=head1 B<Multi-Bit Binary Input Direct Record (mbbiDirect)>
|
||||
|
||||
The mbbiDirect record retrieves a sixteen-bit hardware value and converts it to
|
||||
an array of sixteen unsigned characters, each representing a bit of the word.
|
||||
These fields (B0-B9, BA-BF) are set to 1 if a bit is set, and 0 if not.
|
||||
|
||||
This record's operation is similar to that of the multi-bit binary input record,
|
||||
and it has many fields in common with it. This record also has two available
|
||||
soft device support modules: C<Soft Channel> and C<Raw Soft Channel>.
|
||||
|
||||
=head1 L<Contents>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Parameter Fields>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Scan Parameters>
|
||||
|
||||
=item * L<Desired Output Parameters>
|
||||
|
||||
=item * L<Write Parameters>
|
||||
|
||||
=item * L<Operator Display Parameters>
|
||||
|
||||
=item * L<Alarm Parameters>
|
||||
|
||||
=item * L<Monitor Parameters>
|
||||
|
||||
=item * L<Simulation Mode Parameters>
|
||||
|
||||
=back
|
||||
|
||||
=item * L<Record Support>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Record Support Routines>
|
||||
|
||||
=item * L<Record Processing>
|
||||
|
||||
=back
|
||||
|
||||
=item * L<Device Support>
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Fields Of Interest To Device Support>
|
||||
|
||||
=item * L<Device Support Routines>
|
||||
|
||||
=item * L<Device Support For Soft Records>
|
||||
|
||||
=back
|
||||
|
||||
=back
|
||||
|
||||
=begin html
|
||||
|
||||
<br><hr><br>
|
||||
|
||||
=end html
|
||||
|
||||
=recordtype mbbiDirect
|
||||
|
||||
=cut
|
||||
|
||||
recordtype(mbbiDirect) {
|
||||
include "dbCommon.dbd"
|
||||
|
||||
=head2 Parameter Fields
|
||||
|
||||
The fields fall into the following categories:
|
||||
|
||||
=over
|
||||
|
||||
=item * L<Scan Parameters>
|
||||
|
||||
=item * L<Read and Convert Parameters>
|
||||
|
||||
=item * L<Operator Display Parameters>
|
||||
|
||||
=item * L<Alarm Parameters>
|
||||
|
||||
=item * L<Run-time and Simulation Mode Parameters>
|
||||
|
||||
=back
|
||||
|
||||
=cut
|
||||
|
||||
=head3 Scan Parameters
|
||||
|
||||
The mbbiDirect record has the standard fields for specifying under what
|
||||
circumstances the record will be processed. These fields are listed in L<Scan
|
||||
Fields>. In addition, L<Scanning Specification> explains how these fields are
|
||||
used. Note that I/O event scanning is only supported for those card types
|
||||
that interrupt.
|
||||
|
||||
=cut
|
||||
|
||||
=head3 Read and Convert Parameters
|
||||
|
||||
The device support routines obtain the record's input from the device or link
|
||||
specified in the INP field. For records that obtain their input from devices,
|
||||
the INP field must contain the address of the I/O card, and the DTYP field
|
||||
must specify the proper device support module. Be aware that the address format
|
||||
differs according to the I/O bus used. See L<Address Specification> for
|
||||
information on the format of hardware addresses.
|
||||
|
||||
Two soft device support modules can be specified in DTYP C<Soft Channel> and
|
||||
C<<< Raw Soft Channel >>>.
|
||||
|
||||
C<<< Raw Soft Channel >>> reads the value into RVAL,
|
||||
upon which the normal conversion process is undergone. C<<< Soft Channel >>>
|
||||
reads any unsigned integer directly into VAL. For a soft mbbiDirect record, the
|
||||
INP field can be a constant, a database, or a channel access link. If INP is a
|
||||
constant, then the VAL is initialized to the INP value but can be changed at
|
||||
run-time via dbPutField or dbPutLink. See L<Address Specification> for
|
||||
information on how to database links.
|
||||
|
||||
For records that don't use C<<< Soft Channel >>> device support, RVAL is used to
|
||||
determine VAL as follows:
|
||||
|
||||
=over
|
||||
|
||||
=item 1. RVAL is assigned to a temporary variable I<rval> = RVAL
|
||||
|
||||
=item 2. I<rval> is shifted right SHFT number of bits.
|
||||
|
||||
=item 3. VAL is set equal to I<rval>.
|
||||
|
||||
=back
|
||||
|
||||
Each of the fields, B0-BF, represents one bit of the word.
|
||||
|
||||
=fields VAL, INP, RVAL, SHFT, B0, B1, B2, B3, B4, B5, B6, B7, B8, B9, BA, BB, BC, BD, BE, BF
|
||||
|
||||
=cut
|
||||
|
||||
=head3 Operator Display Parameters
|
||||
|
||||
These parameters are used to present meaningful data to the operator.
|
||||
|
||||
See L<Fields Common to All Record Types> for more on the record name (NAME) and
|
||||
description (DESC) fields.
|
||||
|
||||
=fields NAME, DESC
|
||||
|
||||
=cut
|
||||
|
||||
include "dbCommon.dbd"
|
||||
field(VAL,DBF_USHORT) {
|
||||
prompt("Current Value")
|
||||
promptgroup("40 - Input")
|
||||
@@ -49,6 +199,27 @@ recordtype(mbbiDirect) {
|
||||
promptgroup("40 - Input")
|
||||
interest(1)
|
||||
}
|
||||
|
||||
=head3 Run-time and Simulation Mode Parameters
|
||||
|
||||
These parameters are used by the run-time code for processing the mbbi direct
|
||||
record. They are not configurable prior to run-time.
|
||||
|
||||
MASK is used by device support routine to read hardware register. Record support
|
||||
sets low order NOBT bits in MASK. Device support can shift this value.
|
||||
|
||||
MLST holds the value when the last monitor for value change was triggered.
|
||||
|
||||
=fields NOBT, ORAW, MASK, MLST
|
||||
|
||||
The following fields are used to operate the mbbiDirect record in the simulation
|
||||
mode. See L<Fields Common to Many Record Types> for more information on these
|
||||
fields.
|
||||
|
||||
=fields SIOL, SVAL, SIML, SIMM, SIMS
|
||||
|
||||
=cut
|
||||
|
||||
field(SIOL,DBF_INLINK) {
|
||||
prompt("Sim Input Specifctn")
|
||||
promptgroup("90 - Simulate")
|
||||
@@ -67,6 +238,20 @@ recordtype(mbbiDirect) {
|
||||
interest(1)
|
||||
menu(menuSimm)
|
||||
}
|
||||
|
||||
=head3 Alarm Parameters
|
||||
|
||||
The possible alarm conditions for multi-bit binary input direct records are the
|
||||
SCAN and READ alarms. These alarms are not configurable by the user since they
|
||||
are always of MAJOR severity. See L<Alarm Specification> for a complete
|
||||
explanation of Scan and Read alarms. No fields exist for the mbbi direct record
|
||||
to have state alarms.
|
||||
|
||||
L<Alarm Fields> lists other fields related to a alarms that are common to all
|
||||
record types.
|
||||
|
||||
=cut
|
||||
|
||||
field(SIMS,DBF_MENU) {
|
||||
prompt("Sim mode Alarm Svrty")
|
||||
promptgroup("90 - Simulate")
|
||||
@@ -153,4 +338,223 @@ recordtype(mbbiDirect) {
|
||||
pp(TRUE)
|
||||
interest(1)
|
||||
}
|
||||
|
||||
=begin html
|
||||
|
||||
<br><hr><br>
|
||||
|
||||
=end html
|
||||
|
||||
=head2 Record Support
|
||||
|
||||
=head3 Record Support Routines
|
||||
|
||||
=head4 init_record
|
||||
|
||||
This routine initializes SIMM with the value of SIML if SIML type is CONSTANT
|
||||
link or creates a channel access link if SIML type is PV_LINK. SVAL is likewise
|
||||
initialized if SIOL is CONSTANT or PV_LINK.
|
||||
|
||||
This routine next checks to see that device support is available and a device
|
||||
support read routine is defined. If either does not exist, an error message is
|
||||
issued and processing is terminated.
|
||||
|
||||
Clears MASK and then sets the NOBT low order bits.
|
||||
|
||||
If device support includes C<init_record()>, it is called.
|
||||
|
||||
refresh_bits is then called to refresh all the bit fields based on a hardware
|
||||
value.
|
||||
|
||||
=head4 process
|
||||
|
||||
See next section.
|
||||
|
||||
=head3 Record Processing
|
||||
|
||||
Routine process implements the following algorithm:
|
||||
|
||||
=over
|
||||
|
||||
=item 1.
|
||||
|
||||
Check to see that the appropriate device support module exists. If it doesn't,
|
||||
an error message is issued and processing is terminated with the PACT field
|
||||
still set to TRUE. This ensures that processes will no longer be called for this
|
||||
record. Thus error storms will not occur.
|
||||
|
||||
=item 2.
|
||||
|
||||
readValue is called. See L<Output Records> for information.
|
||||
|
||||
=item 3.
|
||||
|
||||
If PACT has been changed to TRUE, the device support read routine has started
|
||||
but has not completed reading a new input value. In this case, the processing
|
||||
routine merely returns, leaving PACT TRUE.
|
||||
|
||||
=item 4.
|
||||
|
||||
Convert.
|
||||
|
||||
=over
|
||||
|
||||
=item * status = read_mbbiDirect
|
||||
|
||||
=item * PACT = TRUE
|
||||
|
||||
=item * C<recGblGetTimeStamp()> is called.
|
||||
|
||||
=item * If status is 0, then determine VAL
|
||||
|
||||
=over
|
||||
|
||||
=item * Set rval = RVAL
|
||||
|
||||
=item * Shift rval right SHFT bits
|
||||
|
||||
=item * Set VAL = RVAL
|
||||
|
||||
=back
|
||||
|
||||
=item * If status is 1, return 0
|
||||
|
||||
=item * If status is 2, set status = 0
|
||||
|
||||
=back
|
||||
|
||||
=item 5.
|
||||
|
||||
Check to see if monitors should be invoked.
|
||||
|
||||
=over
|
||||
|
||||
=item * Alarm monitors are invoked if the alarm status or severity has changed.
|
||||
|
||||
=item * Archive and value change monitors are invoked if MLST is not equal to VAL.
|
||||
|
||||
=item * Monitors for RVAL are checked whenever other monitors are invoked.
|
||||
|
||||
=item * NSEV and NSTA are reset to 0.
|
||||
|
||||
=back
|
||||
|
||||
=item 6.
|
||||
|
||||
Scan forward link if necessary, set PACT FALSE, and return.
|
||||
|
||||
=back
|
||||
|
||||
=begin html
|
||||
|
||||
<br><hr><br>
|
||||
|
||||
=end html
|
||||
|
||||
=head2 Device Support
|
||||
|
||||
=head3 Fields Of Interest To Device Support
|
||||
|
||||
Each input record must have an associated set of device support routines.
|
||||
|
||||
The primary responsibility of the device support routines is to obtain a new raw
|
||||
input value whenever read_mbbiDirect is called. The device support routines are
|
||||
primarily interested in the following fields:
|
||||
|
||||
=fields PACT, DPVT, UDF, NSEV, NSTA, NOBT, VAL, INP, RVAL, MASK, SHFT
|
||||
|
||||
=head3 Device Support Routines
|
||||
|
||||
Device support consists of the following routines:
|
||||
|
||||
=head4 long report(int level)
|
||||
|
||||
This optional routine is called by the IOC command C<dbior> and is passed the
|
||||
report level that was requested by the user.
|
||||
It should print a report on the state of the device support to stdout.
|
||||
The C<level> parameter may be used to output increasingly more detailed
|
||||
information at higher levels, or to select different types of information with
|
||||
different levels.
|
||||
Level zero should print no more than a small summary.
|
||||
|
||||
=head4 long init(int after)
|
||||
|
||||
This optional routine is called twice at IOC initialization time.
|
||||
The first call happens before any of the C<init_record()> calls are made, with
|
||||
the integer parameter C<after> set to 0.
|
||||
The second call happens after all of the C<init_record()> calls have been made,
|
||||
with C<after> set to 1.
|
||||
|
||||
=head4 init_record
|
||||
|
||||
init_record(precord)
|
||||
|
||||
This routine is optional. If provided, it is called by the record support
|
||||
C<init_record()> routine. If it uses MASK, it should shift it as necessary and
|
||||
also give SHFT a value.
|
||||
|
||||
=head4 get_ioint_info
|
||||
|
||||
get_ioint_info(int cmd,struct dbCommon *precord,IOSCANPVT *ppvt)
|
||||
|
||||
This routine is called by the ioEventScan system each time the record is added
|
||||
or deleted from an IE<sol>O event scan list. cmd has the value (0,1) if the
|
||||
record is being (added to, deleted from) an IE<sol>O event list. It must be
|
||||
provided for any device type that can use the ioEvent scanner.
|
||||
|
||||
=head4 read_mbbiDirect
|
||||
|
||||
read_mbbiDirect(precord)
|
||||
|
||||
This routine must provide a new input value. It returns the following values:
|
||||
|
||||
=over
|
||||
|
||||
=item *
|
||||
|
||||
0: Success. A new raw value is placed in RVAL. The record support module
|
||||
determines VAL from RVAL and SHFT.
|
||||
|
||||
=item *
|
||||
|
||||
2: Success, but don't modify VAL.
|
||||
|
||||
=item *
|
||||
|
||||
Other: Error.
|
||||
|
||||
=back
|
||||
|
||||
=head3 Device Support For Soft Records
|
||||
|
||||
Two soft device support modules, C<<< Soft Channel >>> and C<<< Raw Soft Channel
|
||||
>>>, are provided for multi-bit binary input direct records not related to
|
||||
actual hardware devices. The INP link type must be either CONSTANT, DB_LINK, or
|
||||
CA_LINK.
|
||||
|
||||
=head4 Soft Channel
|
||||
|
||||
For this module, read_mbbiDirect always returns a value of 2, which means that
|
||||
no conversion is performed.
|
||||
|
||||
If the INP link type is constant, then the constant value is stored into VAL by
|
||||
C<init_record()>, and UDF is set to FALSE. VAL can be changed via dbPut
|
||||
requests. If the INP link type is PV_LINK, then dbCaAddInlink is called by
|
||||
C<init_record()>.
|
||||
|
||||
read_mbbiDirect calls recGblGetLinkValue to read the current value of VAL.
|
||||
|
||||
See L<Input Records> for a further explanation.
|
||||
|
||||
If the return status of recGblGetLinkValue is zero, then read_mbbi sets UDF to
|
||||
FALSE. The status of recGblGetLinkValue is returned.
|
||||
|
||||
=head4 Raw Soft Channel
|
||||
|
||||
This module is like the previous except that values are read into RVAL, VAL is
|
||||
computed from RVAL, and read_mbbiDirect returns a value of 0. Thus the record
|
||||
processing routine will determine VAL in the normal way.
|
||||
|
||||
=cut
|
||||
|
||||
}
|
||||
|
||||