@ -47,7 +47,6 @@ record(ai, "$(P):$(NAME):READALL")
{
field(DESC, "Reads monitors and elapsed time")
field(INP, "@$(PROTO) readAll4($(P):$(NAME):) $(ASYN_PORT)")
field(SCAN, ".2 second")
field(DTYP, "stream")
field(FLNK, "$(P):$(NAME):UNSET-COUNTING")
field(FLNK, "$(P):$(NAME):MAP-STATUS")
}

View File

@ -47,9 +47,8 @@ record(ai, "$(P):$(NAME):READALL")
{
field(DESC, "Reads monitors and elapsed time")
field(INP, "@$(PROTO) readAll8($(P):$(NAME):) $(ASYN_PORT)")
field(SCAN, ".2 second")
field(DTYP, "stream")
field(FLNK, "$(P):$(NAME):UNSET-COUNTING")
field(FLNK, "$(P):$(NAME):MAP-STATUS")
}
record(longin, "$(P):$(NAME):M5")

View File

@ -23,7 +23,7 @@ record(fanout, "$(P):$(NAME):INIT-BOX")
field(DESC, "Rewrite PVs to Box")
field(SELM, "All")
field(LNK0, "$(P):$(NAME):MONITOR-CHANNEL_RBV PP")
field(LNK1, "$(P):$(NAME):READALL PP")
field(LNK1, "$(P):$(NAME):RAW-STATUS PP")
field(LNK2, "$(P):$(NAME):THRESHOLD_RBV PP")
}
@ -63,45 +63,17 @@ record(seq, "$(P):$(NAME):REINIT-CONF")
field(SELL, "$(P):$(NAME):INVALID-CONFIG.VAL")
}
# The COUNTING PV stays True until Counterbox has switched back to idle mode
# and the monitor counts have been read. Therefore, we know that the monitor
# values have been updated to represent their final values, when this switches
# back to False.
#
# This is accomplished via the explicit SET-COUNTING and UNSET-COUNTING seq
# records, that are triggered by a switch to the counting status
# (RAW-STATUS == 1 || 2) and a read of the monitors respectively.
record(bi, "$(P):$(NAME):COUNTING")
{
field(DESC, "Counterbox is Counting")
field(VAL, 0)
}
record(seq, "$(P):$(NAME):SET-COUNTING")
{
field(LNK1, "$(P):$(NAME):COUNTING PP")
field(DO1, 1)
field(SELM, "Specified")
field(SELL, "$(P):$(NAME):MAP-STATUS.VAL")
field(FLNK, "$(P):$(NAME):STATUS")
}
record(seq, "$(P):$(NAME):UNSET-COUNTING")
{
field(LNK0, "$(P):$(NAME):COUNTING PP")
field(DO0, 0)
field(SELM, "Specified")
field(SELL, "$(P):$(NAME):RAW-STATUS.VAL")
field(FLNK, "$(P):$(NAME):MAP-STATUS")
}
# Important! The "$(P):$(NAME):READALL" isn't configure with a SCAN. Instead,
# it must always be triggered after the value of $(P):$(NAME):RAW-STATUS is
# updated, so that it can't be the case that the status changes back from
# counting to idle, without having updated the time and count values.
record(longin, "$(P):$(NAME):RAW-STATUS")
{
field(DESC, "Raw returned status value")
field(DTYP, "stream")
field(SCAN, ".2 second")
field(SCAN, ".1 second")
field(INP, "@$(PROTO) readStatus($(P):$(NAME):) $(ASYN_PORT)")
field(FLNK, "$(P):$(NAME):MAP-STATUS")
field(FLNK, "$(P):$(NAME):READALL")
}
record(calc, "$(P):$(NAME):MAP-STATUS")
@ -109,9 +81,8 @@ record(calc, "$(P):$(NAME):MAP-STATUS")
field(DESC, "Maps Raw Status to State")
field(INPA, "$(P):$(NAME):RAW-STATUS NPP")
field(INPB, "$(P):$(NAME):INVALID-CONFIG NPP")
field(INPC, "$(P):$(NAME):COUNTING NPP")
field(CALC, "B=1?4:(C=1&&A=0)||A=1||A=2?1:A=0?0:A=5||A=6?2:A=9||A=13||A=10||A=14?3:4")
field(FLNK, "$(P):$(NAME):SET-COUNTING")
field(CALC, "B=1?4:A=0?0:(A=1||A=2)?1:(A=5||A=6)?2:(A=9||A=13||A=10||A=14)?3:4")
field(FLNK, "$(P):$(NAME):STATUS")
}
record(mbbi, "$(P):$(NAME):STATUS")

View File

@ -49,9 +49,8 @@ record(ai, "$(P):$(NAME):READALL")
{
field(DESC, "Reads monitors and elapsed time")
field(INP, "@$(PROTO) readAll10($(P):$(NAME):) $(ASYN_PORT)")
field(SCAN, ".2 second")
field(DTYP, "stream")
field(FLNK, "$(P):$(NAME):UNSET-COUNTING")
field(FLNK, "$(P):$(NAME):MAP-STATUS")
}
record(longin, "$(P):$(NAME):M5")
@ -83,33 +82,3 @@ record(longin, "$(P):$(NAME):M10")
{
field(DESC, "Counterbox CH10")
}
################################################################################
# Testing Commands
# These won't match the values on the machine after a full restart But I chose
# not to force their intialisation as they are only important for testing
record(bo, "$(P):$(NAME):TESTGEN")
{
field(DESC, "Turn on/off Testgen Signal")
field(DTYP, "stream")
field(OUT, "@$(PROTO) switchTestgenOnOff($(P):$(NAME):) $(ASYN_PORT)")
field(VAL, 0)
}
record(longout, "$(P):$(NAME):TESTGEN-LOWRATE")
{
field(DESC, "Set Minimum Testgen Rate")
field(DTYP, "stream")
field(OUT, "@$(PROTO) setTestSignal($(P):$(NAME):) $(ASYN_PORT)")
field(VAL, 1000)
}
record(longout, "$(P):$(NAME):TESTGEN-HIGHRATE")
{
field(DESC, "Set Maximum Testgen Rate")
field(DTYP, "stream")
field(OUT, "@$(PROTO) setTestSignal($(P):$(NAME):) $(ASYN_PORT)")
field(VAL, 1000)
}

31
db/counterbox_v2_test.db Normal file
View File

@ -0,0 +1,31 @@
################################################################################
# Testing Commands
# These won't match the values on the machine after a full restart But I chose
# not to force their intialisation as they are only important for testing
record(bo, "$(P):$(NAME):TESTGEN")
{
field(DESC, "Turn on/off Testgen Signal")
field(DTYP, "stream")
field(OUT, "@$(PROTO) switchTestgenOnOff($(P):$(NAME):) $(ASYN_PORT)")
field(VAL, 0)
field(ZNAM, "OFF")
field(ONAM, "ON")
}
record(longout, "$(P):$(NAME):TESTGEN-LOWRATE")
{
field(DESC, "Set Minimum Testgen Rate")
field(DTYP, "stream")
field(OUT, "@$(PROTO) setTestSignal($(P):$(NAME):) $(ASYN_PORT)")
field(VAL, 1000)
}
record(longout, "$(P):$(NAME):TESTGEN-HIGHRATE")
{
field(DESC, "Set Maximum Testgen Rate")
field(DTYP, "stream")
field(OUT, "@$(PROTO) setTestSignal($(P):$(NAME):) $(ASYN_PORT)")
field(VAL, 1000)
}