Added disclaimer for default behaviour of SHFT and OFFS fields (#989)
This commit is contained in:
1 parent
d606ed927b
commit
c74d4363d9
1 file changed
+14
-2
@@ -80,16 +80,28 @@ If bit 0 (LSB) is set, LNK0 is processed.
|
||||
|
||||
=item *
|
||||
|
||||
If bit 1 is set, LNK2 is processed.
|
||||
If bit 1 is set, LNK1 is processed.
|
||||
|
||||
=item *
|
||||
|
||||
If bit 2 is set, LNK3 is processed, etc.
|
||||
If bit 2 is set, LNK2 is processed, etc.
|
||||
|
||||
=back
|
||||
|
||||
=back
|
||||
|
||||
If not set, the SHFT field is set to -1, so bits from SELN are shifted left by 1.
|
||||
|
||||
=head4 Note about SHFT and OFFS fields
|
||||
|
||||
The first versions of the fanout record had LNK fields starting with index ONE
|
||||
(LNK1). The fanout record now supports 16 links, starting from index ZERO (LNK0).
|
||||
The default behaviour of the SHFT and OFFS fields was introduced for compatibility
|
||||
with old databases that used fanout records with links indexed from one.
|
||||
|
||||
B<To use the LNK0 field when SELM = Mask, the SHFT field must be explicitly set
|
||||
to ZERO.>
|
||||
|
||||
SELN reads its value from SELL. SELL can be a constant, a database link, or a
|
||||
channel access link. If a constant, SELN is initialized with the constant value
|
||||
and can be changed via dbPuts. For database/channel access links, SELN is
|
||||
|
||||
Reference in new issue
Block a user