An attached property may be defined with mandatory=False.
In this case, when no value or an empty string is given,
<modobj>.<attached_mod> must return None after initialisation.
+ remove 'dispatcher' level from the logger hierarchy on modules
Change-Id: Icee3ae3f9142cd7a910c579ae1ffaa35f93cee03
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/32187
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
in the previous version FloatRange(max=100) was neither working
properly nor complaining, because the maxval=None default was
overriding the value for max.
possible fixes:
- raise an error when min/max used as argument (confusing for
the programmer, as it is a property)
- allow both versions minval/maxval and min/max (more code)
- use min/max and a pylint directive here (the only thing to
take care is not to use the min/max builtin in __init__)
this change uses the last option for the fix
Change-Id: Iff0e0c4d0d7b165003bdeffa67a93a1cd7f29eea
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/31982
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
adds a generic solution for creating parameters with struct datatype
with their members linked to individual parameters.
main use case: ctrlpars
read_*/write_* methods are either created for the main (structed)
parameter based on the corresponding methods of the individual
parameters or the methods for the individual parameters are created
based on the methods of the main parameter
+ disable pylint use-dict-literal
Change-Id: I7f1d9fb3d3b2226b548c2999bbfebe2ba5ac285e
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/31405
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
add module which scans a connection and registers new devices depending
on the answer.
* change module initialization to demand-based
* move code from server to dispatcher
- remove intermediate step in Attached __get__
TODO:
factor out dispatcher (regards to playground)
discuss factoring out of module creation code from server AND
dispatcher
Change-Id: I7af959b99a84c291c526aac067a4e2bf3cd741d4
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/31470
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Enrico Faulhaber <enrico.faulhaber@frm2.tum.de>
Reviewed-by: Georg Brandl <g.brandl@fz-juelich.de>
Reviewed-by: Alexander Zaft <a.zaft@fz-juelich.de>
compatible used sys.float_info.min (smallest representable positive
float) instead of -sys.float_info.max.
so FloatRanges -500,10 and -10,10 were two-way compatible
Since it is correctly set in __init__, no need for the guard here
Change-Id: If693fa69a8b2de1aa52ce702bd282a84a8f4c55a
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/31056
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Georg Brandl <g.brandl@fz-juelich.de>
Reviewed-by: Alexander Zaft <a.zaft@fz-juelich.de>
- in order to work properly, readonly=True in limit parameters
has to be set before creating the write_* method
- more explicit: Use e.g. target_max=Limit()
- fix an error in the loop over the base classes when creating
the check_* method
- more concise error message when a limit is violated
+ fix an error in playground when using persistent parameters
Change-Id: Ibd557b55d6c0d9a2612cda4460b16e3c70e1bc9e
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/31017
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
- treat validation errors of the result of write_ and read_ messages
properly
- add info about the called read_* and write_ methods to the error
message, in case the error is not raised in the outmost method
- as subsequent errors in poll functions are logged only once, log an
info when a poll function succeeds again
- remove DiscouragedConversion error
Change-Id: Ib66e001cc95de8225751a1464a92594c369ceb3f
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/30788
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
* add optional parameter for ValueType: validator
used for checking, if a value meets a criteria (e.g. is dict)
+ InternalParameter, which is not exported and can hold any python value
Change-Id: If39a7a4a8019f2aa1a930e42cbef4fca59163b78
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/30787
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Alexander Zaft <a.zaft@fz-juelich.de>
- include all secop errors from spec
- add doc strings
- make conversion to and from error report nicer
- move all error classes to frappy.errors
- rename errors clashing with built-in errors
Change-Id: I4d882173b020cd4baf862c5891375b691e67e24a
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/30721
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
- check for <param>_min and <param>_max
- customized checks with check_<param> method
the inherited customized check functions are all called in
a sequence, with the possibilty to return True to quit earlier,
no need to use super calls here
Change-Id: I903081abbbad2586c1e8237e303abaa3683ac419
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/30632
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
'Done' was introduced in order to suppress unneccessary
duplicate updates. However, since super calls on access methods are
allowed, it is not nice when such a method returns Done, as this
is not automagically replaced by the current parameter value.
As a consequence:
- using Done is discouraged, but not (yet) removed in all code
- the 'omit_unchanged_within' property is moved from Module to an
internal Parameter property 'update_unchanged'
- its default is moved from a SEC node property to generalConfig
- the 'update_unchanged' parameter property may be set to
'never' for parameters where duplicate updates make no sense
- this property might be set to 'always', for measurements, where
even unchanged values taken from HW should be transmitted
Change-Id: I2847c983ca09c2c4098e402edd08d0c96c3913f4
Reviewed-on: https://forge.frm2.tum.de/review/c/secop/frappy/+/30672
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
- watch is now a command, not a module method
- finish watching with ctrl-C
- watching an io module logs communication
- add bin/frappy-cli to start interactive client
+ remove sorted function from StructOf.format_value
Change-Id: I7dd707473e4534f2d39c5d6afc533c2d872380f8
use mro for status code inheritance
- as a consequence, the decorator class 'StatusCode' is now a
decorator function 'status_code'. snake case is anyway more
common for decorators.
- adapt tests
+ fix an error message
Change-Id: Ib409b963c51e0fe807397ff1d73d77d0147b8580
A value given in config overrides values read from the persistent data file.
To let the loaded parameter have precedence, configure a default only.
The write_<param> method of a persistent parameter is now always called
on startup.
- add tests for persistent behaviour
+ simplify Modules.writeInitParams: remove started_callback argument
Change-Id: I08b49de52e9d9a2ed0918018eb2fe538141a4f5e
- make 'value' a Parameter property instead of an attribute
- use 'value' instead of 'default' property for setting
the initial value in the config file
- removal of initwrite parameter property
this change is the basis of a better implementation
for change 30041 (PersistentParam property 'override_cfg')
Change-Id: I2b82bdd54c2dacb87dcd2b3472004d2f0a730cf0
- use Datatype.validate for converting and checking limits
(used also in properties)
- Datatype.__call__ converts and validates, but without checking
limits (used in setter)
- Datatype.validate may be used to add missing optional struct elements
from previous value (used in Dispatcher._setParameterValue)
- remove problematic range check
+ use shorter formula for converting float to int in ScaledInteger
(leftover from python2 compatibility)
+ improve error messages (strip very long repr(value))
Change-Id: Ib85736fe558ec3370ebce4e1c43f957e3bb0497c
- Change Configuration format to be python-based.
- move config logic to frappy/config.py
- Add first py-config: cryo_cfg.py
- Adapt test to new expected config format
Change-Id: Iaec484e0e1e21ebbb1e5c74b53be6231329ddf71
With the current implementation, we run into a deadlock with the lock
from the state machine interfering with the accessLock on the module.
We can not wait for the state machine to finish while having the
accessLock locked by write_target. As a consequence, when restarting
the state machine we should not wait, but remember the state function
to call and postpone the restart after the cleanup has finished.
For this, we want to know the status before calling the state function.
- create HasState mixin, using doPoll for driving the machine
- StatusCode decorator for assigning a status to a state function
- remove the state machines 'threaded' option
- 'Retry' is now a unique value instead of a class. The retry period
is determined by the (fast) poll interval.
- return 'Finish' instead of None for finishing the machine. returning
None for state function is now an error, as this might happen
easily inadvertently.
Change-Id: Icb31367442f10e98be69af3e05a84f12ce5cc966
- repeated errors on poller are only once logged (per poll
function / read_* method)
- during exception handling, silent=True on a SECoP error indicates
that the error is already logged
+ fix the name of HardwareError
+ add test for consistency of SECoPErrors
+ catch socket.timeout in AsynTcp
Change-Id: I9df6c775cc19553b22a4d6e39591092adf7ff9a1
Reviewed-on: https://forge.frm2.tum.de/review/c/sine2020/secop/playground/+/28139
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
Reviewed-by: Enrico Faulhaber <enrico.faulhaber@frm2.tum.de>
This valve needs 8 turns to open. As the encoder forgets
the number if turns on power cycle, a home switch is
mounte, which engages during the last turn when closing.
The final close position is determined by closing the valve
with a defined motor current/torque.
+ fix an issue in StateMachine.start: the first cycle
must be called after the new state is assigned
Change-Id: I34cd05d10d97b043f9e3126310943b74ee727382
Reviewed-on: https://forge.frm2.tum.de/review/c/sine2020/secop/playground/+/28030
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Enrico Faulhaber <enrico.faulhaber@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
When several poller threads are using the same io, the resposivity
of client requests is reduced, as every thread first finishes
its pending communication requests, before it is the turn of the
request thread. This is solved by using one common poller thread
for all modules sharing the same communicator.
+ fix an issue with overriding a property with a parameter, as
this is the case for pollperiod (cfg was applied to property
instead of overriding parameter)
+ separate setFastPoll arguments into flag and fast interval
+ fix missing announceUpdate call when read function fails
+ fix mechanism for triggering polls after an io connection
reconnected again.
Change-Id: I1115a61fae3de80d18416e61f40b52a0eebb637c
Reviewed-on: https://forge.frm2.tum.de/review/c/sine2020/secop/playground/+/28021
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
- write method may be used internally on a readonly parameter
+ add IDLE, WARN, BUSY and ERROR to secop.core
+ secop.datatype.EnumType: allow 'self' as member name
+ secop.lib.statemachine: log Restart and Stop exceptions only on debug level
+ secop_psi.ccu4.CCU4: explicit conversion to float
+ secop.proxy: remove superfluos and erroneous make_secop_error
Change-Id: I2f13d31ceacd2bde65eab64f8eae4225556c18f5
Reviewed-on: https://forge.frm2.tum.de/review/c/sine2020/secop/playground/+/27963
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Enrico Faulhaber <enrico.faulhaber@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
- Attached checks now for proper base class
- fixes an error in Attached: attached saved in attachedModules
dict instead on the Attached object (which sits on the class!)
+ fix: in testonly mode errors must be logged before returning
+ fix: use repr of exception in poll to check for repeated errors
Change-Id: I141fa107fed48e58b55ddf1e071987656c0f618f
Reviewed-on: https://forge.frm2.tum.de/review/c/sine2020/secop/playground/+/27913
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
- remove secop.poller and basic poller
- regular polls for 'important' parameters done by method doPoll
- all other parameters are polled slower (slowInterval) and
with lower priority (only one at a time when main poll is due)
- nopoll decorator for read_* to disable poll
- enablePoll attribute (default True) for disabling polling a module
- fast polls may be implemented by means of a statemachine
- configurable slow poll interval
+ allow a Parameter to override a Property (parameter
Readable.pollinterval overrides Module.pollinterval)
Change-Id: Ib1b3453041a233678b7c4b4add22ac399670e447
Reviewed-on: https://forge.frm2.tum.de/review/c/sine2020/secop/playground/+/27832
Reviewed-by: Enrico Faulhaber <enrico.faulhaber@frm2.tum.de>
Reviewed-by: Markus Zolliker <markus.zolliker@psi.ch>
Tested-by: Jenkins Automated Tests <pedersen+jenkins@frm2.tum.de>