docs(flomni): flag unguarded heater-vs-OSA collision gap in fosa_in()
CI for csaxs_bec / test (push) Failing after 4m58s

Audit of heater interlocks (pre-first-use) found that fosa_in()/
foptics_in() never check fheater position before driving fosaz, even
though the OSA travels inside the heater's envelope. Heater motion
itself is well protected (ensure_osa_back()/ensure_fheater_up()), but
this one direction is open. Not fixing it yet -- documenting it so it
is remembered when fheater's userParameter is added during hardware
commissioning.

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01XdHenMmwbrCz1juWMi1yZc
This commit is contained in:
x12saandClaude Sonnet 5 committed 2026-09-11 13:15:58 +02:00
1 parent f56d11d730
commit 42739fcc7a
2 files changed
+14

No files matched your search

@@ -167,6 +167,13 @@ class FlomniOpticsMixin:
dev.rtx.controller.feedback_enable_with_reset()
def fosa_in(self):
# TODO(commissioning): the OSA travels inside the heater's (fheater)
# envelope, but this function never checks fheater position before
# driving fosaz. fosaz must only move while fheater is fully "up" or
# fully "down" -- an intermediate heater position here risks a
# collision. Add a heater-state check (see ensure_osa_back()/
# ensure_fheater_up() in flomni.py for the pattern) once fheater's
# up/down limits are commissioned.
# 6.2 keV, 170 um FZP
# umv(dev.losax, -1.4450000, dev.losay, -0.1800)
# umv(dev.losaz, -1)
@@ -46,6 +46,13 @@ feyey:
in: -10.09
deviceTags:
- ptycho_flomni
# TODO(commissioning): needs userParameter (e.g. in/up, down) -- move_fheater_down()
# in flomni.py currently reads user_parameter.get("in") and gets None.
# KNOWN GAP: fosa_in()/foptics_in() (flomni_optics_mixin.py) never check fheater
# position before driving fosaz. The OSA travels inside the heater's envelope, so
# fosaz must only move while fheater is fully at its "up" or fully at its "down"
# limit -- an intermediate heater position during fosa_in() risks a collision.
# Verify/add that check once real up/down limits are known from hardware.
fheater:
description: Heater Y
deviceClass: csaxs_bec.devices.omny.galil.fgalil_ophyd.FlomniGalilMotor