Merge Saeed's stringin POD conversion branch
This commit is contained in:
@@ -1,71 +0,0 @@
|
||||
#*************************************************************************
|
||||
# Copyright (c) 2002 The University of Chicago, as Operator of Argonne
|
||||
# National Laboratory.
|
||||
# Copyright (c) 2002 The Regents of the University of California, as
|
||||
# Operator of Los Alamos National Laboratory.
|
||||
# EPICS BASE is distributed subject to a Software License Agreement found
|
||||
# in file LICENSE that is included with this distribution.
|
||||
#*************************************************************************
|
||||
menu(stringinPOST) {
|
||||
choice(stringinPOST_OnChange,"On Change")
|
||||
choice(stringinPOST_Always,"Always")
|
||||
}
|
||||
recordtype(stringin) {
|
||||
include "dbCommon.dbd"
|
||||
field(VAL,DBF_STRING) {
|
||||
prompt("Current Value")
|
||||
promptgroup("40 - Input")
|
||||
asl(ASL0)
|
||||
pp(TRUE)
|
||||
size(40)
|
||||
}
|
||||
field(OVAL,DBF_STRING) {
|
||||
prompt("Previous Value")
|
||||
special(SPC_NOMOD)
|
||||
interest(3)
|
||||
size(40)
|
||||
}
|
||||
field(INP,DBF_INLINK) {
|
||||
prompt("Input Specification")
|
||||
promptgroup("40 - Input")
|
||||
interest(1)
|
||||
}
|
||||
field(MPST,DBF_MENU) {
|
||||
prompt("Post Value Monitors")
|
||||
promptgroup("80 - Display")
|
||||
interest(1)
|
||||
menu(stringinPOST)
|
||||
}
|
||||
field(APST,DBF_MENU) {
|
||||
prompt("Post Archive Monitors")
|
||||
promptgroup("80 - Display")
|
||||
interest(1)
|
||||
menu(stringinPOST)
|
||||
}
|
||||
field(SIOL,DBF_INLINK) {
|
||||
prompt("Sim Input Specifctn")
|
||||
promptgroup("90 - Simulate")
|
||||
interest(1)
|
||||
}
|
||||
field(SVAL,DBF_STRING) {
|
||||
prompt("Simulation Value")
|
||||
pp(TRUE)
|
||||
size(40)
|
||||
}
|
||||
field(SIML,DBF_INLINK) {
|
||||
prompt("Sim Mode Location")
|
||||
promptgroup("90 - Simulate")
|
||||
interest(1)
|
||||
}
|
||||
field(SIMM,DBF_MENU) {
|
||||
prompt("Simulation Mode")
|
||||
interest(1)
|
||||
menu(menuYesNo)
|
||||
}
|
||||
field(SIMS,DBF_MENU) {
|
||||
prompt("Sim mode Alarm Svrty")
|
||||
promptgroup("90 - Simulate")
|
||||
interest(2)
|
||||
menu(menuAlarmSevr)
|
||||
}
|
||||
}
|
||||
360
src/std/rec/stringinRecord.dbd.pod
Normal file
360
src/std/rec/stringinRecord.dbd.pod
Normal file
@@ -0,0 +1,360 @@
|
||||
#*************************************************************************
|
||||
# Copyright (c) 2002 The University of Chicago, as Operator of Argonne
|
||||
# National Laboratory.
|
||||
# Copyright (c) 2002 The Regents of the University of California, as
|
||||
# Operator of Los Alamos National Laboratory.
|
||||
# EPICS BASE is distributed subject to a Software License Agreement found
|
||||
# in file LICENSE that is included with this distribution.
|
||||
#*************************************************************************
|
||||
|
||||
=head1 String Input Record (stringin)
|
||||
|
||||
The string input record retrieves an arbitrary ASCII string of up to 40
|
||||
characters. Several device support routines are available, all of which are soft
|
||||
device support for retrieving values from other records or other software
|
||||
components.
|
||||
|
||||
=head2 Contents
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Parameter Fields>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Scan Parameters>
|
||||
|
||||
=item * L<Read Parameters>
|
||||
|
||||
=item * L<Monitor Parameters>
|
||||
|
||||
=item * L<Operator Display Parameters>
|
||||
|
||||
=item * L<Alarm Parameters>
|
||||
|
||||
=item * L<Run-time and Simulation Mode Parameters>
|
||||
|
||||
=back
|
||||
|
||||
=item * L<Record Support>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Record Support Routines (stringinRecord.c)>
|
||||
|
||||
=item * L<Record Processing>
|
||||
|
||||
=back
|
||||
|
||||
=item * L<Device Support>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Fields Of Interest To Device Support>
|
||||
|
||||
=item * L<Device Support Routines (devSiSoft.c)>
|
||||
|
||||
=item * L<Device Support for Soft Records>
|
||||
|
||||
=back
|
||||
|
||||
=back
|
||||
|
||||
=begin html
|
||||
|
||||
<br>
|
||||
<hr>
|
||||
<br>
|
||||
|
||||
=end html
|
||||
|
||||
=recordtype stringin
|
||||
|
||||
=cut
|
||||
|
||||
menu(stringinPOST) {
|
||||
choice(stringinPOST_OnChange,"On Change")
|
||||
choice(stringinPOST_Always,"Always")
|
||||
}
|
||||
recordtype(stringin) {
|
||||
include "dbCommon.dbd"
|
||||
field(VAL,DBF_STRING) {
|
||||
prompt("Current Value")
|
||||
promptgroup("40 - Input")
|
||||
asl(ASL0)
|
||||
pp(TRUE)
|
||||
size(40)
|
||||
}
|
||||
|
||||
=head2 Parameter Fields
|
||||
|
||||
=head3 Scan Parameters
|
||||
|
||||
The string input record has the standard fields for specifying under what
|
||||
circumstances it will be processed. These fields are listed in
|
||||
L<Scan Fields|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_dbCommon#Scan_Fields>.
|
||||
In addition,
|
||||
L<Scanning Specification|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Concepts#Scanning_Specification>
|
||||
explains how these fields are used.
|
||||
|
||||
=head3 Read Parameters
|
||||
|
||||
The INP field determines where the string input record gets its string. It can
|
||||
be a database or channel access link, or a constant. If constant, the VAL field
|
||||
is initialized with the constant and can be changed via dbPuts. Otherwise, the
|
||||
string is read from the specified location each time the record is processed and
|
||||
placed in the VAL field. The maximum number of characters that the string in VAL
|
||||
can be is 40. In addition, the appropriate device support module must be entered
|
||||
into the DTYP field.
|
||||
|
||||
See L<Address Specification|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Concepts#Address_Specification>
|
||||
for information on specifying links.
|
||||
|
||||
=fields VAL, INP, DTYP
|
||||
|
||||
=cut
|
||||
|
||||
field(INP,DBF_INLINK) {
|
||||
prompt("Input Specification")
|
||||
promptgroup("40 - Input")
|
||||
interest(1)
|
||||
}
|
||||
|
||||
=head3 Monitor Parameters
|
||||
|
||||
These parameters are used to specify when the monitor post should be sent by
|
||||
C<monitor()> routine. There are two possible choices:
|
||||
|
||||
=head4 Menu stringinPOST
|
||||
|
||||
=menu stringinPOST
|
||||
|
||||
APST is used for archiver monitors and MPST is for all other type of monitors.
|
||||
|
||||
=fields MPST, APST
|
||||
|
||||
=cut
|
||||
|
||||
field(MPST,DBF_MENU) {
|
||||
prompt("Post Value Monitors")
|
||||
promptgroup("80 - Display")
|
||||
interest(1)
|
||||
menu(stringinPOST)
|
||||
}
|
||||
field(APST,DBF_MENU) {
|
||||
prompt("Post Archive Monitors")
|
||||
promptgroup("80 - Display")
|
||||
interest(1)
|
||||
menu(stringinPOST)
|
||||
}
|
||||
|
||||
=head3 Operator Display Parameters
|
||||
|
||||
See L<Fields Common to All Record Types|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_dbCommon#Fields_Common_to_All_Record_Types>
|
||||
for more on the record name (NAME) and description (DESC) fields.
|
||||
|
||||
=fields NAME, DESC
|
||||
|
||||
=head3 Alarm Parameters
|
||||
|
||||
The string input record has the alarm parameters common to all record types.
|
||||
L<Alarm Fields|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_dbCommon#Alarm_Fields>
|
||||
lists other fields related to a alarms that are common to all record types.
|
||||
|
||||
=head3 Run-time and Simulation Mode Parameters
|
||||
|
||||
The old value field (OVAL) of the string input is used to implement value change
|
||||
monitors for VAL. If VAL is not equal to OVAL, then monitors are triggered.
|
||||
|
||||
=fields OVAL
|
||||
|
||||
|
||||
|
||||
The following fields are used to operate the string input in the simulation
|
||||
mode. See
|
||||
L<Simulation Mode|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Common#Simulation_Mode>
|
||||
for more information on simulation mode fields.
|
||||
|
||||
=fields SIOL, SVAL, SIML, SIMM, SIMS
|
||||
|
||||
=cut
|
||||
|
||||
field(OVAL,DBF_STRING) {
|
||||
prompt("Previous Value")
|
||||
special(SPC_NOMOD)
|
||||
interest(3)
|
||||
size(40)
|
||||
}
|
||||
field(SIOL,DBF_INLINK) {
|
||||
prompt("Sim Input Specifctn")
|
||||
promptgroup("90 - Simulate")
|
||||
interest(1)
|
||||
}
|
||||
field(SVAL,DBF_STRING) {
|
||||
prompt("Simulation Value")
|
||||
pp(TRUE)
|
||||
size(40)
|
||||
}
|
||||
field(SIML,DBF_INLINK) {
|
||||
prompt("Sim Mode Location")
|
||||
promptgroup("90 - Simulate")
|
||||
interest(1)
|
||||
}
|
||||
field(SIMM,DBF_MENU) {
|
||||
prompt("Simulation Mode")
|
||||
interest(1)
|
||||
menu(menuYesNo)
|
||||
}
|
||||
field(SIMS,DBF_MENU) {
|
||||
prompt("Sim mode Alarm Svrty")
|
||||
promptgroup("90 - Simulate")
|
||||
interest(2)
|
||||
menu(menuAlarmSevr)
|
||||
}
|
||||
|
||||
=begin html
|
||||
|
||||
<br>
|
||||
<hr>
|
||||
<br>
|
||||
|
||||
=end html
|
||||
|
||||
=head2 Record Support
|
||||
|
||||
=head3 Record Support Routines (stringinRecord.c)
|
||||
|
||||
=head4 init_record
|
||||
|
||||
long (*init_record)(struct dbCommon *precord, int pass)
|
||||
|
||||
This routine initializes SIMM with the value of SIML if SIML type is CONSTANT
|
||||
link or creates a channel access link if SIML type is PV_LINK. SVAL is likewise
|
||||
initialized if SIOL is CONSTANT or PV_LINK.
|
||||
|
||||
This routine next checks to see that device support is available and a record
|
||||
support read routine is defined. If either does not exist, an error message is
|
||||
issued and processing is terminated.
|
||||
|
||||
If device support includes an C<init_record()> routine it is called.
|
||||
|
||||
=head4 process
|
||||
|
||||
long (*process)(struct dbCommon *precord)
|
||||
|
||||
See L<Record Processing>.
|
||||
|
||||
=head3 Record Processing
|
||||
|
||||
Routine process implements the following algorithm:
|
||||
|
||||
=over
|
||||
|
||||
=item 1.
|
||||
|
||||
Check to see that the appropriate device support module exists. If it doesn't,
|
||||
an error message is issued and processing is terminated with the PACT field
|
||||
still set to TRUE. This ensures that processes will no longer be called for this
|
||||
record. Thus error storms will not occur.
|
||||
|
||||
=item 2.
|
||||
|
||||
readValue is called. See
|
||||
L<Simulation Mode|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Common#Simulation_Mode>
|
||||
for more information on simulation mode fields and how they affect input.
|
||||
|
||||
=item 3.
|
||||
|
||||
If PACT has been changed to TRUE, the device support read routine has started
|
||||
but has not completed reading a new input value. In this case, the processing
|
||||
routine merely returns, leaving PACT TRUE.
|
||||
|
||||
=item 4.
|
||||
|
||||
C<recGblGetTimeStamp()> is called.
|
||||
|
||||
=item 5.
|
||||
|
||||
Check to see if monitors should be invoked.
|
||||
|
||||
=over
|
||||
|
||||
=item *
|
||||
|
||||
Alarm monitors are invoked if the alarm status or severity has changed.
|
||||
|
||||
=item *
|
||||
|
||||
Archive and value change monitors are invoked if OVAL is not equal to VAL.
|
||||
|
||||
=item *
|
||||
|
||||
NSEV and NSTA are reset to 0.
|
||||
|
||||
=back
|
||||
|
||||
=item 6.
|
||||
|
||||
Scan forward link if necessary, set PACT FALSE, and return.
|
||||
|
||||
=back
|
||||
|
||||
=begin html
|
||||
|
||||
<br>
|
||||
<hr>
|
||||
<br>
|
||||
|
||||
=end html
|
||||
|
||||
=head2 Device Support
|
||||
|
||||
=head3 Fields Of Interest To Device Support
|
||||
|
||||
Each stringin input record must have an associated set of device support
|
||||
routines. The primary responsibility of the device support routines is to obtain
|
||||
a new ASCII string value whenever read_stringin is called. The device support
|
||||
routines are primarily interested in the following fields:
|
||||
|
||||
=fields PACT, DPVT, UDF, VAL, INP
|
||||
|
||||
=head3 Device Support Routines (devSiSoft.c)
|
||||
|
||||
=head4 init_record
|
||||
|
||||
long init_record(stringinRecord *prec)
|
||||
|
||||
This routine is optional. If provided, it is called by the record support
|
||||
C<init_record()> routine.
|
||||
|
||||
=head4 read_stringin
|
||||
|
||||
long read_stringin(stringinRecord *prec)
|
||||
|
||||
This routine must provide a new input value. It returns the following values:
|
||||
|
||||
=over
|
||||
|
||||
=item * 0: Success. A new ASCII string is stored into VAL.
|
||||
|
||||
=item * Other: Error.
|
||||
|
||||
=back
|
||||
|
||||
=head3 Device Support for Soft Records
|
||||
|
||||
The C<<< Soft Channel >>> module places a value directly in VAL.
|
||||
|
||||
If the INP link type is constant, the double constant, if non-zero, is converted
|
||||
to a string and stored into VAL by C<init_record()>, and UDF is set to FALSE. If
|
||||
the INP link type is PV_LINK, then dbCaAddInlink is called by C<init_record()>.
|
||||
|
||||
read_stringin calls recGblGetLinkValue to read the current value of VAL. See
|
||||
L<Soft Input|https://wiki-ext.aps.anl.gov/epics/index.php/RRM_3-14_Common#Soft_Input>.
|
||||
|
||||
If the return status of recGblGetLinkValue is zero, then read_stringin sets UDF
|
||||
to FALSE. The status of recGblGetLinkValue is returned.
|
||||
|
||||
=cut
|
||||
|
||||
}
|
||||
Reference in New Issue