OWIS stage with ED7062 CSV and TR SSI encoder

This folder configures the OWIS linear stage with an ED7062 two-channel stepper drive in cyclic synchronous velocity (CSV) mode. ECMC closes the position loop using the TR-Electronic LT140-S absolute SSI linear encoder. The configured engineering unit is millimetres.

The configuration was derived from ../EL7062_CSV, but all drive declarations and descriptions in this folder refer to the ED7062.

ED7062 declarations

Setting Configured value
Hardware description HW_DESC=ED7062
EtherCAT slave position 10
Used channel Channel 1
Unused channel Channel 2, Generic-Ch-Not-Used
Axis mode CSV
Drive setpoint velocitySetpoint01
Drive/control type 1, DS402/advanced drive
Internal position positionActual01
Digital limit inputs binaryInputs01.0 and .1

The declaration and PDO pattern follow PSI's ED7062 CSV example:

The copied EL7062-specific CSV firmware warning is intentionally not presented as an ED7062 fact. The files contain no evidence about the installed ED7062 firmware; its disable/re-enable behaviour must still be checked on hardware.

System configuration

Function Configured hardware or setting
ECMC ecmccfg 11.0.8, engineering mode enabled, EC_RATE=500 Hz
Motion axis Axis 1, EPICS name M1, description OWIS Stage ED7062
Stepper drive ED7062 at EtherCAT slave 10, channel 1, CSV mode
Motor OWIS two-phase stepper; 0.8 A maximum, 0.5 A standby, 48 V nominal, 7.5 ohm/phase, 3080 uH, 400 full steps/revolution
Primary feedback TR-Electronic LT140-S on EL5042 slave 2, channel 1
Limit-switch supply EL2008 slave 5, channel 4 switched output
Position unit mm

CSV drive scaling

The ED7062 CSV velocity setpoint uses a signed 32-bit range. With a stage travel of 1 mm/revolution and a 500 Hz EtherCAT rate:

drive.numerator   = 1 mm/revolution * 500 cycles/second = 500
drive.denominator = 2^31 = 2147483648

raw velocity = commanded velocity * 2147483648 / 500
commanded velocity = raw velocity * 500 / 2147483648 mm/s

At the configured default velocity of 3 mm/s, the nominal raw command is about 12884902 counts. Confirm the live setpoint and actual velocity during reduced- speed commissioning.

Encoder configuration

Primary SSI encoder

The EL5042 channel is configured by SDO before the axis is loaded:

  • SSI mode, binary coding
  • 24 position bits, no multiturn or offset bits
  • Status bits disabled and CRC inversion enabled
  • 1 MHz clock
  • 9.0 V encoder supply
  • Scale: 1 / 10000 mm/count, equivalent to 0.1 um/count
  • Absolute offset: -11.826 mm
  • Counter overflow/wraparound disabled

The 10000 counts/mm value is labelled as interferometer-calibrated in cfg/axis.yaml. The files do not establish its calibration uncertainty or confirm the current mechanical datum.

ED7062 internal counter

  • Secondary encoder; the SSI encoder remains primary feedback
  • Scale: 1 / 1048576 mm/count for a 1 mm/revolution stage
  • Incremental, 32-bit counter
  • Referenced to the primary SSI encoder at startup
  • Position PDO: positionActual01

Position controller

In CSV mode, ECMC generates the trajectory and closes the position loop using the SSI encoder. The ED7062 closes its internal velocity and current loops.

The configured ECMC controller gains are:

Parameter Value
Kp 14
Ki 1.6
Kd 0.5
Kff 1

These values differ substantially from the copied EL7062 configuration and are treated as local tuning values. Their origin and stability are not established by the files. Validate them at reduced current and velocity before normal motion.

Motion and monitoring

Characteristic Configured value
Trajectory profile Trapezoidal (type: 0)
Default velocity 3 mm/s
Default acceleration/deceleration 2 mm/s^2
Emergency deceleration 10 mm/s^2
Jog velocity 1 mm/s
Backward software limit -1 mm
Forward software limit 95 mm
Maximum monitored velocity 10 mm/s
Following-error tolerance 0.5 mm for 10 EtherCAT cycles
At-target tolerance 0.002 mm for 50 EtherCAT cycles
Auto-enable timeout 10 s
Automatic disable delay 10 s idle

The hardware limits use ED7062 channel 1 inputs:

  • Backward limit: binaryInputs01.0
  • Forward limit: binaryInputs01.1
  • Limit-switch power: EL2008 channel 4

Home and external interlock are constant true because no corresponding sensors are assigned. Software limits and axis monitoring remain enabled.

Automatic FAT motion sequence

startup.cmd loads cfg/code_2.plc at a 500 ms PLC sample period. A rising edge on doMotion starts the sequence.

  • Move velocity: 2 mm/s
  • Acceleration and deceleration: 3 mm/s^2
  • Ten measurement positions from 1.0000 mm to 90.0000 mm
  • A preliminary position 0.2 mm below each measurement point
  • Intermediate dwell: 2 PLC scans, nominally 1 s
  • Measurement dwell: 12 PLC scans, nominally 6 s
  • Five forward/backward cycles
# Start
caput aik-motion-pc5:Set-M1-DoMtn-RB 1

# Stop
caput aik-motion-pc5:Set-M1-DoMtn-RB 0

Remaining commissioning issues

  • The motor component declares R_COIL_MOHM=7500, while the drive-controller component declares R_COIL_MOHM=2471. Resolve this mismatch before enabling motion. Use motor measurements and ED7062 autotune results for the installed motor rather than assuming the copied values are valid.
  • Confirm that HW_DESC=ED7062 matches the installed device and the available ecmccfg 11.0.8 hardware definition before starting the IOC.
  • Confirm the EL5042 output is 9.0 V and permitted by the exact encoder order code before connecting the encoder.
  • Confirm motor direction and SSI direction before closing the position loop. A sign error can command immediate motion in the wrong direction.
  • The PLC accepts busy-low plus attarget as move completion without first latching that busy became high. Validate or correct this handshake before unattended operation.
  • Static review does not prove PDO compatibility, controller stability, limit polarity, or safe operation on the target hardware.

Relevant files

  • startup.cmd - EL5042 SDOs, ED7062 declaration, motor/controller components, axis loading, and PLC loading
  • cfg/axis.yaml - ED7062 CSV mapping, primary SSI feedback, trajectory, controller, limits, and monitoring
  • cfg/enc_open_loop.yaml - secondary ED7062 internal counter
  • cfg/code_2.plc - active FAT motion sequence
  • cfg/code.plc - alternate older sequence, not loaded by startup.cmd

Commissioning sequence

  1. Confirm that the IOC loads ECMC/ED7062_CSV/startup.cmd.
  2. Verify that EtherCAT slave 10 is the installed ED7062 and that channel 1 is connected to the motor while channel 2 is unused.
  3. Resolve the motor-resistance mismatch and run the appropriate drive autotune.
  4. Confirm 9.0 V at the EL5042 connector before attaching the encoder.
  5. With motion disabled, verify SSI readiness, position, status bits, ED7062 counter, limit inputs, and limit-switch supply.
  6. Enable at reduced current and command a very low positive motion. Confirm motor direction, SSI direction, velocitySetpoint01, and actual velocity.
  7. Verify the 500/2147483648 CSV scaling against live setpoint and velocity.
  8. Tune and validate the ECMC position controller, following error, settling, software limits, and stop behaviour.
  9. Test disable/re-enable counter continuity on the installed ED7062 firmware.
  10. Validate the PLC execute/busy handshake before running the complete FAT sequence.