dil5: working alfa version
Change-Id: Ib6bf2234633cc760fc771a3f5c0beb4cb63a0f6d
This commit is contained in:
@ -55,38 +55,42 @@ class Dilution(HasStates, Drivable):
|
||||
condense_valve = Attached()
|
||||
dump_valve = Attached()
|
||||
|
||||
circulate_pump = Attached()
|
||||
forepump = Attached()
|
||||
compressor = Attached(mandatory=False)
|
||||
turbopump = Attached(mandatory=False)
|
||||
condenseline_valve = Attached()
|
||||
circuitshort_valve = Attached()
|
||||
still_pressure = Attached()
|
||||
still_pressure_turbo = Attached(mandatory=False)
|
||||
|
||||
value = Parameter('current state', EnumType(T), default=0)
|
||||
target = Parameter('target state', EnumType(T), default=0)
|
||||
|
||||
sorbpumped = Parameter('sorb pump done', BoolType(), default=False)
|
||||
dump_pressure = Attached()
|
||||
|
||||
#ls372 = Attached()
|
||||
V5 = Attached() #Name noch ändern!!!
|
||||
p1 = Attached() #Name noch ändern!!!
|
||||
|
||||
condensing_p_low = Parameter('Lower limit for condenseline pressure', FloatRange(unit='mbar'))
|
||||
condensing_p_high = Parameter('Higher limit for condenseline pressure', FloatRange(unit='mbar'))
|
||||
condensing_p_low = Parameter('Lower limit for condenseline pressure',
|
||||
FloatRange(unit='mbar'), readonly=False, default=1200)
|
||||
condensing_p_high = Parameter('Higher limit for condenseline pressure',
|
||||
FloatRange(unit='mbar'), readonly=False, default=1500)
|
||||
dump_target = Parameter('low dump pressure limit indicating end of condensation phase',
|
||||
FloatRange(unit='mbar'), default=20)
|
||||
FloatRange(unit='mbar * min'), readonly=False, default=100)
|
||||
pulse_factor = Parameter('factor for calculating V9 pulse length',
|
||||
FloatRange(unit='mbar'), readonly=False, default=20)
|
||||
end_condense_pressure = Parameter('low condense pressure indicating end of condensation phase',
|
||||
FloatRange(unit='mbar'), default=500)
|
||||
FloatRange(unit='mbar'), readonly=False, default=500)
|
||||
turbo_condense_pressure = Parameter('low condense pressure before turbo start',
|
||||
FloatRange(unit='mbar'), default=900)
|
||||
turbo_still_pressure = Parameter('low still pressure before turbo start',
|
||||
FloatRange(unit='mbar'), default=10)
|
||||
turbo_off_delay = Parameter('wait time after switching turbo off',
|
||||
FloatRange(unit='s'), default=300)
|
||||
FloatRange(unit='mbar'), readonly=False, default=900)
|
||||
safe_turbo_pressure = Parameter('low still pressure before turbo start',
|
||||
FloatRange(unit='mbar'), readonly=False, default=10)
|
||||
turbo_off_speed = Parameter('speed to wait for after switching turbo off',
|
||||
FloatRange(unit='s'), default=60)
|
||||
end_remove_still_pressure = Parameter('pressure reached before end of remove',
|
||||
FloatRange(unit='mbar'), default=1e-4)
|
||||
FloatRange(unit='Hz'), readonly=False, default=200)
|
||||
end_remove_turbo_pressure = Parameter('pressure reached before end of remove (before turbo)',
|
||||
FloatRange(unit='mbar'), readonly=False, default=1e-4)
|
||||
end_remove_pressure = Parameter('pressure reached before end of remove (before fore pump)',
|
||||
FloatRange(unit='mbar'), readonly=False, default=0.02)
|
||||
st = StringType()
|
||||
valve_set = StructOf(close=st, open=st, check_open=st, check_closed=st)
|
||||
condense_valves = Parameter('valve to act when condensing', valve_set)
|
||||
@ -105,10 +109,16 @@ class Dilution(HasStates, Drivable):
|
||||
self.value = Targetstates.SORBPUMP
|
||||
return self.value
|
||||
"""
|
||||
if self.value == self.target:
|
||||
self.log.info('start %s', target.name)
|
||||
if self.value == target:
|
||||
return target # not sure if this is correct. may be a step wants to be repeated?
|
||||
|
||||
self.start_machine(getattr(self, target.name, None))
|
||||
try:
|
||||
self.start_machine(getattr(self, target.name, None))
|
||||
except Exception as e:
|
||||
self.log.exception('error')
|
||||
self.log.info('started %s', target.name)
|
||||
|
||||
return target
|
||||
|
||||
"""
|
||||
@ -150,22 +160,40 @@ class Dilution(HasStates, Drivable):
|
||||
def condense(self, state):
|
||||
"""Führt das Kondensationsverfahren durch."""
|
||||
if state.init:
|
||||
self.value = V.condensing
|
||||
# self.value = V.condensing
|
||||
pumpstate = self.forepump.read_value()
|
||||
if self.turbopump:
|
||||
self.turbopump.write_target(0)
|
||||
self.handle_valves(**self.condense_valves)
|
||||
self._start_time = state.now
|
||||
if not pumpstate: # wait longer for starting fore pump
|
||||
self._start_time += 10
|
||||
return Retry
|
||||
if self.wait_valves():
|
||||
return Retry
|
||||
self.check_valve_result()
|
||||
return Retry
|
||||
return self.condensing
|
||||
|
||||
@status_code(BUSY)
|
||||
def condensing(self, state):
|
||||
if self.condenseline_pressure.read_value() < self.condensing_p_low:
|
||||
self.condense_valve.write_target(1)
|
||||
elif self.condenseline_pressure.read_value() > self.condensing_p_high:
|
||||
self.condense_valve.write_target(0)
|
||||
pdump = self.dump_pressure.value # or self.dump_pressure.read_value() ?
|
||||
pcond = self.condenseline_pressure.read_value()
|
||||
v9 = self.condense_valve.read_value()
|
||||
if v9:
|
||||
if pcond > self.condensing_p_high:
|
||||
self.log.info('shut V9')
|
||||
self.condense_valve.write_target(0)
|
||||
elif pcond < self.condensing_p_low and state.now > self._start_time + 5:
|
||||
pulse_time = 60 * self.pulse_factor / pdump
|
||||
if pulse_time > 59:
|
||||
self.log.info('open V9')
|
||||
self.condense_value.write_target(1)
|
||||
else:
|
||||
self.log.info('V9 pulse %r', pulse_time)
|
||||
self._start_time = state.now
|
||||
self.condense_valve.pulse(pulse_time)
|
||||
|
||||
if self.p1.read_value() > self.dump_target:
|
||||
if pdump > self.dump_target:
|
||||
return Retry
|
||||
|
||||
self.condense_valve.write_target(1)
|
||||
@ -175,6 +203,14 @@ class Dilution(HasStates, Drivable):
|
||||
|
||||
return self.wait_for_condense_line_pressure
|
||||
|
||||
@status_code(BUSY, 'condense (wait before starting turbo)')
|
||||
def condense_wait_before_turbo_start(self, state):
|
||||
if (self.condenseline_pressure.read_value() > self.turbo_condense_pressure
|
||||
and self.still_pressure.read_value() > self.safe_turbo_pressure):
|
||||
return Retry
|
||||
self.turbopump.write_target(1)
|
||||
return self.wait_for_condense_line_pressure
|
||||
|
||||
@status_code(BUSY)
|
||||
def wait_for_condense_line_pressure(self, state):
|
||||
if self.condenseline_pressure.read_value() > self.end_condense_pressure:
|
||||
@ -182,14 +218,6 @@ class Dilution(HasStates, Drivable):
|
||||
self.condense_valve.write_target(0)
|
||||
return self.circulate
|
||||
|
||||
@status_code(BUSY, 'condense (wait before starting turbo)')
|
||||
def condense_wait_before_turbo_start(self, state):
|
||||
if (self.condenseline_pressure.read_value() > self.turbo_condense_pressure
|
||||
and self.still_pressure.read_value() > self.turbo_still_pressure):
|
||||
return Retry
|
||||
self.turbopump.write_target(1)
|
||||
return self.wait_for_condense_line_pressure
|
||||
|
||||
@status_code(BUSY)
|
||||
def circulate(self, state):
|
||||
"""Zirkuliert die Mischung."""
|
||||
@ -206,18 +234,15 @@ class Dilution(HasStates, Drivable):
|
||||
"""Entfernt die Mischung."""
|
||||
|
||||
if state.init:
|
||||
self.condenseline_valve.write_target(0)
|
||||
self.dump_valve.write_target(1)
|
||||
self.handle_valves(**self.remove_valves)
|
||||
if self.turbopump is not None:
|
||||
self._start_time = state.now
|
||||
self.turbopump.write_target(0)
|
||||
return Retry
|
||||
|
||||
if self.turbopump is not None:
|
||||
self.turbopump.write_target(0)
|
||||
|
||||
if (state.now - self._start_time < self.turbo_off_delay
|
||||
or self.turbopump.read_speed() > self.turbo_off_speed):
|
||||
# if (state.now - self._start_time < self.turbo_off_delay or
|
||||
if self.turbopump.read_speed() > self.turbo_off_speed:
|
||||
return Retry
|
||||
|
||||
self.circuitshort_valve.write_target(1)
|
||||
@ -229,27 +254,30 @@ class Dilution(HasStates, Drivable):
|
||||
|
||||
@status_code(BUSY, 'remove (wait for still pressure low)')
|
||||
def remove_wait_for_still_pressure(self, state):
|
||||
if self.still_pressure.read_value() > self.turbo_still_pressure:
|
||||
if self.still_pressure.read_value() > self.safe_turbo_pressure:
|
||||
return Retry
|
||||
self.turbopump.write_target(1)
|
||||
return self.remove_endsequence
|
||||
|
||||
@status_code(BUSY)
|
||||
def remove_endsequence(self, state):
|
||||
if self.still_pressure.read_value() > self.end_remove_still_pressure:
|
||||
if (self.still_pressure_turbo and
|
||||
self.still_pressure_turbo.read_value() > self.end_remove_turbo_pressure):
|
||||
return Retry
|
||||
if self.still_pressure.read_value() > self.end_remove_pressure:
|
||||
return Retry
|
||||
self.circuitshort_valve.write_target(0)
|
||||
self.dump_valve.write_target(0)
|
||||
|
||||
if self.compressor is not None:
|
||||
self.compressor.write_target(0)
|
||||
self.circulate_pump.write_target(0)
|
||||
return self.close_valves_after_remove
|
||||
|
||||
@status_code(BUSY)
|
||||
def close_valves_after_remove(self, state):
|
||||
if state.init:
|
||||
self.handle_valves(**self.valves_after_remove)
|
||||
self.turbopump.write_target(0)
|
||||
if self.wait_valves():
|
||||
return Retry
|
||||
self.check_valve_result()
|
||||
@ -313,7 +341,13 @@ class DIL5(Dilution):
|
||||
'close': 'V2 V4 V9',
|
||||
'check_closed': 'MV10 MV13 MV8 MVB MV2',
|
||||
'check_open': 'MV1 MV3a MV3b GV1 MV9 MV11 MV12 MV14',
|
||||
'open': 'V1 V5 compressor pump',
|
||||
'open': 'V1 V5 compressor forepump',
|
||||
}
|
||||
remove_valves = {
|
||||
'close': 'V1 V2 V9',
|
||||
'check_closed': 'MV10 MV13 MV8 MVB MV2',
|
||||
'check_open': 'MV1 MV3a MV3b GV1 MV9 MV11 MV12 MV14',
|
||||
'open': 'V4 V5 compressor forepump',
|
||||
}
|
||||
valves_after_remove = {
|
||||
'close': 'V1 V2 V4 V5 V9',
|
||||
@ -330,6 +364,7 @@ class DIL5(Dilution):
|
||||
|
||||
|
||||
class Interlock(LogoMixin, AddrMixin, Readable):
|
||||
dil = Attached()
|
||||
value = AddrParam('interlock state (bitmap)',
|
||||
IntRange(0, 31), addr='V414', readonly=False)
|
||||
p5lim = AddrParam('safety limit on p5 to protect forepump',
|
||||
@ -349,6 +384,15 @@ class Interlock(LogoMixin, AddrMixin, Readable):
|
||||
reset_param = Property('addr for reset', StringType(), default='V418.1')
|
||||
_mismatch = None
|
||||
_prefix = ''
|
||||
_actuators = None
|
||||
|
||||
def initModule(self):
|
||||
super().initModule()
|
||||
self._actuators = {}
|
||||
for actions in self.conditions.values():
|
||||
for modname in actions:
|
||||
if modname not in self._actuators:
|
||||
self._actuators[modname] = self.secNode.modules[modname]
|
||||
|
||||
def doPoll(self):
|
||||
self.read_status() # this includes read_value
|
||||
@ -362,9 +406,8 @@ class Interlock(LogoMixin, AddrMixin, Readable):
|
||||
"""reset the interlock"""
|
||||
self._prefix = ''
|
||||
self.set_vm_value(self.reset_param, 1)
|
||||
for actions in self.conditions.values():
|
||||
for mname in actions:
|
||||
self.secNode.modules[mname].reset_fault()
|
||||
for actuator in self._actuators.values():
|
||||
actuator.reset_fault()
|
||||
if self.read_value() != 0:
|
||||
raise HardwareError('can not clear status byte')
|
||||
self.set_vm_value(self.reset_param, 0)
|
||||
@ -375,13 +418,14 @@ class Interlock(LogoMixin, AddrMixin, Readable):
|
||||
self._mismatch = set()
|
||||
bits = self.read_value()
|
||||
if bits:
|
||||
self.dil.stop()
|
||||
keys = formatStatusBits(bits, self.conditions, 1)
|
||||
statustext = []
|
||||
for key in keys:
|
||||
actions = self.conditions[key]
|
||||
statustext.append(f"{' and '.join(actions)} {key}")
|
||||
for module, value in actions.items():
|
||||
modobj = self.secNode.modules[module]
|
||||
modobj = self._actuators[module]
|
||||
if modobj.target != value:
|
||||
self._prefix = 'switched '
|
||||
modobj.set_fault(value, f'switched {key}')
|
||||
|
@ -118,7 +118,7 @@ class DigitalActuator(LogoMixin, Writable):
|
||||
|
||||
def initialReads(self):
|
||||
super().initialReads()
|
||||
self.target = self.value
|
||||
self.target = self.read_value()
|
||||
|
||||
def set_fault(self, value, statustext):
|
||||
"""on a fault condition, set target to value
|
||||
@ -229,6 +229,10 @@ class Value(LogoMixin, Readable):
|
||||
return IDLE, ''
|
||||
|
||||
|
||||
class DigitalValue(Value):
|
||||
value = Parameter('airpressure state', datatype=BoolType())
|
||||
|
||||
|
||||
# TODO: the following classes are too specific, they have to be moved
|
||||
|
||||
class Pressure(LogoMixin, Drivable):
|
||||
|
@ -129,7 +129,7 @@ class PfeifferMixin(HasIO):
|
||||
|
||||
|
||||
class RPT200(PfeifferMixin, Readable):
|
||||
value = Parameter('Pressure', FloatRange(unit='hPa'))
|
||||
value = Parameter('Pressure', FloatRange(unit='mbar'))
|
||||
|
||||
def read_value(self):
|
||||
return self.data_request_u_expo_new(740)
|
||||
@ -143,11 +143,11 @@ class RPT200(PfeifferMixin, Readable):
|
||||
|
||||
|
||||
class TCP400(PfeifferMixin, Drivable, Readable):
|
||||
speed= Parameter('Rotational speed', FloatRange(unit = 'Hz'), readonly = False)
|
||||
speed= Parameter('Rotational speed', FloatRange(unit='Hz'), readonly = False)
|
||||
target= Parameter('Pumping station', BoolType())
|
||||
current= Parameter('Current consumption', FloatRange(unit = '%'))
|
||||
current= Parameter('Current consumption', FloatRange(unit='%'))
|
||||
value = Parameter('Turbopump state', BoolType())
|
||||
temp = Parameter('temp', FloatRange(unit = 'C'))
|
||||
temp = Parameter('temp', FloatRange(unit='C'))
|
||||
|
||||
def read_temp (self):
|
||||
return self.data_request_u_int(326)
|
||||
|
Reference in New Issue