deviceDesc = ILL furnace (1400 K), OLD POWERSUPPLY, type W thermocouple (1500 / 1800 K) defineTemperature tt makenv tt -driver 340_lsc -port @lsc340a { # the temperature scale is kinked above 1000 K, by a factor 2 lsc_kink 1000 2 lsc_sensor ts C -sensor type-c-k1000 -sensorname sample -alarm 1805 lsc_sensor t2 D -sensor type-c-k1000 -sensorname t2 -alarm 1805 # lsc_sensor te B -sensor rhfe4140 -sensorname outer -alarm 323 lsc_sensor te B -sensor pt1000e -sensorname outer -alarm 323 lsc_sensor p A -sensor vacuum -sensorname vacuum lsc_loop set -loop 1 -channel C -maxheater 0.05A -resist 1000Ohm -linearpower 3000 hsetprop /tt dblmode disabled hsetprop /tt/dblctrl visible false hdelprop /tt/dblctrl group } GraphAdd tt.set.reg K T_reg auto GraphAdd tt.ts.raw V V_sample blue GraphAdd tt.t2.raw V V_t2 auto catch { tt set/prop 1 tt set/integ 5 # tt set/ramp 10 tt set/limit 1700 } makenv table -driver table /tt/ts { "tt set/prop" "500:0.5 1500:5" "tt set/integ" "500:1 1500:5" }