# EPICS Database for streamdevice specific to measurement channels # # Macros # INSTR - Prefix # NAME - the device name, e.g. EL737 # PROTO - Stream device protocol file # ASYN_PORT - Low level Asyn IP Port to DAQ # CHANNEL - the number associated with the measurment channel ################################################################################ # Status Variables # Trigger a change in status as clearing record(bo, "$(INSTR)$(NAME):T$(CHANNEL)") { field(DESC, "Trigger Clearing Status") field(VAL, 1) field(OUT, "$(INSTR)$(NAME):S$(CHANNEL) PP") } # Trigger a change in status as value returned to 0 record(seq, "$(INSTR)$(NAME):O$(CHANNEL)") { field(DESC, "Trigger Returned to 0 Status") field(LNK0, "$(INSTR)$(NAME):S$(CHANNEL) PP") field(DO0, 0) field(SELM, "Specified") field(SELL, "$(INSTR)$(NAME):M$(CHANNEL).VAL") } # Current Status of Channel, i.e. is it ready to count? record(bi, "$(INSTR)$(NAME):S$(CHANNEL)") { field(DESC, "Channel Status") field(VAL, 0) field(ZNAM, "OK") field(ONAM, "CLEARING") } ################################################################################ # Count Commands record(longout, "$(INSTR)$(NAME):C$(CHANNEL)") { field(DESC, "Clear the current channel count") field(DTYP, "stream") field(OUT, "@$(PROTO) clearChannel($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)") field(FLNK, "$(INSTR)$(NAME):T$(CHANNEL)") } record(ao,"$(INSTR)$(NAME):THRESH$(CHANNEL)") { field(DESC, "Sets min rate for counting to proceed") field(OMSL, "supervisory") field(OROC, "0") field(OUT, "@$(PROTO) setMinRate($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)") field(DTYP, "stream") } ################################################################################ # Read all monitors values record(longin, "$(INSTR)$(NAME):M$(CHANNEL)") { field(DESC, "DAQ CH$(CHANNEL)") field(EGU, "cts") field(FLNK, "$(INSTR)$(NAME):O$(CHANNEL)") } record(ai, "$(INSTR)$(NAME):R$(CHANNEL)") { field(DESC, "Rate of DAQ CH$(CHANNEL)") field(INP, "@$(PROTO) readRate($(INSTR)$(NAME):, $(CHANNEL)) $(ASYN_PORT)") field(DTYP, "stream") field(EGU, "cts/sec") field(SCAN, "1 second") }