0")
|
||||
}
|
||||
|
||||
record(bo, "$(P):$(NAME):STOP")
|
||||
{
|
||||
field(DESC, "Stop the current counting operation")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) stopCount($(P):$(NAME):) $(ASYN_PORT)")
|
||||
}
|
||||
|
||||
# TODO should changing the monitor also set things?
|
||||
# or only when actually setting a threshold?
|
||||
record(longout,"$(P):$(NAME):THRESHOLD")
|
||||
{
|
||||
field(DESC, "Minimum rate for counting to proceed")
|
||||
field(VAL, "0") # Rate
|
||||
field(DRVL, "0") # Minimum Rate
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setMinRate($(P):$(NAME):) $(ASYN_PORT)")
|
||||
}
|
||||
|
||||
record(longin,"$(P):$(NAME):THRESHOLD_RBV")
|
||||
{
|
||||
field(DESC, "Minimum rate for counting to proceed")
|
||||
field(DTYP, "stream")
|
||||
field(INP, "@$(PROTO) readMinRate($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(SCAN, "2 second")
|
||||
}
|
||||
|
||||
record(longout,"$(P):$(NAME):THRESHOLD-MONITOR")
|
||||
{
|
||||
field(DESC, "Channel monitored for minimum rate")
|
||||
field(VAL, "1") # Monitor
|
||||
field(DRVL, "1") # Smallest Threshold Channel
|
||||
field(DRVL, "$(CHANNELS)") # Largest Threshold Channel
|
||||
}
|
||||
|
||||
record(longin,"$(P):$(NAME):THRESHOLD-MONITOR_RBV")
|
||||
{
|
||||
field(DESC, "Channel monitored for minimum rate")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
||||
|
||||
record(ai, "$(P):$(NAME):READALL")
|
||||
{
|
||||
field(DESC, "Reads monitors and elapsed time")
|
||||
field(INP, "@$(PROTO) readAll$(CHANNELS)($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
field(FLNK, "$(P):$(NAME):MAP-STATUS")
|
||||
}
|
||||
|
||||
record(ai,"$(P):$(NAME):ELAPSED-TIME")
|
||||
{
|
||||
field(DESC, "Counterbox Measured Time")
|
||||
field(EGU, "seconds")
|
||||
}
|
||||
|
||||
# Not yet sure whether we want to support this
|
||||
# record(longin, "$(P):$(NAME):R1")
|
||||
# {
|
||||
# field(DESC, "Counterbox Rate CH1")
|
||||
# field(INP, "@$(PROTO) readRate($(P):$(NAME):, 1) $(ASYN_PORT)")
|
||||
# field(SCAN, ".2 second")
|
||||
# field(DTYP, "stream")
|
||||
# }
|
@ -1,31 +0,0 @@
|
||||
# EL737 EPICS Database for streamdevice support
|
||||
# Macros
|
||||
# P - Prefix
|
||||
# NAME - just a name, e.g. DAQV2
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to Counterbox
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(longout, "$(P):$(NAME):MONITOR-CHANNEL")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) writePresetMonitor($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(FLNK, "$(P):$(NAME):MONITOR-CHANNEL_RBV")
|
||||
}
|
||||
|
||||
record(longin, "$(P):$(NAME):MONITOR-CHANNEL_RBV")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(DTYP, "stream")
|
||||
field(INP, "@$(PROTO) readPresetMonitor($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(SCAN, "5 second")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
@ -1,31 +0,0 @@
|
||||
################################################################################
|
||||
# Testing Commands
|
||||
|
||||
# These won't match the values on the machine after a full restart But I chose
|
||||
# not to force their intialisation as they are only important for testing
|
||||
|
||||
record(bo, "$(P):$(NAME):TESTGEN")
|
||||
{
|
||||
field(DESC, "Turn on/off Testgen Signal")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) switchTestgenOnOff($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 0)
|
||||
field(ZNAM, "OFF")
|
||||
field(ONAM, "ON")
|
||||
}
|
||||
|
||||
record(longout, "$(P):$(NAME):TESTGEN-LOWRATE")
|
||||
{
|
||||
field(DESC, "Set Minimum Testgen Rate")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setTestSignal($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 1000)
|
||||
}
|
||||
|
||||
record(longout, "$(P):$(NAME):TESTGEN-HIGHRATE")
|
||||
{
|
||||
field(DESC, "Set Maximum Testgen Rate")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setTestSignal($(P):$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 1000)
|
||||
}
|
268
db/daq.proto
Normal file
268
db/daq.proto
Normal file
@ -0,0 +1,268 @@
|
||||
#
|
||||
# SinqDAQ Protocol File
|
||||
#
|
||||
OutTerminator = CR;
|
||||
InTerminator = CR;
|
||||
ReadTimeout = 100;
|
||||
WriteTimeout = 100;
|
||||
ReplyTimeout = 200;
|
||||
LockTimeout = 450;
|
||||
|
||||
initialise {
|
||||
out "RMT 1"; # Turn on Remote Control
|
||||
in;
|
||||
out "ECHO 2"; # Ask for reponses
|
||||
in "%(\$1MsgTxt)s"; # Clear MsgTxt on Init
|
||||
@mismatch{
|
||||
exec 'echo "Failed to configure DAQ" && exit(1)';
|
||||
}
|
||||
}
|
||||
|
||||
fullReset {
|
||||
out "\%";
|
||||
wait 5000;
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
readStatus {
|
||||
out "RS";
|
||||
in "%d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readPresetMonitor {
|
||||
out "PC";
|
||||
in "%d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
writePresetMonitor {
|
||||
out "PC %d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
pauseCount {
|
||||
out "PS";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
continueCount {
|
||||
out "CO";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
stopCount {
|
||||
out "S";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
clearTimer{
|
||||
# We first stop the count, as otherwise the 2nd Gen Data Acquisition starts
|
||||
# counting again if a time preset was set. Not a problem with the older boxes
|
||||
stopCount;
|
||||
out "CT";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
clearChannel{
|
||||
out "CC \$2";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
clearCounter4 {
|
||||
out "CC 1";
|
||||
in;
|
||||
out "CC 2";
|
||||
in;
|
||||
out "CC 3";
|
||||
in;
|
||||
out "CC 4";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
clearCounter8 {
|
||||
out "CC 5";
|
||||
in;
|
||||
out "CC 6";
|
||||
in;
|
||||
out "CC 7";
|
||||
in;
|
||||
out "CC 8";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
clearCounter10 {
|
||||
out "CC 9";
|
||||
in;
|
||||
out "CC 10";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
startWithCountPreset {
|
||||
out "MP %d";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
startWithTimePreset {
|
||||
out "TP %#.2f";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
setMinRate{
|
||||
out "DL \$2 %.3f";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readMinRate{
|
||||
out "DL %(\$1THRESHOLD-MONITOR_RBV)d";
|
||||
in "%f";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
setRateMonitor{
|
||||
out "DR %d";
|
||||
in;
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readRateMonitor{
|
||||
out "DR";
|
||||
in "%d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read Values From Monitors
|
||||
|
||||
readAll4 {
|
||||
out "RA";
|
||||
in "%(\$1ELAPSED-TIME)f %(\$1M1)d %(\$1M2)d %(\$1M3)d %(\$1M4)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readAll8 {
|
||||
out "RA";
|
||||
in "%(\$1ELAPSED-TIME)f %(\$1M1)d %(\$1M2)d %(\$1M3)d %(\$1M4)d %(\$1M5)d %(\$1M6)d %(\$1M7)d %(\$1M8)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readAll10 {
|
||||
out "RA";
|
||||
in "%(\$1ELAPSED-TIME)f %(\$1M1)d %(\$1M2)d %(\$1M3)d %(\$1M4)d %(\$1M5)d %(\$1M6)d %(\$1M7)d %(\$1M8)d";
|
||||
# At least on the sinqtest variant this is broken
|
||||
# requiring channels 9 and 10 to be manually queried
|
||||
out "RC 9";
|
||||
in "%(\$1M9)d";
|
||||
out "RC 10";
|
||||
in "%(\$1M10)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
readRate {
|
||||
out "RR \$2";
|
||||
in "%f";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Testing Commands
|
||||
|
||||
switchTestgenOnOff {
|
||||
out "TG %{off|on}";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
# Only suppporting test channel 1 at the moment. (The first argument to TG)
|
||||
setTestSignal {
|
||||
out "TG 1 %(\$1TESTGEN-HIGHRATE)d %(\$1TESTGEN-LOWRATE)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Gating Settings
|
||||
|
||||
getGateStatus {
|
||||
out "GT \$2";
|
||||
in "%d %(\$1GATE-\$2-TRIG_RBV)d";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
setGateStatus {
|
||||
extrainput = ignore;
|
||||
out "GT \$2 %(\$1GATE-\$2-ENABLE)d %(\$1GATE-\$2-TRIG)d";
|
||||
in "Gate \$2";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
setGate {
|
||||
out "GATE \$2 %d";
|
||||
in "";
|
||||
@mismatch{in "%(\$1MsgTxt)s";}
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# TODO To clean
|
||||
|
||||
startWithCountPreset4 {
|
||||
clearTimer;
|
||||
clearCounter4;
|
||||
readAll4;
|
||||
startWithCountPreset;
|
||||
}
|
||||
|
||||
startWithCountPreset8 {
|
||||
clearTimer;
|
||||
clearCounter4;
|
||||
clearCounter8;
|
||||
readAll8;
|
||||
startWithCountPreset;
|
||||
}
|
||||
|
||||
startWithCountPreset10 {
|
||||
clearTimer;
|
||||
clearCounter4;
|
||||
clearCounter8;
|
||||
clearCounter10;
|
||||
readAll10;
|
||||
startWithCountPreset;
|
||||
}
|
||||
|
||||
startWithTimePreset4 {
|
||||
clearTimer;
|
||||
clearCounter4;
|
||||
readAll4;
|
||||
startWithTimePreset;
|
||||
}
|
||||
|
||||
startWithTimePreset8 {
|
||||
clearTimer;
|
||||
clearCounter4;
|
||||
clearCounter8;
|
||||
readAll8;
|
||||
startWithTimePreset;
|
||||
}
|
||||
|
||||
startWithTimePreset10 {
|
||||
clearTimer;
|
||||
clearCounter4;
|
||||
clearCounter8;
|
||||
clearCounter10;
|
||||
readAll10;
|
||||
startWithTimePreset;
|
||||
}
|
78
db/daq_2nd_gen.db
Normal file
78
db/daq_2nd_gen.db
Normal file
@ -0,0 +1,78 @@
|
||||
# EPICS Database for streamdevice support for functionality specific to the 2nd
|
||||
# Generation Systems
|
||||
#
|
||||
# Macros
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. DAQV2
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to DAQ
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):MONITOR-CHANNEL")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(DRVL, "1") # Smallest Monitor Channel
|
||||
field(DRVH, "$(CHANNELS)") # Largest Monitor Channel
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) writePresetMonitor($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(FLNK, "$(INSTR)$(NAME):MONITOR-CHANNEL_RBV")
|
||||
}
|
||||
|
||||
record(longin, "$(INSTR)$(NAME):MONITOR-CHANNEL_RBV")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(DTYP, "stream")
|
||||
field(INP, "@$(PROTO) readPresetMonitor($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(SCAN, "1 second")
|
||||
}
|
||||
|
||||
# Force back to 1 if it is 0, as 0 has no meaning...
|
||||
record(seq, "$(INSTR)$(NAME):CORRECT-MONITOR-CHANNEL")
|
||||
{
|
||||
field(SELM, "Specified")
|
||||
field(SELL, "$(INSTR)$(NAME):MONITOR-CHANNEL_RBV.VAL NPP")
|
||||
field(DO0, 1)
|
||||
field(LNK0, "$(INSTR)$(NAME):MONITOR-CHANNEL PP")
|
||||
field(SCAN, ".5 second")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
# The hardware stores a separate threshold for each channel, which is somewhat
|
||||
# unintuitive for the user, as only one can actually be made use of at a time.
|
||||
# So, we just write the threshold value to all channels when it is changed.
|
||||
record(dfanout,"$(INSTR)$(NAME):THRESHOLD-F")
|
||||
{
|
||||
field(OMSL, "supervisory")
|
||||
field(SELM, "All")
|
||||
field(OUTA, "$(INSTR)$(NAME):THRESHOLD-F1 PP")
|
||||
field(OUTB, "$(INSTR)$(NAME):THRESHOLD-F2 PP")
|
||||
}
|
||||
|
||||
record(dfanout,"$(INSTR)$(NAME):THRESHOLD-F1")
|
||||
{
|
||||
field(OMSL, "supervisory")
|
||||
field(SELM, "All")
|
||||
field(OUTA, "$(INSTR)$(NAME):THRESH1 PP")
|
||||
field(OUTB, "$(INSTR)$(NAME):THRESH2 PP")
|
||||
field(OUTC, "$(INSTR)$(NAME):THRESH3 PP")
|
||||
field(OUTD, "$(INSTR)$(NAME):THRESH4 PP")
|
||||
field(OUTE, "$(INSTR)$(NAME):THRESH5 PP")
|
||||
field(OUTF, "$(INSTR)$(NAME):THRESH6 PP")
|
||||
field(OUTG, "$(INSTR)$(NAME):THRESH7 PP")
|
||||
field(OUTH, "$(INSTR)$(NAME):THRESH8 PP")
|
||||
}
|
||||
|
||||
record(dfanout,"$(INSTR)$(NAME):THRESHOLD-F2")
|
||||
{
|
||||
field(OMSL, "supervisory")
|
||||
field(SELM, "All")
|
||||
field(OUTA, "$(INSTR)$(NAME):THRESH9 PP")
|
||||
field(OUTB, "$(INSTR)$(NAME):THRESH10 PP")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
40
db/daq_2nd_gen_test.db
Normal file
40
db/daq_2nd_gen_test.db
Normal file
@ -0,0 +1,40 @@
|
||||
# EPICS Database for streamdevice support for testing functionality specific to
|
||||
# the 2nd Generation Systems
|
||||
#
|
||||
# Macros
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. DAQV2
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to DAQ
|
||||
|
||||
################################################################################
|
||||
# Testing Commands
|
||||
|
||||
# These won't match the values on the machine after a full restart But I chose
|
||||
# not to force their intialisation as they are only important for testing
|
||||
|
||||
record(bo, "$(INSTR)$(NAME):TESTGEN")
|
||||
{
|
||||
field(DESC, "Turn on/off Testgen Signal")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) switchTestgenOnOff($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 0)
|
||||
field(ZNAM, "OFF")
|
||||
field(ONAM, "ON")
|
||||
}
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):TESTGEN-LOWRATE")
|
||||
{
|
||||
field(DESC, "Set Minimum Testgen Rate")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setTestSignal($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 1000)
|
||||
}
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):TESTGEN-HIGHRATE")
|
||||
{
|
||||
field(DESC, "Set Maximum Testgen Rate")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setTestSignal($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 1000)
|
||||
}
|
45
db/daq_4ch.db
Normal file
45
db/daq_4ch.db
Normal file
@ -0,0 +1,45 @@
|
||||
# EPICS Database for streamdevice support 1st gen systems with 4 channels
|
||||
#
|
||||
# Macros
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to DAQ
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):MONITOR-CHANNEL")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DRVL, "1") # Smallest Monitor Channel
|
||||
field(DRVH, "1") # Largest Monitor Channel
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
record(longin, "$(INSTR)$(NAME):MONITOR-CHANNEL_RBV")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
# The hardware stores a separate threshold for each channel, which is somewhat
|
||||
# unintuitive for the user, as only one can actually be made use of at a time.
|
||||
# So, we just write the threshold value to all channels when it is changed.
|
||||
record(dfanout,"$(INSTR)$(NAME):THRESHOLD-F")
|
||||
{
|
||||
field(OMSL, "supervisory")
|
||||
field(SELM, "All")
|
||||
field(OUTA, "$(INSTR)$(NAME):THRESH1 PP")
|
||||
field(OUTB, "$(INSTR)$(NAME):THRESH2 PP")
|
||||
field(OUTC, "$(INSTR)$(NAME):THRESH3 PP")
|
||||
field(OUTD, "$(INSTR)$(NAME):THRESH4 PP")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
49
db/daq_8ch.db
Normal file
49
db/daq_8ch.db
Normal file
@ -0,0 +1,49 @@
|
||||
# EPICS Database for streamdevice support 1st gen systems with 8 channels
|
||||
#
|
||||
# Macros
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to DAQ
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):MONITOR-CHANNEL")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DRVL, "1") # Smallest Monitor Channel
|
||||
field(DRVH, "1") # Largest Monitor Channel
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
record(longin, "$(INSTR)$(NAME):MONITOR-CHANNEL_RBV")
|
||||
{
|
||||
field(DESC, "PRESET-COUNT Monitors this channel")
|
||||
field(VAL, 1)
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
# The hardware stores a separate threshold for each channel, which is somewhat
|
||||
# unintuitive for the user, as only one can actually be made use of at a time.
|
||||
# So, we just write the threshold value to all channels when it is changed.
|
||||
record(dfanout,"$(INSTR)$(NAME):THRESHOLD-F")
|
||||
{
|
||||
field(OMSL, "supervisory")
|
||||
field(SELM, "All")
|
||||
field(OUTA, "$(INSTR)$(NAME):THRESH1 PP")
|
||||
field(OUTB, "$(INSTR)$(NAME):THRESH2 PP")
|
||||
field(OUTC, "$(INSTR)$(NAME):THRESH3 PP")
|
||||
field(OUTD, "$(INSTR)$(NAME):THRESH4 PP")
|
||||
field(OUTE, "$(INSTR)$(NAME):THRESH5 PP")
|
||||
field(OUTF, "$(INSTR)$(NAME):THRESH6 PP")
|
||||
field(OUTG, "$(INSTR)$(NAME):THRESH7 PP")
|
||||
field(OUTH, "$(INSTR)$(NAME):THRESH8 PP")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
243
db/daq_common.db
Normal file
243
db/daq_common.db
Normal file
@ -0,0 +1,243 @@
|
||||
# EPICS Database for streamdevice support with SinqDAQ Systems
|
||||
#
|
||||
# Macros
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to EL737
|
||||
|
||||
# Send initial initialisation commands
|
||||
record(bo, "$(INSTR)$(NAME):INIT-CONF")
|
||||
{
|
||||
field(DESC, "Initialises the DAQ")
|
||||
field(OUT, "@$(PROTO) initialise($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(PINI, "YES") # Run at init
|
||||
field(DTYP, "stream")
|
||||
}
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):FULL-RESET")
|
||||
{
|
||||
field(DESC, "Reset the DAQ")
|
||||
field(OUT, "@$(PROTO) fullReset($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Status Variables
|
||||
|
||||
record(stringin, "$(INSTR)$(NAME):MsgTxt")
|
||||
{
|
||||
field(DESC, "Unexpected received response")
|
||||
field(DTYP, "devDAQStringError")
|
||||
field(FLNK, "$(INSTR)$(NAME):INVALID-CONFIG")
|
||||
}
|
||||
|
||||
# We want to recognise the invalid config error message, so that we can rerun
|
||||
# the init if it occurs. This should only happen after turning the DAQ off and
|
||||
# on again or running a full reset
|
||||
record(scalcout, "$(INSTR)$(NAME):INVALID-CONFIG")
|
||||
{
|
||||
field(DESC, "Has the DAQ been configured?")
|
||||
field(CALC, "AA[0,2] == '?OF'")
|
||||
field(INAA, "$(INSTR)$(NAME):MsgTxt")
|
||||
field(FLNK, "$(INSTR)$(NAME):REINIT-CONF")
|
||||
}
|
||||
|
||||
record(seq, "$(INSTR)$(NAME):REINIT-CONF")
|
||||
{
|
||||
field(LNK1, "$(INSTR)$(NAME):INIT-CONF PP")
|
||||
field(DO1, 1)
|
||||
field(SELM, "Specified")
|
||||
field(SELL, "$(INSTR)$(NAME):INVALID-CONFIG.VAL")
|
||||
}
|
||||
|
||||
# Important! The "$(INSTR)$(NAME):READALL" isn't configure with a SCAN. Instead,
|
||||
# it must always be triggered after the value of $(INSTR)$(NAME):RAW-STATUS is
|
||||
# updated, so that it can't be the case that the status changes back from
|
||||
# counting to idle, without having updated the time and count values.
|
||||
record(longin, "$(INSTR)$(NAME):RAW-STATUS")
|
||||
{
|
||||
field(DESC, "Raw returned status value")
|
||||
field(DTYP, "stream")
|
||||
field(SCAN, ".5 second")
|
||||
field(INP, "@$(PROTO) readStatus($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(FLNK, "$(INSTR)$(NAME):READALL")
|
||||
}
|
||||
|
||||
record(calc, "$(INSTR)$(NAME):MAP-STATUS")
|
||||
{
|
||||
field(DESC, "Maps Raw Status to State")
|
||||
field(INPA, "$(INSTR)$(NAME):RAW-STATUS NPP")
|
||||
field(INPB, "$(INSTR)$(NAME):INVALID-CONFIG NPP")
|
||||
field(INPC, "$(INSTR)$(NAME):RAW-STATUS.UDF NPP") # should also be invalid if can't read the status
|
||||
field(CALC, "(B=1||C==1)?4:A=0?0:(A=1||A=2)?1:(A=5||A=6)?2:(A=9||A=13||A=10||A=14)?3:4")
|
||||
field(FLNK, "$(INSTR)$(NAME):STATUS")
|
||||
}
|
||||
|
||||
record(mbbi, "$(INSTR)$(NAME):STATUS")
|
||||
{
|
||||
field(DESC, "DAQ Status")
|
||||
field(INP, "$(INSTR)$(NAME):MAP-STATUS NPP")
|
||||
field(ZRVL, "0")
|
||||
field(ZRST, "Idle")
|
||||
field(ONVL, "1")
|
||||
field(ONST, "Counting")
|
||||
field(TWVL, "2")
|
||||
field(TWST, "Low rate")
|
||||
field(THVL, "3")
|
||||
field(THST, "Paused")
|
||||
# 4 should never happen, if it does it means the DAQ reports undocumented statusbits
|
||||
field(FRVL, "4")
|
||||
field(FRST, "INVALID")
|
||||
}
|
||||
|
||||
record(longin, "$(INSTR)$(NAME):CHANNELS")
|
||||
{
|
||||
field(DESC, "Total Supported Channels")
|
||||
field(VAL, $(CHANNELS))
|
||||
field(DISP, 1)
|
||||
}
|
||||
|
||||
# Trigger a change in status as clearing
|
||||
record(bo, "$(INSTR)$(NAME):ETT")
|
||||
{
|
||||
field(DESC, "Trigger Clearing Status")
|
||||
field(VAL, 1)
|
||||
field(OUT, "$(INSTR)$(NAME):ETS PP")
|
||||
}
|
||||
|
||||
# Trigger a change in status as value returned to 0
|
||||
record(seq, "$(INSTR)$(NAME):ETO")
|
||||
{
|
||||
field(DESC, "Trigger Returned to 0 Status")
|
||||
field(LNK0, "$(INSTR)$(NAME):ETS PP")
|
||||
field(DO0, 0)
|
||||
field(SELM, "Specified")
|
||||
field(SELL, "$(INSTR)$(NAME):ELAPSED-TIME.VAL")
|
||||
}
|
||||
|
||||
# Current Status of Channel, i.e. is it ready to count?
|
||||
record(bi, "$(INSTR)$(NAME):ETS")
|
||||
{
|
||||
field(DESC, "Channel Status")
|
||||
field(VAL, 0)
|
||||
field(ZNAM, "OK")
|
||||
field(ONAM, "CLEARING")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Count Commands
|
||||
|
||||
record(ao,"$(INSTR)$(NAME):PRESET-COUNT")
|
||||
{
|
||||
field(DESC, "Count until preset reached")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) startWithCountPreset$(CHANNELS)($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 0)
|
||||
field(PREC, 2)
|
||||
field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
|
||||
}
|
||||
|
||||
record(ao,"$(INSTR)$(NAME):PRESET-TIME")
|
||||
{
|
||||
field(DESC, "Count for specified time")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) startWithTimePreset$(CHANNELS)($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, 0)
|
||||
field(PREC, 2)
|
||||
field(EGU, "seconds")
|
||||
field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
|
||||
}
|
||||
|
||||
record(bo,"$(INSTR)$(NAME):PAUSE")
|
||||
{
|
||||
field(DESC, "Pause the current count")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) pauseCount($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, "0")
|
||||
field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
|
||||
}
|
||||
|
||||
record(bo,"$(INSTR)$(NAME):CONTINUE")
|
||||
{
|
||||
field(DESC, "Continue with a count that was paused")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) continueCount($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(VAL, "0")
|
||||
field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
|
||||
}
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):STOP")
|
||||
{
|
||||
field(DESC, "Stop the current counting operation")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) stopCount($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(FLNK, "$(INSTR)$(NAME):RAW-STATUS")
|
||||
}
|
||||
|
||||
record(ao,"$(INSTR)$(NAME):THRESHOLD")
|
||||
{
|
||||
field(DESC, "Minimum rate for counting to proceed")
|
||||
field(VAL, "1") # Default Rate
|
||||
# Could perhaps still be improved.
|
||||
# It seems to only accept whole counts?
|
||||
field(DRVL, "1") # Minimum Rate
|
||||
field(DRVH, "100000") # Maximum Rate
|
||||
field(OMSL, "supervisory")
|
||||
field(OROC, "0")
|
||||
field(OUT, "$(INSTR)$(NAME):THRESHOLD-F PP")
|
||||
}
|
||||
|
||||
record(ai,"$(INSTR)$(NAME):THRESHOLD_RBV")
|
||||
{
|
||||
field(DESC, "Minimum rate for counting to proceed")
|
||||
field(INP, "@$(PROTO) readMinRate($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
field(SCAN, "1 second")
|
||||
field(EGU, "cts/sec")
|
||||
}
|
||||
|
||||
record(longout,"$(INSTR)$(NAME):THRESHOLD-MONITOR")
|
||||
{
|
||||
field(DESC, "Channel monitored for minimum rate")
|
||||
field(VAL, "1") # Monitor
|
||||
field(DRVL, "0") # Smallest Threshold Channel (0 is off)
|
||||
field(DRVH, "$(CHANNELS)") # Largest Threshold Channel
|
||||
field(OUT, "@$(PROTO) setRateMonitor($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
}
|
||||
|
||||
record(longin,"$(INSTR)$(NAME):THRESHOLD-MONITOR_RBV")
|
||||
{
|
||||
field(DESC, "Channel monitored for minimum rate")
|
||||
field(INP, "@$(PROTO) readRateMonitor($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
field(SCAN, "1 second")
|
||||
field(EGU, "CH")
|
||||
}
|
||||
|
||||
record(longout, "$(INSTR)$(NAME):CT")
|
||||
{
|
||||
field(DESC, "Clear the timer")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) clearTimer($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(FLNK, "$(INSTR)$(NAME):ETT")
|
||||
}
|
||||
|
||||
################################################################################
|
||||
# Read all monitors values
|
||||
|
||||
record(ai, "$(INSTR)$(NAME):READALL")
|
||||
{
|
||||
field(DESC, "Reads monitors and elapsed time")
|
||||
field(INP, "@$(PROTO) readAll$(CHANNELS)($(INSTR)$(NAME):) $(ASYN_PORT)")
|
||||
field(DTYP, "stream")
|
||||
field(FLNK, "$(INSTR)$(NAME):MAP-STATUS")
|
||||
}
|
||||
|
||||
record(ai,"$(INSTR)$(NAME):ELAPSED-TIME")
|
||||
{
|
||||
field(DESC, "DAQ Measured Time")
|
||||
field(EGU, "sec")
|
||||
field(FLNK, "$(INSTR)$(NAME):ETO")
|
||||
}
|
27
db/daq_simcontrol.db
Normal file
27
db/daq_simcontrol.db
Normal file
@ -0,0 +1,27 @@
|
||||
# Sinq DAQ EPICS Database for StreamDevice Communication with Simulation
|
||||
# Macros
|
||||
#
|
||||
# INSTR - Prefix
|
||||
# NAME - just a name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to EL737
|
||||
|
||||
################################################################################
|
||||
|
||||
record(bo, "$(INSTR)$(NAME):G1")
|
||||
{
|
||||
field(DESC, "Set Gate 1 Low/High")
|
||||
field(ZNAM, "Low")
|
||||
field(ONAM, "High")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setGate($(INSTR)$(NAME):, 1) $(ASYN_PORT)")
|
||||
}
|
||||
|
||||
record(bo, "$(INSTR)$(NAME):G2")
|
||||
{
|
||||
field(DESC, "Set Gate 2 Low/High")
|
||||
field(ZNAM, "Low")
|
||||
field(ONAM, "High")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setGate($(INSTR)$(NAME):, 2) $(ASYN_PORT)")
|
||||
}
|
102
db/gating_channels.db
Normal file
102
db/gating_channels.db
Normal file
@ -0,0 +1,102 @@
|
||||
# EPICS Database for streamdevice specific to gating channels
|
||||
#
|
||||
# Macros
|
||||
# INSTR - Prefix
|
||||
# NAME - the device name, e.g. EL737
|
||||
# PROTO - Stream device protocol file
|
||||
# ASYN_PORT - Low level Asyn IP Port to DAQ
|
||||
# CHANNEL - the number associated with the measurment channel
|
||||
|
||||
################################################################################
|
||||
|
||||
# Records for configuring gating settings
|
||||
record(mbbo, "$(INSTR)$(NAME):GATE-$(CHANNEL)")
|
||||
{
|
||||
field(DESC, "Sets the current gate state")
|
||||
field(DTYP, "Soft Channel")
|
||||
field(OUT, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SET PP")
|
||||
field(ZRST, "Disabled")
|
||||
field(ONST, "Trigger Low")
|
||||
field(TWST, "Trigger High")
|
||||
}
|
||||
|
||||
record(dfanout, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SET")
|
||||
{
|
||||
field(OUTA, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SEL.SELN PP")
|
||||
field(OUTB, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SEL2.SELN PP")
|
||||
}
|
||||
|
||||
record(seq, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SEL")
|
||||
{
|
||||
field(SELM, "Specified")
|
||||
field(DO0, 0)
|
||||
field(LNK0, "$(INSTR)$(NAME):GATE-$(CHANNEL)-ENABLE PP")
|
||||
field(DO1, 1)
|
||||
field(LNK1, "$(INSTR)$(NAME):GATE-$(CHANNEL)-ENABLE PP")
|
||||
field(DO2, 1)
|
||||
field(LNK2, "$(INSTR)$(NAME):GATE-$(CHANNEL)-ENABLE PP")
|
||||
}
|
||||
|
||||
record(bo, "$(INSTR)$(NAME):GATE-$(CHANNEL)-ENABLE")
|
||||
{
|
||||
field(DESC, "Enable Gating Channel")
|
||||
field(ZNAM, "Disabled")
|
||||
field(ONAM, "Enabled")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setGateStatus($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)")
|
||||
}
|
||||
|
||||
record(seq, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SEL2")
|
||||
{
|
||||
field(SELM, "Specified")
|
||||
field(DO1, 0)
|
||||
field(LNK1, "$(INSTR)$(NAME):GATE-$(CHANNEL)-TRIG PP")
|
||||
field(DO2, 1)
|
||||
field(LNK2, "$(INSTR)$(NAME):GATE-$(CHANNEL)-TRIG PP")
|
||||
}
|
||||
|
||||
record(bo, "$(INSTR)$(NAME):GATE-$(CHANNEL)-TRIG")
|
||||
{
|
||||
field(DESC, "Set Count when first Gate high/low")
|
||||
field(ZNAM, "Low")
|
||||
field(ONAM, "High")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@$(PROTO) setGateStatus($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)")
|
||||
}
|
||||
|
||||
# Records for reading configured gating settings
|
||||
record(mbbi, "$(INSTR)$(NAME):GATE-$(CHANNEL)_RBV")
|
||||
{
|
||||
field(DESC, "The current gate state")
|
||||
field(ZRST, "Disabled")
|
||||
field(ONST, "Trigger Low")
|
||||
field(TWST, "Trigger High")
|
||||
}
|
||||
|
||||
record(calcout, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SEL_RBV")
|
||||
{
|
||||
field(INPA, "$(INSTR)$(NAME):GATE-$(CHANNEL)-ENABLE_RBV NPP")
|
||||
field(INPB, "$(INSTR)$(NAME):GATE-$(CHANNEL)-TRIG_RBV NPP")
|
||||
field(CALC, "A=0?0:B=0?1:2")
|
||||
field(OOPT, "On Change")
|
||||
field(OUT, "$(INSTR)$(NAME):GATE-$(CHANNEL)_RBV PP")
|
||||
field(FLNK, "$(INSTR)$(NAME):GATE-$(CHANNEL)_RBV")
|
||||
}
|
||||
|
||||
record(bi, "$(INSTR)$(NAME):GATE-$(CHANNEL)-ENABLE_RBV")
|
||||
{
|
||||
field(DESC, "Is Gating Channel Enabled")
|
||||
field(ZNAM, "Disabled")
|
||||
field(ONAM, "Enabled")
|
||||
field(DTYP, "stream")
|
||||
field(INP, "@$(PROTO) getGateStatus($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)")
|
||||
field(SCAN, "2 second")
|
||||
field(FLNK, "$(INSTR)$(NAME):GATE-$(CHANNEL)-SEL_RBV")
|
||||
}
|
||||
|
||||
record(bi, "$(INSTR)$(NAME):GATE-$(CHANNEL)-TRIG_RBV")
|
||||
{
|
||||
field(DESC, "Count when first Gate high/low")
|
||||
field(ZNAM, "Low")
|
||||
field(ONAM, "High")
|
||||
}
|
@ -1,22 +0,0 @@
|
||||
require asyn
|
||||
require stream
|
||||
|
||||
epicsEnvSet("$(NAME)_CNTBOX_HOST", "$(CNTBOX_IP):$(CNTBOX_PORT)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) require misc
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) epicsEnvSet("$(NAME)_CNTBOX_HOST", "127.0.0.1:$(CNTBOX_PORT)")
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) system "$(counterbox_DIR)counterbox_sim.py $(CNTBOX_PORT) 4 &"
|
||||
# starting the python socket seems to take a while
|
||||
# and need misc to use built in sleep command
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) sleep 3
|
||||
|
||||
epicsEnvSet("PROTO", "$(counterbox_DB)counterbox.proto")
|
||||
drvAsynIPPortConfigure("ASYN_$(NAME)", "$($(NAME)_CNTBOX_HOST)", 0, 0, 0)
|
||||
dbLoadRecords("$(counterbox_DB)counterbox_common.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=4")
|
||||
dbLoadRecords("$(counterbox_DB)counterbox_4ch.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
||||
|
||||
# Could also use substitions instead.
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=2")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=3")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=4")
|
@ -1,26 +0,0 @@
|
||||
require asyn
|
||||
require stream
|
||||
|
||||
epicsEnvSet("$(NAME)_CNTBOX_HOST", "$(CNTBOX_IP):$(CNTBOX_PORT)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) require misc
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) epicsEnvSet("$(NAME)_CNTBOX_HOST", "127.0.0.1:$(CNTBOX_PORT)")
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) system "$(counterbox_DIR)counterbox_sim.py $(CNTBOX_PORT) 10 &"
|
||||
# starting the python socket seems to take a while
|
||||
# and need misc to use built in sleep command
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) sleep 3
|
||||
|
||||
epicsEnvSet("PROTO", "$(counterbox_DB)counterbox.proto")
|
||||
drvAsynIPPortConfigure("ASYN_$(NAME)", "$($(NAME)_CNTBOX_HOST)", 0, 0, 0)
|
||||
dbLoadRecords("$(counterbox_DB)counterbox_common.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=8")
|
||||
dbLoadRecords("$(counterbox_DB)counterbox_8ch.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
||||
|
||||
# Could also use substitions instead.
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=2")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=3")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=4")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=5")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=6")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=7")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=8")
|
@ -1,30 +0,0 @@
|
||||
require asyn
|
||||
require stream
|
||||
|
||||
epicsEnvSet("$(NAME)_CNTBOX_HOST", "$(CNTBOX_IP):$(CNTBOX_PORT=2000)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) require misc
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) epicsEnvSet("$(NAME)_CNTBOX_HOST", "127.0.0.1:$(CNTBOX_PORT=2000)")
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) system "$(counterbox_DIR)counterbox_sim.py $(CNTBOX_PORT=2000) 10 &"
|
||||
# starting the python socket seems to take a while
|
||||
# and need misc to use built in sleep command
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) sleep 3
|
||||
|
||||
epicsEnvSet("PROTO", "$(counterbox_DB)counterbox.proto")
|
||||
drvAsynIPPortConfigure("ASYN_$(NAME)", "$($(NAME)_CNTBOX_HOST)", 0, 0, 0)
|
||||
dbLoadRecords("$(counterbox_DB)counterbox_common.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=10")
|
||||
dbLoadRecords("$(counterbox_DB)counterbox_v2.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
||||
|
||||
# Could also use substitions instead.
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=2")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=3")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=4")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=5")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=6")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=7")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=8")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=9")
|
||||
dbLoadRecords("$(counterbox_DB)channels.db", "P=$(PREFIX), NAME=$(NAME), CHANNEL=10")
|
||||
|
||||
$(LOAD_TEST_PVS=#) $(LOAD_TEST_PVS) dbLoadRecords("$(counterbox_DB)counterbox_v2_test.db", "P=$(PREFIX), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
35
scripts/daq_2nd_gen.cmd
Normal file
35
scripts/daq_2nd_gen.cmd
Normal file
@ -0,0 +1,35 @@
|
||||
require asyn
|
||||
require stream
|
||||
|
||||
epicsEnvSet("$(NAME)_DAQ_HOST", "$(DAQ_IP):$(DAQ_PORT=2000)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) require misc
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) epicsEnvSet("$(NAME)_DAQ_HOST", "127.0.0.1:$(DAQ_PORT=2000)")
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) system "$(sinqDAQ_DIR)daq_sim.py $(DAQ_PORT=2000) 10 &"
|
||||
# starting the python socket seems to take a while
|
||||
# and need misc to use built in sleep command
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) sleep 3
|
||||
|
||||
epicsEnvSet("PROTO", "$(sinqDAQ_DB)daq.proto")
|
||||
drvAsynIPPortConfigure("ASYN_$(NAME)", "$($(NAME)_DAQ_HOST)", 0, 0, 0)
|
||||
dbLoadRecords("$(sinqDAQ_DB)daq_common.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=10")
|
||||
dbLoadRecords("$(sinqDAQ_DB)daq_2nd_gen.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=10")
|
||||
|
||||
# Could also use substitions instead.
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=2")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=3")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=4")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=5")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=6")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=7")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=8")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=9")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=10")
|
||||
|
||||
dbLoadRecords("$(sinqDAQ_DB)gating_channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(sinqDAQ_DB)gating_channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=2")
|
||||
|
||||
$(LOAD_TEST_PVS=#) $(LOAD_TEST_PVS) dbLoadRecords("$(sinqDAQ_DB)daq_2nd_gen_test.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) dbLoadRecords("$(sinqDAQ_DB)daq_simcontrol.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
22
scripts/daq_4ch.cmd
Normal file
22
scripts/daq_4ch.cmd
Normal file
@ -0,0 +1,22 @@
|
||||
require asyn
|
||||
require stream
|
||||
|
||||
epicsEnvSet("$(NAME)_DAQ_HOST", "$(DAQ_IP):$(DAQ_PORT)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) require misc
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) epicsEnvSet("$(NAME)_DAQ_HOST", "127.0.0.1:$(DAQ_PORT)")
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) system "$(sinqDAQ_DIR)daq_sim.py $(DAQ_PORT) 4 &"
|
||||
# starting the python socket seems to take a while
|
||||
# and need misc to use built in sleep command
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) sleep 3
|
||||
|
||||
epicsEnvSet("PROTO", "$(sinqDAQ_DB)daq.proto")
|
||||
drvAsynIPPortConfigure("ASYN_$(NAME)", "$($(NAME)_DAQ_HOST)", 0, 0, 0)
|
||||
dbLoadRecords("$(sinqDAQ_DB)daq_common.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=4")
|
||||
dbLoadRecords("$(sinqDAQ_DB)daq_4ch.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
||||
|
||||
# Could also use substitions instead.
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=2")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=3")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=4")
|
26
scripts/daq_8ch.cmd
Normal file
26
scripts/daq_8ch.cmd
Normal file
@ -0,0 +1,26 @@
|
||||
require asyn
|
||||
require stream
|
||||
|
||||
epicsEnvSet("$(NAME)_DAQ_HOST", "$(DAQ_IP):$(DAQ_PORT)")
|
||||
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) require misc
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) epicsEnvSet("$(NAME)_DAQ_HOST", "127.0.0.1:$(DAQ_PORT)")
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) system "$(sinqDAQ_DIR)daq_sim.py $(DAQ_PORT) 8 &"
|
||||
# starting the python socket seems to take a while
|
||||
# and need misc to use built in sleep command
|
||||
$(SET_SIM_MODE=#) $(SET_SIM_MODE) sleep 3
|
||||
|
||||
epicsEnvSet("PROTO", "$(sinqDAQ_DB)daq.proto")
|
||||
drvAsynIPPortConfigure("ASYN_$(NAME)", "$($(NAME)_DAQ_HOST)", 0, 0, 0)
|
||||
dbLoadRecords("$(sinqDAQ_DB)daq_common.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNELS=8")
|
||||
dbLoadRecords("$(sinqDAQ_DB)daq_8ch.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME)")
|
||||
|
||||
# Could also use substitions instead.
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=1")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=2")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=3")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=4")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=5")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=6")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=7")
|
||||
dbLoadRecords("$(sinqDAQ_DB)channels.db", "INSTR=$(INSTR), NAME=$(NAME), PROTO=$(PROTO), ASYN_PORT=ASYN_$(NAME), CHANNEL=8")
|
@ -1,146 +0,0 @@
|
||||
#!/usr/bin/env python3
|
||||
|
||||
import re
|
||||
import socket
|
||||
import sys
|
||||
import time
|
||||
|
||||
from random import randrange
|
||||
|
||||
HOST = "127.0.0.1" # Localhost
|
||||
PORT = int(sys.argv[1]) # Port to listen on
|
||||
TOTAL_CH = int(sys.argv[2]) # Number of Channels
|
||||
|
||||
|
||||
class CounterBox:
|
||||
def __init__(self, total_channels):
|
||||
self.total_channels = total_channels
|
||||
self.counts = [0] * self.total_channels
|
||||
|
||||
self.status = 0
|
||||
self.countmode = 'time'
|
||||
self.presettime = 0
|
||||
self.presetcount = 0
|
||||
self.starttime = 0
|
||||
self.elapsed = 0
|
||||
self.monitor = 0
|
||||
|
||||
def resetCounts(self):
|
||||
self.counts = [0] * self.total_channels
|
||||
self.starttime = time.time()
|
||||
self.elapsed = 0
|
||||
|
||||
def getStatus(self):
|
||||
return self.status
|
||||
|
||||
def getCounts(self):
|
||||
return self.counts
|
||||
|
||||
def getMonitorCount(self):
|
||||
return self.counts[self.monitor]
|
||||
|
||||
def updateCounts(self):
|
||||
for i in range(self.total_channels):
|
||||
self.counts[i] += randrange(5)
|
||||
|
||||
def getRunTime(self):
|
||||
elapsed = round(time.time() - self.starttime, 3)
|
||||
|
||||
if self.countmode == 'time':
|
||||
if elapsed < self.presettime:
|
||||
self.updateCounts()
|
||||
self.elapsed = elapsed
|
||||
else:
|
||||
self.elapsed = self.presettime
|
||||
self.status = 0
|
||||
|
||||
elif self.countmode == 'count':
|
||||
if self.getMonitorCount() < self.presetcount:
|
||||
self.updateCounts()
|
||||
self.elapsed = elapsed
|
||||
|
||||
if self.getMonitorCount() >= self.presetcount:
|
||||
self.counts[self.monitor] = self.presetcount
|
||||
self.status = 0
|
||||
|
||||
else:
|
||||
raise Exception("Invalid State")
|
||||
|
||||
return self.elapsed
|
||||
|
||||
def startTimePreset(self, presettime):
|
||||
self.countmode = 'time'
|
||||
self.status = 1
|
||||
self.presettime = round(presettime, 3)
|
||||
self.resetCounts()
|
||||
|
||||
def startCountPreset(self, presetcount):
|
||||
self.countmode = 'count'
|
||||
self.status = 1
|
||||
self.presetcount = presetcount
|
||||
self.resetCounts()
|
||||
|
||||
with socket.socket(socket.AF_INET, socket.SOCK_STREAM) as s:
|
||||
|
||||
s.bind((HOST, PORT))
|
||||
s.listen()
|
||||
conn, addr = s.accept()
|
||||
with conn:
|
||||
|
||||
def send(data: str):
|
||||
if data:
|
||||
return conn.sendall(f'{data}\r'.encode())
|
||||
else:
|
||||
return conn.sendall(b'\r')
|
||||
|
||||
def receive():
|
||||
data = conn.recv(1024)
|
||||
if data:
|
||||
# also removes terminator
|
||||
return data.decode('ascii').rstrip()
|
||||
else:
|
||||
return ''
|
||||
|
||||
counterbox = CounterBox(TOTAL_CH)
|
||||
|
||||
while True:
|
||||
|
||||
data = receive()
|
||||
|
||||
if not data: # Empty implies client disconnected
|
||||
break # Close Server
|
||||
|
||||
try:
|
||||
|
||||
if data == 'RMT 1':
|
||||
send('')
|
||||
|
||||
elif data == 'ECHO 2':
|
||||
send('Counterbox') # Sends some sort of info command
|
||||
|
||||
elif data == 'RA':
|
||||
send(
|
||||
' '.join(map(str,
|
||||
[counterbox.getRunTime()] + \
|
||||
counterbox.getCounts()
|
||||
))
|
||||
)
|
||||
|
||||
elif data == 'RS':
|
||||
send(str(counterbox.getStatus()))
|
||||
|
||||
elif re.fullmatch(r'TP (\d+(\.\d+)?)', data):
|
||||
presettime = float(re.fullmatch(r'TP (\d+(\.\d+)?)', data).group(1))
|
||||
counterbox.startTimePreset(presettime)
|
||||
send('')
|
||||
|
||||
elif re.fullmatch(r'MP (\d+)', data):
|
||||
counts = int(re.fullmatch(r'MP (\d+)', data).group(1))
|
||||
counterbox.startCountPreset(counts)
|
||||
send('')
|
||||
|
||||
else:
|
||||
send('?2') # Bad command
|
||||
|
||||
except:
|
||||
send('?OV')
|
331
sim/daq_sim.py
Normal file
331
sim/daq_sim.py
Normal file
@ -0,0 +1,331 @@
|
||||
#!/usr/bin/env python3
|
||||
|
||||
import os
|
||||
import re
|
||||
import socket
|
||||
import sys
|
||||
import time
|
||||
|
||||
from random import randrange
|
||||
|
||||
HOST = "127.0.0.1" # Localhost
|
||||
PORT = int(sys.argv[1]) # Port to listen on
|
||||
TOTAL_CH = int(sys.argv[2]) # Number of Channels
|
||||
LOG2FILE = False if len(sys.argv) < 4 else bool(int(sys.argv[3]))
|
||||
|
||||
import logging
|
||||
logger = logging.getLogger('daq')
|
||||
|
||||
if LOG2FILE:
|
||||
logging.basicConfig(filename=os.path.join(os.getcwd(), 'daq_sim.log'), level=logging.INFO)
|
||||
|
||||
|
||||
class DAQ:
|
||||
def __init__(self, total_channels):
|
||||
self.total_channels = total_channels
|
||||
self.counts = [0] * self.total_channels
|
||||
self.rates = [randrange(5) for i in range(self.total_channels)]
|
||||
|
||||
self.status = 0
|
||||
self.countmode = 'time'
|
||||
self.presettime = 0
|
||||
self.presetcount = 0
|
||||
self.starttime = 0
|
||||
self.elapsed = 0
|
||||
self.monitor = 0
|
||||
|
||||
self.minratechannel = 0
|
||||
self.minrates = [2] * self.total_channels
|
||||
|
||||
self.gate_config = [
|
||||
#(enabled, count high/low),
|
||||
( False, True),
|
||||
( False, True),
|
||||
]
|
||||
|
||||
self.gate = [
|
||||
# high/low
|
||||
False,
|
||||
False,
|
||||
]
|
||||
|
||||
def clearCount(self, counter):
|
||||
self.counts[counter-1] = 0
|
||||
|
||||
def clearCounts(self):
|
||||
self.counts = [0] * self.total_channels
|
||||
|
||||
def clearTime(self):
|
||||
self.elapsed = 0
|
||||
self.starttime = time.time()
|
||||
|
||||
def getStatus(self):
|
||||
return self.status
|
||||
|
||||
def getCount(self, channel):
|
||||
return self.counts[channel - 1]
|
||||
|
||||
def getCounts(self):
|
||||
# The sinqtest daq returns a maximum of 8
|
||||
return self.counts[0:min(len(self.counts), 8)]
|
||||
|
||||
def getMonitorCount(self):
|
||||
return self.counts[self.monitor]
|
||||
|
||||
def updateRates(self):
|
||||
for i in range(self.total_channels):
|
||||
self.rates[i] = randrange(5)
|
||||
|
||||
def updateCounts(self):
|
||||
for i in range(self.total_channels):
|
||||
self.counts[i] += self.rates[i]
|
||||
|
||||
def getRunTime(self):
|
||||
elapsed = round(time.time() - self.starttime, 3)
|
||||
self.updateRates()
|
||||
|
||||
# If gating and a low rate threshold are enabled, then the threshold
|
||||
# seems to have precedence and sets the status to 5.
|
||||
# If we are waiting on the gate, then the status is just 1 as normal
|
||||
# after having started a count.
|
||||
|
||||
if self.countmode == 'time':
|
||||
if elapsed < self.presettime:
|
||||
|
||||
if self.minratechannel >= 0 and self.rates[self.minratechannel] < self.minrates[self.minratechannel]:
|
||||
# adjust the starttime, so that it is as if this polling period didn't happen
|
||||
self.starttime += elapsed - self.elapsed
|
||||
self.status = 5
|
||||
return self.elapsed
|
||||
|
||||
self.status = 1
|
||||
|
||||
for i in range(len(self.gate)):
|
||||
# If the gating is enabled and the signal is in the active position
|
||||
if self.gate_config[i][0] and self.gate_config[i][1] != self.gate[i]:
|
||||
self.starttime += elapsed - self.elapsed
|
||||
return self.elapsed
|
||||
|
||||
self.updateCounts()
|
||||
self.elapsed = elapsed
|
||||
else:
|
||||
self.elapsed = self.presettime if self.presettime > 0 else self.elapsed
|
||||
self.status = 0
|
||||
|
||||
elif self.countmode == 'count':
|
||||
if self.getMonitorCount() < self.presetcount:
|
||||
|
||||
if self.minratechannel >= 0 and self.rates[self.minratechannel] < self.minrates[self.minratechannel]:
|
||||
# adjust the starttime, so that it is as if this polling period didn't happen
|
||||
self.starttime += elapsed - self.elapsed
|
||||
self.status = 5
|
||||
return self.elapsed
|
||||
|
||||
self.status = 1
|
||||
|
||||
for i in range(len(self.gate)):
|
||||
# If the gating is enabled and the signal is in the active position
|
||||
if self.gate_config[i][0] and self.gate_config[i][1] != self.gate[i]:
|
||||
self.starttime += elapsed - self.elapsed
|
||||
return self.elapsed
|
||||
|
||||
self.updateCounts()
|
||||
self.elapsed = elapsed
|
||||
|
||||
if self.getMonitorCount() >= self.presetcount:
|
||||
self.counts[self.monitor] = self.presetcount if self.presetcount > 0 else self.counts[self.monitor]
|
||||
self.status = 0
|
||||
|
||||
else:
|
||||
raise Exception("Invalid State")
|
||||
|
||||
return self.elapsed
|
||||
|
||||
def stop(self):
|
||||
self.getRunTime()
|
||||
self.status = 0
|
||||
self.presettime = 0
|
||||
self.presetcount = 0
|
||||
|
||||
def startTimePreset(self, presettime):
|
||||
self.countmode = 'time'
|
||||
self.status = 1
|
||||
self.presettime = round(presettime, 3)
|
||||
self.clearTime()
|
||||
self.clearCounts()
|
||||
|
||||
def startCountPreset(self, presetcount):
|
||||
self.countmode = 'count'
|
||||
self.status = 1
|
||||
self.presetcount = presetcount
|
||||
self.clearTime()
|
||||
self.clearCounts()
|
||||
|
||||
def setMonitorChannel(self, channel):
|
||||
self.monitor = channel - 1
|
||||
|
||||
def getMonitorChannel(self):
|
||||
return self.monitor + 1
|
||||
|
||||
def getRate(self, channel):
|
||||
return float(self.rates[channel - 1])
|
||||
|
||||
def getMinRateChannel(self):
|
||||
return self.minratechannel + 1
|
||||
|
||||
def setMinRateChannel(self, channel):
|
||||
self.minratechannel = channel - 1
|
||||
|
||||
def getMinRate(self, channel):
|
||||
return self.minrates[channel - 1]
|
||||
|
||||
def setMinRate(self, channel, rate):
|
||||
self.minrates[channel - 1] = rate
|
||||
|
||||
def getGateStatus(self, channel):
|
||||
return self.gate_config[channel - 1]
|
||||
|
||||
def setGateStatus(self, channel, enable, highlow):
|
||||
self.gate_config[channel - 1] = (enable, highlow)
|
||||
|
||||
def setGate(self, channel, highlow):
|
||||
self.gate[channel - 1] = highlow
|
||||
|
||||
|
||||
with socket.socket(socket.AF_INET, socket.SOCK_STREAM) as s:
|
||||
|
||||
s.bind((HOST, PORT))
|
||||
s.listen()
|
||||
conn, addr = s.accept()
|
||||
with conn:
|
||||
|
||||
def send(data: str):
|
||||
if data:
|
||||
logger.info(f'SENDING: "{data}"')
|
||||
return conn.sendall(f'{data}\r'.encode())
|
||||
else:
|
||||
logger.info(f'SENDING: ""')
|
||||
return conn.sendall(b'\r')
|
||||
|
||||
def receive():
|
||||
data = conn.recv(1024)
|
||||
if data:
|
||||
# also removes terminator
|
||||
received = data.decode('ascii').rstrip()
|
||||
else:
|
||||
received = ''
|
||||
logger.info(f'RECEIVED: "{received}"')
|
||||
return received
|
||||
|
||||
daq = DAQ(TOTAL_CH)
|
||||
|
||||
while True:
|
||||
|
||||
data = receive()
|
||||
|
||||
if not data: # Empty implies client disconnected
|
||||
break # Close Server
|
||||
|
||||
try:
|
||||
|
||||
if data == 'RMT 1':
|
||||
send('')
|
||||
|
||||
elif data == 'ECHO 2':
|
||||
send('DAQ System Version Simulation') # Sends some sort of info command
|
||||
|
||||
elif data == 'RA':
|
||||
send(
|
||||
' '.join(map(str,
|
||||
[daq.getRunTime()] + \
|
||||
daq.getCounts()
|
||||
))
|
||||
)
|
||||
|
||||
elif re.fullmatch(r'RC (\d+)', data):
|
||||
channel = int(re.fullmatch(r'RC (\d+)', data).group(1))
|
||||
count = daq.getCount(channel)
|
||||
send(f'{count}')
|
||||
|
||||
elif data == 'RS':
|
||||
send(str(daq.getStatus()))
|
||||
|
||||
elif data == 'S':
|
||||
daq.stop()
|
||||
send('')
|
||||
|
||||
elif data == 'CT':
|
||||
daq.clearTime()
|
||||
send('')
|
||||
|
||||
elif re.fullmatch(r'CC (\d+)', data):
|
||||
counter = int(re.fullmatch(r'CC (\d+)', data).group(1))
|
||||
daq.clearCount(counter)
|
||||
send('')
|
||||
|
||||
elif re.fullmatch(r'TP (\d+(\.\d+)?)', data):
|
||||
presettime = float(re.fullmatch(r'TP (\d+(\.\d+)?)', data).group(1))
|
||||
daq.startTimePreset(presettime)
|
||||
send('')
|
||||
|
||||
elif re.fullmatch(r'MP (\d+)', data):
|
||||
counts = int(re.fullmatch(r'MP (\d+)', data).group(1))
|
||||
daq.startCountPreset(counts)
|
||||
send('')
|
||||
|
||||
elif data == 'PC':
|
||||
send(str(daq.getMonitorChannel()))
|
||||
|
||||
elif re.fullmatch(r'PC (\d+)', data):
|
||||
channel = int(re.fullmatch(r'PC (\d+)', data).group(1))
|
||||
daq.setMonitorChannel(channel)
|
||||
send('')
|
||||
|
||||
elif data == 'DR':
|
||||
send(str(daq.getMinRateChannel()))
|
||||
|
||||
elif re.fullmatch(r'DR (\d+)', data):
|
||||
channel = int(re.fullmatch(r'DR (\d+)', data).group(1))
|
||||
daq.setMinRateChannel(channel)
|
||||
send('')
|
||||
|
||||
elif re.fullmatch(r'DL (\d+)', data):
|
||||
channel = int(re.fullmatch(r'DL (\d+)', data).group(1))
|
||||
send('{:.3f}'.format(daq.getMinRate(channel)))
|
||||
|
||||
elif re.fullmatch(r'DL (\d+) (\d+(?:.\d+)?)', data):
|
||||
channel, rate = re.fullmatch(r'DL (\d+) (\d+(?:.\d+)?)', data).groups()
|
||||
daq.setMinRate(int(channel), float(rate))
|
||||
send('')
|
||||
|
||||
elif re.fullmatch(r'RR (\d+)', data):
|
||||
channel = int(re.fullmatch(r'RR (\d+)', data).group(1))
|
||||
send(daq.getRate(channel))
|
||||
|
||||
elif re.fullmatch(r'GT (\d+)', data):
|
||||
channel = int(re.fullmatch(r'GT (\d+)', data).group(1))
|
||||
enabled, highlow = daq.getGateStatus(channel)
|
||||
send(f'{int(enabled)} {int(highlow)}')
|
||||
|
||||
elif re.fullmatch(r'GT (\d+) (\d+) (\d+)', data):
|
||||
channel, enable, highlow = re.fullmatch(r'GT (\d+) (\d+) (\d+)', data).groups()
|
||||
channel, enable, highlow = int(channel), bool(int(enable)), bool(int(highlow))
|
||||
daq.setGateStatus(channel, enable, highlow)
|
||||
if enable:
|
||||
send(f'Gate {channel} enabled, counting when input = {"high" if highlow else "low"}')
|
||||
else:
|
||||
send(f'Gate {channel} disabled')
|
||||
|
||||
# Only for the simulation
|
||||
elif re.fullmatch(r'GATE (\d+) (\d+)', data):
|
||||
channel, highlow = re.fullmatch(r'GATE (\d+) (\d+)', data).groups()
|
||||
channel, highlow = int(channel), bool(int(highlow))
|
||||
daq.setGate(channel, highlow)
|
||||
send('')
|
||||
|
||||
else:
|
||||
send('?2') # Bad command
|
||||
|
||||
except Exception as e:
|
||||
logger.exception('Simulation Broke')
|
||||
send('?OV')
|
@ -1,5 +0,0 @@
|
||||
#---------------------------------------------
|
||||
# Counterbox specific DB definitions
|
||||
#---------------------------------------------
|
||||
|
||||
device(stringin,INST_IO,devCounterBoxStringError,"devCounterBoxStringError")
|
@ -54,7 +54,7 @@ struct {
|
||||
DEVSUPFUN get_ioint_info;
|
||||
DEVSUPFUN read_ai;
|
||||
DEVSUPFUN special_linconv;
|
||||
} devCounterBoxStringError = {
|
||||
} devDAQStringError = {
|
||||
6, NULL, NULL, NULL, NULL, (DEVSUPFUN)map_raw_failure_message, NULL};
|
||||
|
||||
epicsExportAddress(dset, devCounterBoxStringError);
|
||||
epicsExportAddress(dset, devDAQStringError);
|
5
src/daq.dbd
Normal file
5
src/daq.dbd
Normal file
@ -0,0 +1,5 @@
|
||||
#---------------------------------------------
|
||||
# DAQ specific DB definitions
|
||||
#---------------------------------------------
|
||||
|
||||
device(stringin, INST_IO, devDAQStringError, "devDAQStringError")
|
@ -2,13 +2,13 @@
|
||||
|
||||
on error break
|
||||
|
||||
require counterbox
|
||||
require sinqDAQ
|
||||
|
||||
epicsEnvSet("STREAM_PROTOCOL_PATH","./db")
|
||||
epicsEnvSet("PREFIX","SQ:TEST")
|
||||
epicsEnvSet("INSTR","SQ:TEST:")
|
||||
epicsEnvSet("NAME","CB_TEST")
|
||||
|
||||
epicsEnvSet("SET_SIM_MODE","") # Run Counterbox Simulation Instead of Actual Box
|
||||
runScript "$(counterbox_DIR)counterbox_v2.cmd" "CNTBOX_IP=127.0.0.1, CNTBOX_PORT=2000"
|
||||
epicsEnvSet("SET_SIM_MODE","") # Run Simulation Instead of Actual Interface
|
||||
runScript "$(sinqDAQ_DIR)daq_2nd_gen.cmd" "DAQ_IP=127.0.0.1, DAQ_PORT=2000"
|
||||
|
||||
iocInit()
|
||||
|
50
test/test.py
50
test/test.py
@ -40,53 +40,53 @@ def get_piped_output(proc):
|
||||
|
||||
return stdqueue, errqueue
|
||||
|
||||
def getState(prefix, name):
|
||||
result = run(['caget', f'{prefix}:{name}:STATUS'], stdout=PIPE)
|
||||
def getState(instr, name):
|
||||
result = run(['caget', f'{instr}{name}:STATUS'], stdout=PIPE)
|
||||
state = result.stdout.decode('ascii').rstrip().split()[1]
|
||||
print(f'Currently in state {state}')
|
||||
return state
|
||||
|
||||
def getCount(prefix, name, ch):
|
||||
result = run(['caget', f'{prefix}:{name}:M{ch}'], stdout=PIPE)
|
||||
def getCount(instr, name, ch):
|
||||
result = run(['caget', f'{instr}{name}:M{ch}'], stdout=PIPE)
|
||||
count = int(result.stdout.decode('ascii').rstrip().split()[1])
|
||||
print(f'M{ch} == {count}')
|
||||
return count
|
||||
|
||||
def presetTime(prefix, name, time):
|
||||
def presetTime(instr, name, time):
|
||||
print(f'Starting count for {time} seconds')
|
||||
run(['caput', f'{prefix}:{name}:PRESET-TIME', f'{time}'])
|
||||
run(['caput', f'{instr}{name}:PRESET-TIME', f'{time}'])
|
||||
|
||||
def presetCount(prefix, name, count):
|
||||
def presetCount(instr, name, count):
|
||||
print(f'Starting count until channel 1 reaches {count}')
|
||||
run(['caput', f'{prefix}:{name}:PRESET-COUNT', f'{count}'])
|
||||
run(['caput', f'{instr}{name}:PRESET-COUNT', f'{count}'])
|
||||
|
||||
def testCanCount(prefix, name):
|
||||
def testCanCount(instr, name):
|
||||
# Check in Idle State
|
||||
assert getState(prefix, name) == 'Idle', 'Not in valid state'
|
||||
assert getState(instr, name) == 'Idle', 'Not in valid state'
|
||||
|
||||
# Start Time Based Count and Check that Status Changes
|
||||
assert getCount(prefix, name, 1) == 0, "Erroneous nonzero starting count value"
|
||||
presetTime(prefix, name, 5)
|
||||
assert getCount(instr, name, 1) == 0, "Erroneous nonzero starting count value"
|
||||
presetTime(instr, name, 5)
|
||||
time.sleep(1)
|
||||
assert getState(prefix, name) == 'Counting', 'Didn\'t start counting'
|
||||
assert getState(instr, name) == 'Counting', 'Didn\'t start counting'
|
||||
time.sleep(5)
|
||||
assert getState(prefix, name) == 'Idle', 'Didn\'t finish counting'
|
||||
assert getCount(prefix, name, 1) > 0, 'No events were counted'
|
||||
assert getState(instr, name) == 'Idle', 'Didn\'t finish counting'
|
||||
assert getCount(instr, name, 1) > 0, 'No events were counted'
|
||||
|
||||
# Start Monitor Based Count and Check that Status Changes
|
||||
presetAmount = 100
|
||||
presetCount(prefix, name, presetAmount)
|
||||
presetCount(instr, name, presetAmount)
|
||||
time.sleep(1)
|
||||
assert getState(prefix, name) == 'Counting', 'Didn\'t start counting'
|
||||
assert getCount(prefix, name, 1) < presetAmount
|
||||
while getState(prefix, name) != 'Idle':
|
||||
assert getState(instr, name) == 'Counting', 'Didn\'t start counting'
|
||||
assert getCount(instr, name, 1) < presetAmount
|
||||
while getState(instr, name) != 'Idle':
|
||||
time.sleep(1)
|
||||
assert getCount(prefix, name, 1) == presetAmount, 'Counted events not equal to preset'
|
||||
assert getCount(prefix, name, 2) > 0
|
||||
assert getCount(instr, name, 1) == presetAmount, 'Counted events not equal to preset'
|
||||
assert getCount(instr, name, 2) > 0
|
||||
|
||||
def test(prefix, name):
|
||||
def test(instr, name):
|
||||
|
||||
# TODO pass prefix and name to script
|
||||
# TODO pass instr and name to script
|
||||
proc = Popen([f'{os.environ["PARENT_PATH"]}/ioc.sh'], stdout=PIPE, stderr=PIPE, shell=False)
|
||||
|
||||
try:
|
||||
@ -104,7 +104,7 @@ def test(prefix, name):
|
||||
print("IOC Initialisation Complete")
|
||||
print("Starting Tests")
|
||||
|
||||
testCanCount(prefix, name)
|
||||
testCanCount(instr, name)
|
||||
|
||||
print("Success")
|
||||
proc.kill()
|
||||
@ -123,7 +123,7 @@ if __name__ == '__main__':
|
||||
print("Starting Test")
|
||||
|
||||
# Test V2
|
||||
if test('SQ:TEST', 'CB_TEST'):
|
||||
if test('SQ:TEST:', 'CB_TEST'):
|
||||
exit(0)
|
||||
else:
|
||||
exit(1)
|
||||
|
Reference in New Issue