deviceDesc = he meas ccu4_device special proc make_hemeas {ccname pname pshort hostport args} { makenv $ccname -driver ccu4 -port $hostport "He vessels $pname" multiHe hsetprop /$ccname cfgtablefile NONE foreach chan $args { GraphAdd $ccname.h$chan % ${pshort}_He_$chan } # 75 mA meas. current (85 seems to work better) $ccname hd0 85 # 460 Ohm/m resistivity $ccname hwr0 460 # empty at 475 mm from top (sensors exchanged in 2021: was 565 before) $ccname hem0 475 # full at 0 mm from top (sensors exchanged in 2021: was 90 mm before) $ccname hfu0 0 # measurement interval 30 min. (but measured always after plugging) $ccname hts 1800 # hsetprop /$ccname group "He vessels $pname" } make_hemeas cc2 aare aare ldmprep7-ts:3004 0 1 2 3 4 5 make_hemeas cc1 mid1 mid1 psts216:3007 0 1 2 3 4 5 make_hemeas cc6 berg berg ldmprep12-ts:3010 1 2 3 4 5 makenv luft -driver luft SINQ makenv luft_wlga -driver luft WLGA GraphAdd luft %_2 Luft_SINQ GraphAdd luft_wlga %_2 Luft_WLGA if {[sicsdescriptor helium_list] eq "notfound"} { makeobject helium_list array } if {[sicsdescriptor helium_ts] eq "notfound"} { makeobject helium_ts array } if {[sicsdescriptor pump_health] eq "notfound"} { makeobject pump_health array }