Compare commits
2 Commits
Author | SHA1 | Date | |
---|---|---|---|
d1d640805b | |||
92a8dfac5d |
102
cfg/kapillarheizung_cfg.py
Normal file
102
cfg/kapillarheizung_cfg.py
Normal file
@ -0,0 +1,102 @@
|
||||
Node('Gas10kA.psi.ch',
|
||||
'LOGO for 10kBar Gas pressure stick',
|
||||
interface='tcp://5001',
|
||||
)
|
||||
|
||||
Mod('io',
|
||||
'frappy_psi.logo.IO',
|
||||
'',
|
||||
ip_address = "192.168.1.1",
|
||||
tcap_client = 0x3000,
|
||||
tsap_server = 0x2000
|
||||
)
|
||||
|
||||
Mod('PT10000',
|
||||
'frappy_psi.logo.TempSensor',
|
||||
'sensor',
|
||||
io = 'io',
|
||||
vm_address ="VW0",
|
||||
)
|
||||
|
||||
Mod('T_pt10k',
|
||||
'frappy_psi.softcal.Sensor',
|
||||
'?',
|
||||
value=Param(unit='K'),
|
||||
rawsensor='PT10000',
|
||||
calib='pt10000e',
|
||||
)
|
||||
|
||||
Mod('PT1000_oben',
|
||||
'frappy_psi.logo.TempSensor',
|
||||
'sensor',
|
||||
io = 'io',
|
||||
vm_address ="VW2",
|
||||
)
|
||||
|
||||
Mod('T_top',
|
||||
'frappy_psi.softcal.Sensor',
|
||||
'?',
|
||||
value=Param(unit='K'),
|
||||
rawsensor='PT1000_oben',
|
||||
calib='pt1000e',
|
||||
)
|
||||
|
||||
Mod('PT1000_mitte',
|
||||
'frappy_psi.logo.TempSensor',
|
||||
'sensor',
|
||||
io = 'io',
|
||||
vm_address ="VW4",
|
||||
)
|
||||
|
||||
Mod('T_mid',
|
||||
'frappy_psi.softcal.Sensor',
|
||||
'?',
|
||||
value=Param(unit='K'),
|
||||
rawsensor='PT1000_mitte',
|
||||
calib='pt1000e',
|
||||
)
|
||||
|
||||
Mod('PT1000_unten',
|
||||
'frappy_psi.logo.TempSensor',
|
||||
'sensor',
|
||||
io = 'io',
|
||||
vm_address ="VW6",
|
||||
)
|
||||
|
||||
Mod('T_bot',
|
||||
'frappy_psi.softcal.Sensor',
|
||||
'?',
|
||||
value=Param(unit='K'),
|
||||
rawsensor='PT1000_unten',
|
||||
calib='pt1000e',
|
||||
)
|
||||
|
||||
Mod('Cernox',
|
||||
'frappy_psi.logo.TempSensor',
|
||||
'sensor',
|
||||
io = 'io',
|
||||
vm_address ="VW8",
|
||||
)
|
||||
|
||||
Mod('T_cx',
|
||||
'frappy_psi.softcal.Sensor',
|
||||
'?',
|
||||
value=Param(unit='K'),
|
||||
rawsensor='Cernox',
|
||||
calib='X174785',
|
||||
)
|
||||
|
||||
Mod('HeaterLevelHigh',
|
||||
'frappy_psi.logo.HeaterParam',
|
||||
'heater param',
|
||||
io = 'io',
|
||||
vm_address = "VW10",
|
||||
)
|
||||
|
||||
# currently unused:
|
||||
#Mod('HeaterLevelLow',
|
||||
# 'frappy_psi.logo.HeaterParam',
|
||||
# 'heater param',
|
||||
# io = 'io',
|
||||
# vm_address = "VW12",
|
||||
#)
|
158
frappy_psi/logo.py
Normal file
158
frappy_psi/logo.py
Normal file
@ -0,0 +1,158 @@
|
||||
# *****************************************************************************
|
||||
#
|
||||
# This program is free software; you can redistribute it and/or modify it under
|
||||
# the terms of the GNU General Public License as published by the Free Software
|
||||
# Foundation; either version 2 of the License, or (at your option) any later
|
||||
# version.
|
||||
#
|
||||
# This program is distributed in the hope that it will be useful, but WITHOUT
|
||||
# ANY WARRANTY; without even the implied warranty of MERCHANTABILITY or FITNESS
|
||||
# FOR A PARTICULAR PURPOSE. See the GNU General Public License for more
|
||||
# details.
|
||||
#
|
||||
# You should have received a copy of the GNU General Public License along with
|
||||
# this program; if not, write to the Free Software Foundation, Inc.,
|
||||
# 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
||||
#
|
||||
# Module authors:
|
||||
# Andrea Plank <andrea.plank@psi.ch>
|
||||
# Markus Zolliker <markus.zolliker@psi.ch>
|
||||
#
|
||||
# *****************************************************************************
|
||||
import sys
|
||||
import time
|
||||
from ast import literal_eval
|
||||
from threading import RLock
|
||||
import snap7
|
||||
from frappy.core import Readable, Parameter, FloatRange, HasIO, StringIO, Property, StringType,IDLE, BUSY, WARN, ERROR,Writable, Drivable, BoolType, IntRange, Communicator
|
||||
from frappy.errors import CommunicationFailedError
|
||||
|
||||
|
||||
class IO(Communicator):
|
||||
tcap_client = Property('tcap_client', IntRange())
|
||||
tsap_server = Property('tcap_server', IntRange())
|
||||
ip_address = Property('numeric ip address', StringType())
|
||||
_plc = None
|
||||
_last_try = 0
|
||||
|
||||
def initModule(self):
|
||||
self._lock = RLock()
|
||||
super().initModule()
|
||||
|
||||
def _init(self):
|
||||
if not self._plc:
|
||||
if time.time() < self._last_try + 10:
|
||||
raise CommunicationFailedError('logo PLC not reachable')
|
||||
self._plc = snap7.logo.Logo()
|
||||
prev_stderr = sys.stdout
|
||||
sys.stderr = open('/dev/null', 'w') # suppress output of snap7
|
||||
try:
|
||||
self._plc.connect(self.ip_address, self.tcap_client, self.tsap_server)
|
||||
if self._plc.get_connected():
|
||||
return
|
||||
except Exception:
|
||||
pass
|
||||
finally:
|
||||
sys.stderr = prev_stderr
|
||||
self._plc = None
|
||||
self._last_try = time.time()
|
||||
raise CommunicationFailedError('logo PLC not reachable')
|
||||
|
||||
def communicate(self, cmd):
|
||||
with self._lock:
|
||||
self._init()
|
||||
cmd = cmd.split(maxsplit=1)
|
||||
if len(cmd) == 2:
|
||||
self._plc.write(cmd[0], literal_eval(cmd[1]))
|
||||
try:
|
||||
return self._plc.read(cmd[0])
|
||||
except Exception as e:
|
||||
if self._plc:
|
||||
self.log.exception('error in plc read')
|
||||
self._plc = None
|
||||
raise
|
||||
|
||||
|
||||
class Snap7Mixin(HasIO):
|
||||
ioclass = IO
|
||||
|
||||
def get_vm_value(self, vm_address):
|
||||
return self.io.communicate(vm_address)
|
||||
|
||||
|
||||
def set_vm_value(self, vm_address, value):
|
||||
return self.io.communicate(f'{vm_address} {value}')
|
||||
|
||||
|
||||
class Pressure(Snap7Mixin, Readable):
|
||||
vm_address = Property('VM address', datatype= StringType())
|
||||
value = Parameter('pressure', datatype = FloatRange(unit = 'mbar'))
|
||||
|
||||
pollinterval = 0.5
|
||||
|
||||
def read_value(self):
|
||||
return self.get_vm_value(self.vm_address)
|
||||
|
||||
def read_status(self):
|
||||
return IDLE, ''
|
||||
|
||||
|
||||
class Valve(Snap7Mixin, Drivable):
|
||||
vm_address_input = Property('VM address input', datatype= StringType())
|
||||
vm_address_output = Property('VM address output', datatype= StringType())
|
||||
|
||||
target = Parameter('Valve target', datatype = BoolType())
|
||||
value = Parameter('Value state', datatype = BoolType())
|
||||
|
||||
|
||||
def read_value(self):
|
||||
return self.get_vm_value(self.vm_address_input)
|
||||
|
||||
def write_target(self, target):
|
||||
return self.set_vm_value(self.vm_address_output, target)
|
||||
|
||||
def read_status(self):
|
||||
return IDLE, ''
|
||||
|
||||
|
||||
class FluidMachines(Snap7Mixin, Drivable):
|
||||
vm_address_output = Property('VM address output', datatype= StringType())
|
||||
|
||||
target = Parameter('Valve target', datatype = BoolType())
|
||||
value = Parameter('Value state', datatype = BoolType())
|
||||
|
||||
def read_value(self):
|
||||
return self.get_vm_value(self.vm_address_output)
|
||||
|
||||
def write_target(self, target):
|
||||
return self.set_vm_value(self.vm_address_output, target)
|
||||
|
||||
def read_status(self):
|
||||
return IDLE, ''
|
||||
|
||||
|
||||
class TempSensor(Snap7Mixin, Readable):
|
||||
vm_address = Property('VM address', datatype= StringType())
|
||||
value = Parameter('resistance', datatype = FloatRange(unit = 'Ohm'))
|
||||
|
||||
def read_value(self):
|
||||
return self.get_vm_value(self.vm_address)
|
||||
|
||||
def read_status(self):
|
||||
return IDLE, ''
|
||||
|
||||
|
||||
class HeaterParam(Snap7Mixin, Writable):
|
||||
vm_address = Property('VM address output', datatype= StringType())
|
||||
|
||||
target = Parameter('Heater target', datatype = FloatRange(unit='%'))
|
||||
value = Parameter('Heater Param', datatype = FloatRange(unit='%'))
|
||||
|
||||
def read_value(self):
|
||||
return self.get_vm_value(self.vm_address) * 0.1
|
||||
|
||||
def write_target(self, target):
|
||||
return self.set_vm_value(self.vm_address, round(target * 10)) * 0.1
|
||||
|
||||
def read_status(self):
|
||||
return IDLE, ''
|