Convert example configs to python
Fixes: #4627 Change-Id: I1049af9fa2f3f9ec06e55811dc9ecfa5f359c805
This commit is contained in:
88
cfg/sim_mlz_cci3he1_cfg.py
Normal file
88
cfg/sim_mlz_cci3he1_cfg.py
Normal file
@ -0,0 +1,88 @@
|
||||
Node('cci3he1',
|
||||
'[sim] cci3he box of MLZ Sample environment group\n'
|
||||
'\n'
|
||||
'Controls an 3He insert with an ls370 and an PLC controlling \n'
|
||||
'the compressor and the valves of the gas handling.',
|
||||
'tcp://10767',
|
||||
)
|
||||
|
||||
Mod('T_cci3he1',
|
||||
'frappy.simulation.SimDrivable',
|
||||
'Main temperature control node of cci3he1.\n'
|
||||
'\n'
|
||||
'Controls the regulation loop of the ls370.',
|
||||
value = Param(default=300, datatype={"type":"double","unit":"K"}),
|
||||
target = Param(default=300, datatype={"type":"double", "min":0, "max":300, "unit":"K"}),
|
||||
extra_params='ramp',
|
||||
ramp = Param(default=60,
|
||||
datatype={"type":"double","min":0,"max":600,"unit":"K/min"},
|
||||
description='target ramping speed in K/min.',
|
||||
),
|
||||
meaning=["temperature_regulation",40]
|
||||
)
|
||||
|
||||
Mod('T_cci3he1_A',
|
||||
'frappy.simulation.SimReadable',
|
||||
'3He pot temperature sensor. Also used for the regulation.',
|
||||
visibility='expert',
|
||||
value = Param(default=300, datatype={"type":"double","unit":"K"}),
|
||||
meaning=["temperature",38]
|
||||
)
|
||||
|
||||
Mod('T_cci3he1_B',
|
||||
'frappy.simulation.SimReadable',
|
||||
'(optional) sample temperature sensor close to sample.',
|
||||
visibility='user',
|
||||
value = Param(default=300, datatype={"type":"double","unit":"K"}),
|
||||
meaning=["temperature",39]
|
||||
)
|
||||
|
||||
Mod('cci3he1_p1',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Pressure at turbo pump inlet.',
|
||||
value = Param(default=2e-3, datatype={"type":"double","unit":"mbar"}),
|
||||
visibility='expert',
|
||||
)
|
||||
|
||||
Mod('cci3he1_p2',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Pressure at turbo pump outlet.',
|
||||
value = Param(default=9.87, datatype={"type":"double","unit":"mbar"}),
|
||||
visibility='expert',
|
||||
)
|
||||
|
||||
Mod('cci3he1_p3',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Pressure at compressor inlet.',
|
||||
value = Param(default=19.99, datatype={"type":"double","unit":"mbar"}),
|
||||
visibility='expert',
|
||||
)
|
||||
|
||||
Mod('cci3he1_p4',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Pressure at compressor outlet.',
|
||||
value = Param(default=999, datatype={"type":"double","unit":"mbar"}),
|
||||
visibility='expert',
|
||||
)
|
||||
|
||||
Mod('cci3he1_p5',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Pressure in dump tank.',
|
||||
value = Param(default=567, datatype={"type":"double","unit":"mbar"}),
|
||||
visibility='expert',
|
||||
)
|
||||
|
||||
Mod('cci3he1_p6',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Pressure in the vacuum dewar (ivc).',
|
||||
value = Param(default=1e-3, datatype={"type":"double","unit":"mbar"}),
|
||||
visibility='expert',
|
||||
)
|
||||
|
||||
Mod('cci3he1_flow',
|
||||
'frappy.simulation.SimReadable',
|
||||
'Gas Flow (condensing line).',
|
||||
value = Param(default=12.34, datatype={"type":"double","unit":"mln/min"}),
|
||||
visibility='expert',
|
||||
)
|
||||
# note: all valves and switches are missing: use VNC to control them
|
Reference in New Issue