frappy_psi.thermofisher: add limits
also switch off control when T is outside limits by more than security_margin Change-Id: I3df513c7bc36ca23bf249c61fdfadb39870db3a5
This commit is contained in:
@@ -20,7 +20,7 @@
|
|||||||
"""bath thermostat Thermo Scientific™ ARCTIC A10 Refrigerated Circulators"""
|
"""bath thermostat Thermo Scientific™ ARCTIC A10 Refrigerated Circulators"""
|
||||||
|
|
||||||
from frappy.core import Command, StringIO, Parameter, HasIO, \
|
from frappy.core import Command, StringIO, Parameter, HasIO, \
|
||||||
Drivable, FloatRange, IDLE, BUSY, ERROR, WARN, BoolType
|
Drivable, FloatRange, IDLE, BUSY, ERROR, WARN, BoolType, Limit
|
||||||
from frappy.extparams import StructParam
|
from frappy.extparams import StructParam
|
||||||
from frappy_psi.convergence import HasConvergence
|
from frappy_psi.convergence import HasConvergence
|
||||||
|
|
||||||
@@ -34,7 +34,7 @@ class TemperatureLoopA10(HasConvergence, HasIO, Drivable):
|
|||||||
ioClass = ThermFishIO
|
ioClass = ThermFishIO
|
||||||
value = Parameter('temperature', unit='degC')
|
value = Parameter('temperature', unit='degC')
|
||||||
target = Parameter('setpoint/target', datatype=FloatRange, unit='degC', default=0)
|
target = Parameter('setpoint/target', datatype=FloatRange, unit='degC', default=0)
|
||||||
control_active = Parameter('circilation and control is on', BoolType(), default=False)
|
control_active = Parameter('circulation and control is on', BoolType(), default=False)
|
||||||
ctrlpars = StructParam('control parameters struct', dict(
|
ctrlpars = StructParam('control parameters struct', dict(
|
||||||
p_heat = Parameter('proportional heat parameter', FloatRange()),
|
p_heat = Parameter('proportional heat parameter', FloatRange()),
|
||||||
i_heat = Parameter('integral heat parameter', FloatRange()),
|
i_heat = Parameter('integral heat parameter', FloatRange()),
|
||||||
@@ -43,6 +43,11 @@ class TemperatureLoopA10(HasConvergence, HasIO, Drivable):
|
|||||||
i_cool = Parameter('integral cool parameter', FloatRange()),
|
i_cool = Parameter('integral cool parameter', FloatRange()),
|
||||||
d_cool = Parameter('derivative cool parameter', FloatRange()),
|
d_cool = Parameter('derivative cool parameter', FloatRange()),
|
||||||
), readonly=False)
|
), readonly=False)
|
||||||
|
target_min = Limit(default=-99)
|
||||||
|
target_max = Limit(default=199)
|
||||||
|
security_margin = Parameter('security margin for automatic switch off',
|
||||||
|
FloatRange(), default=1)
|
||||||
|
_off_reason = None
|
||||||
|
|
||||||
status_messages = [
|
status_messages = [
|
||||||
(ERROR, 'high tempr. cutout fault', 2, 0),
|
(ERROR, 'high tempr. cutout fault', 2, 0),
|
||||||
@@ -89,7 +94,12 @@ class TemperatureLoopA10(HasConvergence, HasIO, Drivable):
|
|||||||
"""
|
"""
|
||||||
Reading internal temperature sensor value.
|
Reading internal temperature sensor value.
|
||||||
"""
|
"""
|
||||||
return self.get_par('T')
|
value = self.get_par('T')
|
||||||
|
if value > self.target_max + self.security_margin:
|
||||||
|
self.switch_control_off('T above limit')
|
||||||
|
elif value < self.target_min - self.security_margin:
|
||||||
|
self.switch_control_off('T below limit')
|
||||||
|
return value
|
||||||
|
|
||||||
def read_status(self):
|
def read_status(self):
|
||||||
""" convert from RUFS Command: Description of Bits
|
""" convert from RUFS Command: Description of Bits
|
||||||
@@ -132,15 +142,24 @@ class TemperatureLoopA10(HasConvergence, HasIO, Drivable):
|
|||||||
# else our own status
|
# else our own status
|
||||||
return BUSY, conv_status[1] if 'tolerance' in conv_status[1] else status_msg
|
return BUSY, conv_status[1] if 'tolerance' in conv_status[1] else status_msg
|
||||||
return status_type, status_msg
|
return status_type, status_msg
|
||||||
return WARN, 'circulation off'
|
return WARN, (self._off_reason or 'circulation and control off')
|
||||||
|
|
||||||
def read_control_active(self):
|
def read_control_active(self):
|
||||||
return int(self.get_par('O'))
|
return int(self.get_par('O'))
|
||||||
|
|
||||||
|
def initialReads(self):
|
||||||
|
super().initialReads()
|
||||||
|
self.target_max = min(self.target_max, self.get_par('RHTF'))
|
||||||
|
self.target_min = max(self.target_min, self.get_par('RLTF'))
|
||||||
|
|
||||||
|
def switch_control_off(self, reason=None):
|
||||||
|
self._off_reason = reason
|
||||||
|
self.control_active = self.set_par('O', 0)
|
||||||
|
|
||||||
@Command
|
@Command
|
||||||
def control_off(self):
|
def control_off(self):
|
||||||
"""switch control and circulation off"""
|
"""switch control and circulation off"""
|
||||||
self.control_active = self.set_par('O', 0)
|
self.switch_control_off()
|
||||||
|
|
||||||
def read_target(self):
|
def read_target(self):
|
||||||
return self.get_par('S')
|
return self.get_par('S')
|
||||||
|
|||||||